background image

71

XC25

Use the  WEIGH-IN method for adding initial refrigerant charge, and then use SUBCOOLING

 

method for for verifying refrigerant charge

.

WEIGH-IN

Liquid Line

Set Diameter

HFC-410A

(ounces per foot)

5/16”

3/8”

1/2”

0.40

0.60

1.00

NOTE - The nameplate is shown for illustration purposes only. Go to
actual nameplate on outdoor unit for charge information.

CHARGING METHOD

NOTE - Insulate liquid line when it is routed through areas where
the surrounding ambient temperature could become higher than
the temperature of the liquid line or when pressure drop is equal
to or greater than 20 psig.

Amount specified

on nameplate

Adjust amount for variation in
line set length and liquid line
diameter using table below.

Total charge

+

=

64ºF (17.7ºC) and Below

Example

: Units are factory­charged for 15 feet (4.6 meters) of 3/8" line set.

Factory charge for 3/8" is 0.60 oz/ft  x 15 =  9.0 ounces.

Charging Formula for Liquid Line Charge Adjustments

[(Line set oz./ft. x total length) ­ (factory charge for line set)] = charge adjustment

Figure 57. Using

 

HFC-410A

 

Weigh-In Method

1. THE DIAGNOSTIC SCREEN ON THE THERMOSTAT OR OUTDOOR CONTROL 7-SEGMENT DISPLAY WILL SHOW INDOOR AND

OUTDOOR MOTOR CFMS OR RPMS.

2. MEASURE OUTDOOR AMBIENT TEMPERATURE; DETERMINE WHETHER TO USE 

COOLING

 

MODE

 OR 

HEATING MODE

 TO

CHECK CHARGE.

3. CONNECT GAUGE SET.
4. CHECK LIQUID AND VAPOR LINE PRESSURES. COMPARE PRESSURES WITH EITHER HEAT OR COOLING MODE NORMAL

OPERATING PRESSURES IN THE APPLICABLE CHARGING STICKER, NORMAL OPERATING PRESSURES, HIGH STAGE.

NOTE 

-

 THE REFERENCE TABLE IS A GENERAL GUIDE. EXPECT MINOR PRESSURE VARIATIONS. SIGNIFICANT

DIFFERENCES MAY MEAN IMPROPER CHARGE OR OTHER SYSTEM PROBLEM.

5. SET THERMOSTAT FOR HEAT/COOL DEMAND, DEPENDING ON MODE BEING USED:

USING COOLING MODE

 — WHEN THE OUTDOOR AMBIENT TEMPERATURE IS 60°F (15°C) AND ABOVE. TARGET

SUBCOOLING VALUES (SECOND STAGE - HIGH CAPACITY) IN APPLICABLE CHARGING STICKER ARE BASED ON 70 TO
80°F (21-27°C) INDOOR RETURN AIR TEMPERATURE; IF NECESSARY, OPERATE HEATING TO REACH THAT
TEMPERATURE RANGE; THEN SET THERMOSTAT TO COOLING MODE SETPOINT TO 68ºF (20ºC) WHICH SHOULD CALL
FOR SECOND-STAGE (HIGH STAGE) COOLING. WHEN PRESSURES HAVE STABILIZED, CONTINUE WITH STEP 6.

USING HEATING MODE

 — WHEN THE OUTDOOR AMBIENT TEMPERATURE IS BELOW 60°F (15°C). TARGET

SUBCOOLING VALUES (SECOND-STAGE - HIGH CAPACITY) IN APPLICABLE CHARGING STICKER ARE BASED ON 65-75°F
(18-24°C) INDOOR RETURN AIR TEMPERATURE; IF NECESSARY, OPERATE COOLING TO REACH THAT TEMPERATURE
RANGE; THEN SET THERMOSTAT TO HEATING MODE SETPOINT TO 77ºF (25ºC) WHICH SHOULD CALL FOR
SECOND-STAGE (HIGH STAGE) HEATING. WHEN PRESSURES HAVE STABILIZED, CONTINUE WITH STEP 6.

6. READ THE LIQUID LINE TEMPERATURE; RECORD IN THE LIQº SPACE.
7. READ THE LIQUID LINE PRESSURE; THEN FIND ITS CORRESPONDING TEMPERATURE IN THE TEMPERATURE/ PRESSURE

CHART LISTED IN THE APPLICABLE CHARGING STICKER AND RECORD IT IN THE SATº SPACE.

