Step 5. Install the 7mm drive cage to the riser cage.
Figure 159. 7mm drive cage installation
a. Align the left-side pin on the 7mm drive cage with the positioning slot on the securing clip, the
two holes on the side brackets of the 7mm drive cage with the two holes on the front of the
riser cage.
b. Install the two screws to secure the 7mm drive cage in place
Step 6. Install the riser 2 assembly to the riser 2 slot on the system board. See “Install a PCIe adapter and
riser 1/2 assembly” on page 350.
After you finish
1. Reinstall all the drives and fillers (if any) into the drive bays. See “Install a hot-swap drive” on page 178.
2. Complete the parts replacement. See “Complete the parts replacement” on page 397.
344
ThinkSystem SR665 Maintenance Manual
Содержание 7D2V
Страница 1: ...ThinkSystem SR665 Maintenance Manual Machine Types 7D2V and 7D2W ...
Страница 6: ...iv ThinkSystem SR665 Maintenance Manual ...
Страница 10: ...viii ThinkSystem SR665 Maintenance Manual ...
Страница 66: ...56 ThinkSystem SR665 Maintenance Manual ...
Страница 82: ...Figure 25 Cable routing for configuration 4 72 ThinkSystem SR665 Maintenance Manual ...
Страница 111: ...BP 3 NVMe 2 3 PCIe 3 BP 3 NVMe 4 5 PCIe 7 BP3 NVMe 6 7 PCIe 8 Chapter 3 Internal cable routing 101 ...
Страница 123: ...Figure 40 Cable routing for configuration 1 Chapter 3 Internal cable routing 113 ...
Страница 126: ...Figure 42 Cable routing for configuration 2 116 ThinkSystem SR665 Maintenance Manual ...
Страница 131: ...Figure 45 Cable routing for configuration 6 Chapter 3 Internal cable routing 121 ...
Страница 133: ...Chapter 3 Internal cable routing 123 ...
Страница 148: ...138 ThinkSystem SR665 Maintenance Manual ...
Страница 167: ...Chapter 4 Hardware replacement procedures 157 ...
Страница 216: ...Step 2 Connect the cables to the backplanes See 7mm drives on page 64 206 ThinkSystem SR665 Maintenance Manual ...
Страница 237: ...Chapter 4 Hardware replacement procedures 227 ...
Страница 299: ...Chapter 4 Hardware replacement procedures 289 ...
Страница 300: ...On the 2 5 inch middle drive cage 290 ThinkSystem SR665 Maintenance Manual ...
Страница 339: ...Chapter 4 Hardware replacement procedures 329 ...
Страница 364: ...354 ThinkSystem SR665 Maintenance Manual ...
Страница 408: ...398 ThinkSystem SR665 Maintenance Manual ...
Страница 431: ...5 Reseat the failing device 6 Replace the failing device Chapter 5 Problem determination 421 ...
Страница 444: ...434 ThinkSystem SR665 Maintenance Manual ...
Страница 445: ... Copyright Lenovo 2019 435 ...
Страница 448: ...438 ThinkSystem SR665 Maintenance Manual ...
Страница 449: ... Copyright Lenovo 2019 439 ...
Страница 452: ...442 ThinkSystem SR665 Maintenance Manual ...
Страница 464: ...454 ThinkSystem SR665 Maintenance Manual ...
Страница 465: ......
Страница 466: ......