Procedure
Notes:
• It may take some time for the heat sink to cool down after the system has been powered down.
• The heat sink is necessary to maintain proper thermal conditions for the processor. Do not power on the
server with the heat sink removed.
Step 1. Prepare your server.
1. Remove the top cover. See “Remove the top cover” on page 392.
2. Remove the air baffle. See “Remove the air baffle” on page 149.
3. Remove the fan cage (only for removing the performance heat sink). See “Remove the system
4. Remove any parts and disconnect any cables that might impede your access to the heat sink
and processor.
Step 2. Use a Torx #T20 screwdriver to loosen all the captive screws in the
removal sequence
shown on
the heat-sink label. After loosening each captive screw, wait for several seconds for the heat sink to
loosen from the processor. Then, slightly lift the heat sink away from the system.
Note:
The suggested tightening torque value is 14.0 ± 0.5 inch-pounds (1.525 – 1.638 newton
meters).
Figure 116. Removing a standard heat sink
.
Hardware replacement procedures
267
Содержание 7D2V
Страница 1: ...ThinkSystem SR665 Maintenance Manual Machine Types 7D2V and 7D2W ...
Страница 6: ...iv ThinkSystem SR665 Maintenance Manual ...
Страница 10: ...viii ThinkSystem SR665 Maintenance Manual ...
Страница 66: ...56 ThinkSystem SR665 Maintenance Manual ...
Страница 82: ...Figure 25 Cable routing for configuration 4 72 ThinkSystem SR665 Maintenance Manual ...
Страница 111: ...BP 3 NVMe 2 3 PCIe 3 BP 3 NVMe 4 5 PCIe 7 BP3 NVMe 6 7 PCIe 8 Chapter 3 Internal cable routing 101 ...
Страница 123: ...Figure 40 Cable routing for configuration 1 Chapter 3 Internal cable routing 113 ...
Страница 126: ...Figure 42 Cable routing for configuration 2 116 ThinkSystem SR665 Maintenance Manual ...
Страница 131: ...Figure 45 Cable routing for configuration 6 Chapter 3 Internal cable routing 121 ...
Страница 133: ...Chapter 3 Internal cable routing 123 ...
Страница 148: ...138 ThinkSystem SR665 Maintenance Manual ...
Страница 167: ...Chapter 4 Hardware replacement procedures 157 ...
Страница 216: ...Step 2 Connect the cables to the backplanes See 7mm drives on page 64 206 ThinkSystem SR665 Maintenance Manual ...
Страница 237: ...Chapter 4 Hardware replacement procedures 227 ...
Страница 299: ...Chapter 4 Hardware replacement procedures 289 ...
Страница 300: ...On the 2 5 inch middle drive cage 290 ThinkSystem SR665 Maintenance Manual ...
Страница 339: ...Chapter 4 Hardware replacement procedures 329 ...
Страница 364: ...354 ThinkSystem SR665 Maintenance Manual ...
Страница 408: ...398 ThinkSystem SR665 Maintenance Manual ...
Страница 431: ...5 Reseat the failing device 6 Replace the failing device Chapter 5 Problem determination 421 ...
Страница 444: ...434 ThinkSystem SR665 Maintenance Manual ...
Страница 445: ... Copyright Lenovo 2019 435 ...
Страница 448: ...438 ThinkSystem SR665 Maintenance Manual ...
Страница 449: ... Copyright Lenovo 2019 439 ...
Страница 452: ...442 ThinkSystem SR665 Maintenance Manual ...
Страница 464: ...454 ThinkSystem SR665 Maintenance Manual ...
Страница 465: ......
Страница 466: ......