8. SUBTRACT LIQº TEMPERATURE FROM SATº TEMPERATURE TO DETERMINE SUBCOOLING; RECORD IT IN SCº SPACE.
9. COMPARE SCº RESULTS WITH APPLICABLE CHARGING STICKER, BEING SURE TO NOTE ANY ADDITIONAL CHARGE FOR

LINE SET AND/OR MATCH-UP.

10. IF SUBCOOLING VALUE IS GREATER THAN SHOWN IN APPLICABLE CHARGING STICKER FOR THE APPLICABLE UNIT,

REMOVE REFRIGERANT; IF LESS THAN SHOWN, ADD REFRIGERANT.

11. IF REFRIGERANT IS ADDED OR REMOVED, REPEAT STEPS 6 THROUGH 10 TO VERIFY CHARGE.

12. DISCONNECT GAUGE SET AND RE-INSTALL BOTH THE LIQUID AND SUCTION SERVICE VALVE CAPS.

USE

COOLING

MODE

USE

HEATING

MODE

60ºF

(15ºC)

SATº

LIQº

SCº

=

SUBCOOLING

CHARGING METHOD

(All charging 

MUST 

be performed while system is operating

either at maximum speed or 100% demand.)

Figure 58. Using HFC-410A Subcooling Method - High Speed (High Capacity)

Table 19

HFC-410A Temperature (°F) - Pressure (Psig)

°F

Psig

°F

Psig

°F

Psig

°F

Psig

°F

Psig

°F

Psig

°F

Psig

°F

Psig

32

100.8

48

137.1

63

178.5

79

231.6

94

290.8

110

365.0

125

445.9

141

545.6

33

102.9

49

139.6

64

181.6

80

235.3

95

295.1

111

370.0

126

451.8

142

552.3

34

105.0

50

142.2

65

184.3

81

239.0

96

299.4

112

375.1

127

457.6

143

559.1

35

107.1

51

144.8

66

187.7

82

242.7

97

303.8

113

380.2

128

463.5

144

565.9

36

109.2

52

147.4

67

190.9

83

246.5

98

308.2

114

385.4

129

469.5

145

572.8

37

111.4

53

150.1

68

194.1

84

250.3

99

312.7

115

390.7

130

475.6

146

579.8

38

113.6

54

152.8

69

197.3

85

254.1

100

317.2

116

396.0

131

481.6

147

586.8

39

115.8

55

155.5

70

200.6

86

258.0

101

321.8

117

401.3

132

487.8

148

593.8

40

118.0

56

158.2

71

203.9

87

262.0

102

326.4

118

406.7

133

494.0

149

601.0

41

120.3

57

161.0

72

207.2

88

266.0

103

331.0

119

412.2

134

500.2

150

608.1

42

122.6

58

163.9

73

210.6

89

270.0

104

335.7

120

417.7

135

506.5

151

615.4

43

125.0

59

166.7

74

214.0

90

274.1

105

340.5

121

423.2

136

512.9

152

622.7

44

127.3

60

169.6

75

217.4

91

278.2

106

345.3

122

428.8

137

519.3

153

630.1

45

129.7

61

172.6

76

220.9

92

282.3

107

350.1

123

434.5

138

525.8

154

637.5

46

132.2

62

175.4

77

224.4

93

286.5

108

355.0

124

440.2

139

532.4

155

645.0

47

134.6

78

228.0

109

360.0

140

539.0

Содержание XC25-024-230-01

Страница 1: ...ctrical components may hold charge Do not remove this panel or service this area for 5 minutes after the power has been removed TABLE OF CONTENTS I OVERVIEW Model Number Identification 2 Typical Seria...

Страница 2: ...Number of Blades Diameter inches Maximum Minimum XC25 024 230 01 70 59 13 lbs 10 oz 5 26 Model Number Unit Outdoor Fan Sound Rating Number dB 1 Factory Refrigerant Charge2 Number of Blades Diameter in...

Страница 3: ...18 0 1 3 4100 1950 650 350 157 32 2 0 208 230V 60 Hz 1 Ph Model Number Unit Compressor Outdoor Fan RPM varies with compressor RPM Maximum Over current Protection amps 1 Minimum Circuity Ampacity2 Rate...

Страница 4: ...ges and corners while applying excessive force or rapid motion can result in personal injury Be aware of and use caution when working nearby these areas during installation or while servicing this equ...

Страница 5: ...R SPST 25FLA 35RES GROUND LUGS CONTACTOR SPST 35FLA 40RES OUTDOOR CONTROL INVERTER NOISE FILTER FOR 6KW INVERTER 208 240V 60HZ CURRENT RANGE 30A MAXIMUM INDUCTANCE 4 3MH INVERTER REACTOR 230V 6KW CONT...

