Procedure
Step 1. Touch the static-protective package that contains the new riser card to any unpainted surface on
the outside of the server. Then, take the new riser card out of the package and place it on a static-
protective surface.
Step 2. Prepare your server.
1. Power off the server.
2. Remove the top cover. See “Remove the top cover” on page 392.
3. If your server comes with an air baffle, remove it first. See “Remove the air baffle” on page 149.
4. Record all the cables that are passing through the cable wall brackets and disconnect them .
Then, remove any of the following components that are installed on the system board and put
them in a safe, static-protective place.
• “M.2 module” on page 234
• “RAID super capacitor modules” on page 291
• “Middle drive cage” on page 242
• “Rear drive cage” on page 320
• “Backplanes” on page 181
Step 3. Remove the cable wall brackets.
Figure 52. Cable wall brackets removal
a. Remove the two screws.
b. Lift up the brakets from the system board as shown.
After you finish
1. Connect any cables. See Chapter 3 “Internal cable routing” on page 57.
2. Complete the parts replacement. See “Complete the parts replacement” on page 397.
156
ThinkSystem SR665 Maintenance Manual
Содержание 7D2V
Страница 1: ...ThinkSystem SR665 Maintenance Manual Machine Types 7D2V and 7D2W ...
Страница 6: ...iv ThinkSystem SR665 Maintenance Manual ...
Страница 10: ...viii ThinkSystem SR665 Maintenance Manual ...
Страница 66: ...56 ThinkSystem SR665 Maintenance Manual ...
Страница 82: ...Figure 25 Cable routing for configuration 4 72 ThinkSystem SR665 Maintenance Manual ...
Страница 111: ...BP 3 NVMe 2 3 PCIe 3 BP 3 NVMe 4 5 PCIe 7 BP3 NVMe 6 7 PCIe 8 Chapter 3 Internal cable routing 101 ...
Страница 123: ...Figure 40 Cable routing for configuration 1 Chapter 3 Internal cable routing 113 ...
Страница 126: ...Figure 42 Cable routing for configuration 2 116 ThinkSystem SR665 Maintenance Manual ...
Страница 131: ...Figure 45 Cable routing for configuration 6 Chapter 3 Internal cable routing 121 ...
Страница 133: ...Chapter 3 Internal cable routing 123 ...
Страница 148: ...138 ThinkSystem SR665 Maintenance Manual ...
Страница 167: ...Chapter 4 Hardware replacement procedures 157 ...
Страница 216: ...Step 2 Connect the cables to the backplanes See 7mm drives on page 64 206 ThinkSystem SR665 Maintenance Manual ...
Страница 237: ...Chapter 4 Hardware replacement procedures 227 ...
Страница 299: ...Chapter 4 Hardware replacement procedures 289 ...
Страница 300: ...On the 2 5 inch middle drive cage 290 ThinkSystem SR665 Maintenance Manual ...
Страница 339: ...Chapter 4 Hardware replacement procedures 329 ...
Страница 364: ...354 ThinkSystem SR665 Maintenance Manual ...
Страница 408: ...398 ThinkSystem SR665 Maintenance Manual ...
Страница 431: ...5 Reseat the failing device 6 Replace the failing device Chapter 5 Problem determination 421 ...
Страница 444: ...434 ThinkSystem SR665 Maintenance Manual ...
Страница 445: ... Copyright Lenovo 2019 435 ...
Страница 448: ...438 ThinkSystem SR665 Maintenance Manual ...
Страница 449: ... Copyright Lenovo 2019 439 ...
Страница 452: ...442 ThinkSystem SR665 Maintenance Manual ...
Страница 464: ...454 ThinkSystem SR665 Maintenance Manual ...
Страница 465: ......
Страница 466: ......