Procedure
Step 1. Remove the top cover. See “Remove the top cover” on page 392.
Step 2. If your server comes with an air baffle, remove it. See “Remove the air baffle” on page 149.
Step 3. Remove the memory module from the slot.
Figure 109. Memory module removal
a. Open the retaining clip on each end of the memory module slot.
Attention:
To avoid breaking the retaining clips or damaging the memory module slots, handle
the clips gently.
b. Grasp the memory module at both ends and carefully lift it out of the slot.
After you finish
1. Install a memory module filler or a new memory module to cover the slot. See “Install a memory module”
2. If you are instructed to return the old memory module, follow all packaging instructions and use any
packaging materials that are provided.
.
Hardware replacement procedures
253
Содержание 7D2V
Страница 1: ...ThinkSystem SR665 Maintenance Manual Machine Types 7D2V and 7D2W ...
Страница 6: ...iv ThinkSystem SR665 Maintenance Manual ...
Страница 10: ...viii ThinkSystem SR665 Maintenance Manual ...
Страница 66: ...56 ThinkSystem SR665 Maintenance Manual ...
Страница 82: ...Figure 25 Cable routing for configuration 4 72 ThinkSystem SR665 Maintenance Manual ...
Страница 111: ...BP 3 NVMe 2 3 PCIe 3 BP 3 NVMe 4 5 PCIe 7 BP3 NVMe 6 7 PCIe 8 Chapter 3 Internal cable routing 101 ...
Страница 123: ...Figure 40 Cable routing for configuration 1 Chapter 3 Internal cable routing 113 ...
Страница 126: ...Figure 42 Cable routing for configuration 2 116 ThinkSystem SR665 Maintenance Manual ...
Страница 131: ...Figure 45 Cable routing for configuration 6 Chapter 3 Internal cable routing 121 ...
Страница 133: ...Chapter 3 Internal cable routing 123 ...
Страница 148: ...138 ThinkSystem SR665 Maintenance Manual ...
Страница 167: ...Chapter 4 Hardware replacement procedures 157 ...
Страница 216: ...Step 2 Connect the cables to the backplanes See 7mm drives on page 64 206 ThinkSystem SR665 Maintenance Manual ...
Страница 237: ...Chapter 4 Hardware replacement procedures 227 ...
Страница 299: ...Chapter 4 Hardware replacement procedures 289 ...
Страница 300: ...On the 2 5 inch middle drive cage 290 ThinkSystem SR665 Maintenance Manual ...
Страница 339: ...Chapter 4 Hardware replacement procedures 329 ...
Страница 364: ...354 ThinkSystem SR665 Maintenance Manual ...
Страница 408: ...398 ThinkSystem SR665 Maintenance Manual ...
Страница 431: ...5 Reseat the failing device 6 Replace the failing device Chapter 5 Problem determination 421 ...
Страница 444: ...434 ThinkSystem SR665 Maintenance Manual ...
Страница 445: ... Copyright Lenovo 2019 435 ...
Страница 448: ...438 ThinkSystem SR665 Maintenance Manual ...
Страница 449: ... Copyright Lenovo 2019 439 ...
Страница 452: ...442 ThinkSystem SR665 Maintenance Manual ...
Страница 464: ...454 ThinkSystem SR665 Maintenance Manual ...
Страница 465: ......
Страница 466: ......