Страница 6: ...18 15 PSIG CRANKCASE HEATER THERMOSTAT S40 OPENS AT 70 F CLOSES AT 50 F COMPRESSOR TOP CAP SWITCH THERMAL VARIABLE CAPACITY COMPRESSOR HFC 410A 3 PHASE Figure 2 Plumbing Component Locations and Specif...

Страница 7: ...ommended Torque Service valve cap 8 ft lb 11 NM Sheet metal screws 16 in lb 2 NM Machine screws 10 28 in lb 3 NM Compressor bolts 90 in lb 10 NM Gauge port seal cap 8 ft lb 11 NM TORQUE REQUIREMENTS W...

Страница 8: ...TURN To Access Service Port A service port cap protects the service port core from contamination and serves as the primary leak seal 1 Remove service port cap with an appropriately sized wrench 2 Conn...

Страница 9: ...THE UNIT Units are outfitted with elongated support feet as illustrated in figure 5 detail C If additional elevation is necessary raise the unit by ex tending the height of the unit support feet Use...

Страница 10: ...ail D us ing conventional practices 3 Replace the panels after installation is complete ROOF MOUNTING Locate the unit above a load bearing wall or area of the roof that can adequately support the unit...

Страница 11: ...C SLAB NO PLASTIC ANCHOR HOLE DRILL 1 8 INSTALL UNIT LEVEL OR IF ON A SLOPE MAINTAIN SLOPE TOLERANCE OF 2 DEGREES OR 2 INCHES PER 5 FEET 50 MM PER 1 5 M AWAY FROM BUILDING STRUCTURE MOUNTING SLAB BUIL...

Страница 12: ...L INSTALLATION Position the panel almost parallel with the unit as illustrated in detail D with the screw side as close to the unit as possible Then in a continuous motion 1 SLIGHTLY ROTATE AND GUIDE...

Страница 13: ...ANT If this unit is being matched with an approved line set or indoor unit coil that was previously charged with mineral oil or if it is being matched with a coil which was manufactured before January...

Страница 14: ...ections Recommended Line Sets Model Number xx Liquid Line Suction Line L15 Line Set Model Line Set Length Catalog Number XC25 024 230 XX XC25 036 230 XX XC25 048 230 XX 3 8 10 mm 7 8 22 mm L15 65 30 3...

Страница 15: ...BE USED IF LINE SET IS TO BE INSTALLED ON EXTERIOR OF OUTSIDE WALL PVC PIPE FIBERGLASS INSULATION CAULK OUTSIDE WALL VAPOR LINE WRAPPED WITH ARMAFLEX LIQUID LINE OUTSIDE WALL LIQUID LINE VAPOR LINE WO...

Страница 16: ...lth Avoid breathing vapors or fumes from brazing operations Perform operations only in well ventilated areas Wear gloves and protective goggles or face shield to protect against burns Wash hands with...

Страница 17: ...EN HIGH LOW B A C PIPING PANEL REMOVAL AND LINE SET PREPARATION CAP AND CORE REMOVAL Remove piping panel for easier access to service valves Cut ends of the refrigerant lines square free from nicks or...

Страница 18: ...SET TO SERVICE VALVES POINT FLAME AWAY FROM SERVICE VALVE WARNING 1 FIRE PERSONAL INJURY OR PROPERTY DAMAGE will result if you do not wrap a water saturated cloth around both liquid and suction line s...

Страница 19: ...PROVIDED FITTING TO TEMPORARILY RECONNECT THE LIQUID LINE TO THE INDOOR UNIT S LIQUID LINE ORIFICE HOUSING LOW HIGH EXISTING INDOOR UNIT GAUGE MANIFOLD INVERTED HCFC 22 CYLINDER CONTAINS CLEAN HCFC 2...

Страница 20: ...PLICATION INFORMATION A REMOVE THE FIELD PROVIDED FITTING THAT TEMPORARILY RECON NECTED THE LIQUID LINE TO THE INDOOR UNIT S DISTRIBUTOR AS SEMBLY B INSTALL ONE OF THE PROVIDED TEFLON RINGS AROUND THE...

Страница 21: ...ith an approved line set or indoor unit coil which was previously charged with mineral oil or if it is being matched with a coil which was manufactured before January of 1999 the coil and line set mus...

Страница 22: ...GEN WITH A PRESSURE REGULATING VALVE TO THE CENTER PORT OF THE MANIFOLD GAUGE SET D ADJUST DRY NITROGEN PRESSURE TO 150 PSIG 1034 KPA OPEN THE VALVE ON THE HIGH SIDE OF THE MANIFOLD GAUGE SET IN ORDER...

Страница 23: ...DOES NOT RISE ABOVE 500 MICRONS 29 9 INCHES OF MERCURY WITHIN A 20 MINUTE PERIOD AFTER SHUTTING OFF THE VACUUM PUMP AND CLOSING THE MANIFOLD GAUGE VALVES F WHEN THE ABSOLUTE PRESSURE REQUIREMENT ABOVE...

Страница 24: ...2 completing the circuit between terminals R and L on the outdoor control The 24VAC input to terminal L activates the load shedding mode in the outdoor control cycling the outdoor unit OFF The 7 Segm...

Страница 25: ...the four unused wires at each end of the cable Each bundle should also include an additional wire that should be connected on each end to the C termi nal as shown in the figure below Any excess high v...

Страница 26: ...trostatic potential Neutralize electrostatic charge by touching hand and all tools on an unpainted unit surface before performing any service procedure STEP 3 ELECTRICAL Continued Outdoor Control Unit...

Страница 27: ...th the HI PS and TC N A Switched 24VAC Nominal N A Cntctr Contactor common N A 24VAC common Fan PWM PWM fan output N A 10 97 duty cycle 19 23 VDC peak N A COM PWM fan common connection N A N A Fan PWM...

Страница 28: ...ter Connects to Tx of inverter Outdoor control communication receive pin P6 Pin 4 Inv 5V Inverter 5VDC volts Inverter 5VDC volts LIQ Liquid line temperature sensor sup ply N A N A N A LIQ Liquid line...

Страница 29: ...ized 24 hours before unit start up to prevent compressor damage as a result of slugging 1 Rotate fan to check for binding 2 Inspect all factory and field installed wiring for loose connections 3 After...

Страница 30: ...cases errors are related to electrical noise Make sure high voltage power is separated from RS Bus Check for mis wired and or loose connections between the stat indoor unit and outdoor unit Check for...

Страница 31: ...r CFM may be set too low For zoning system zone CFM may be set too low E 413 N A N A N A Critical The high pressure switch has opened 5 times within one hour As a result the out door unit is locked ou...

Страница 32: ...s 10 times within an hour sys tem is locked out Indicates power interruption brownout poor electrical connec tion or loose inverter input wire To clear disconnect power to outdoor unit and restart E 4...

Страница 33: ...continues sending the in verter speed demanded by the thermostat The control sets indoor CFM and outdoor RPM to values according to demand percentage rather than the actual Hz Alarm is automatically c...

Страница 34: ...unit type cannot be determined three bars ap pear OR 7 SEGMENT POWER UP DISPLAY STRING EXAMPLE FIRMWARE VERSION UNIT TYPE UNIT CAPACITY UNIT CODE IDLE MODE Figure 16 Outdoor Control 7 Segment Unit St...

Страница 35: ...s repeated if cooling is active with outdoor fan speed set at 650 RPM and LIQ is 105 F pause pause pause Pump Down Mode While the unit is in pump down mode is displayed repeatedly Errors are shown if...

Страница 36: ...cond time period the control exits the test mode If this occurs test mode must be repeated Error Code Recall Mode NOTE control must be in idle mode To enter error code recall mode push and hold button...

Страница 37: ...uration and test mode Idle mode decimal flashes at 1 Hertz 0 5 second ON 0 5 second OFF Cooling operation Shows and the cooling demand percentage Example pause pause Fan RPM Shows and the current fan...

Страница 38: ...l and liquid line temperature information All temperatures are dis played in Fahrenheit Outdoor control is either in IDLE mode or heating cooling demand To enable temperature display push and hold but...

Страница 39: ...ELECTED Configuring Unit Selection Code Power up Unit selection code two digit number displayed represents unit size code outdoor unit capacity During initial power up firmware version unit type unit...

Страница 40: ...ble through the thermostat s user interface Refer to the iComfort Wi Fi Installer s System Setup Guide D Compressor anti short cycle delay timer status D Cooling rate D Compressor shift delay timer st...

Страница 41: ...r proper intervals procedures for your geographic area or service contract Indoor Unit 1 Clean or change filters 2 Lennox blower motors are pre lubricated and perman ently sealed No more lubrication i...

Страница 42: ...ction Service technician will need to visually inspect the unit being serviced to determine which wiring diagram is applicable Quick verification can usually be made by comparing the wiring diagram lo...

Страница 43: ...43 XC25 Figure 24 Typical Unit Wiring XC25 048 and 060...

Страница 44: ...44 XC25 NOTE For more information on Load Shedding see Electrical on page 24 Figure 25 Load Shedding Feature Wiring Diagram...

Страница 45: ...45 XC25 Factory Wiring Diagrams OUTDOOR CONTROL INVERTER REACTOR INVERTER Figure 26 Typical Factory Wiring XC25 024 and 036...

Страница 46: ...46 XC25 OUTDOOR CONTROL INVERTER REACTOR INVERTER INVERTER NOISE FILTER Figure 27 Typical Factory Wiring XC25 048 and 060...

Страница 47: ...of the outdoor fan motor 3 View the AIR HANDLER screen for actual CFM of the indoor blower motor From idle mode Outdoor Control 1 Sends a demand to the compressor inverter to start and run the compres...

Страница 48: ...REACHES 5 WITHIN A SINGLE Y1 DEMAND LOW PRESSURE SWITCH S87 LOCKOUT LED ALERT CODE OR CRITICAL ALERT 411 DISPLAYED SERVICE REQUIRED2 LED ALERT CODE OR MODERATE ALERT 410 DISPLAYED SERVICE REQUIRED2 NO...

Страница 49: ...MAND HIGH PRESSURE SWITCH S4 LOCKOUT LED ALERT CODE OR CRITICAL ALERT 413 CLEARED SERVICE REQUIRED2 LED ALERT CODE OR MODERATE ALERT 412 DISPLAYED NORMAL OPERATION CLOSED CLOSED OPEN OPEN OPEN CLOSED...

Страница 50: ...Operation 69 Verifying High and Low Pressure Switch Operation OPERATION The unit s pressure switches LO PS S87 and HI PS S4 are factory wired into the control on the LO PS and HI PS termin als respect...

Страница 51: ...D ALERT CODE OR CRITICAL ALERT 411 DISPLAYED SERVICE REQUIRED2 LED ALERT CODE OR MODERATE ALERT 410 DISPLAYED SERVICE REQUIRED2 NORMAL OPERATION CLOSED CLOSED OPEN OPEN 1 The thermostat will terminate...

Страница 52: ...HIGH PRESSURE SWITCH S4 LOCKOUT LED ALERT CODE OR CRITICAL ALERT 413 CLEARED SERVICE REQUIRED2 LED ALERT CODE OR MODERATE ALERT 412 DISPLAYED NORMAL OPERATION CLOSED CLOSED OPEN OPEN OPEN CLOSED CLOSE...

Страница 53: ...limit System is shut down The high pressure switch opens at 590PSIG and closes at 418PSIG Confirm that the system is prop erly charged with refrigerant Check for clogged TXV blockage to indoor unit bl...

Страница 54: ...ected outdoor unit compressor and fan stop Anti short cycle is initiated If condition occurs 10 times within an hour system is locked out Indicates poor connection at compressor harness improper windi...

Страница 55: ...utility company to limit the maximum power level usage of the outdoor unit The feature is activated by applying 24 volts AC power to the L and C terminals on the outdoor control Crankcase Heater Chec...

Страница 56: ...detected the sensor is faulty the sensor needs to be replaced Figure 38 Checking Crankcase Heater Thermostat STATUS CODE None ERROR CODES None Compressor Sound Cover All units come with a soft sided...

Страница 57: ...off compressor operation The auto reset switch closes when the compressor casing temperature falls to 151 187 F and the compressor is re energized This single pole single throw SPST bi metallic switch...

Страница 58: ...E 442 Critical The top cap switch has opened 5 times within one hour As a result the outdoor unit is locked out When compressor thermal protection sensor opens 5 times within 1 hour outdoor stops wor...

Страница 59: ...ts have an external device see illustration below NOTE A line filter is an electronic filter which is placed between electronic equipment and an external power source in order to attenuate conducted r...

Страница 60: ...ostat CHECKOUT VAC Voltage Check Check for 208 240 VAC power at inverter contactor red wires see figure 46 With unit operating check for main VAC to motor and outdoor control VDC output to motor 1 No...

Страница 61: ...e outdoor control therefore no status or error codes are displayed on either the outdoor control or iComfort Wi Fi room thermostat NOTE If the outdoor fan does not operate at the correct RPM or does n...

Страница 62: ...s NOTE System fault and lockout codes take precedence over system status codes cooling heating operating percentages or defrost dehumidification Only the latest active fault or lockout codes are displ...

Страница 63: ...on is re established E 125 Critical There is a hardware problem with the outdoor control There is a control hardware problem Replace the outdoor control if the problem pre vents operation and is persi...

Страница 64: ...s into the outdoor control Through the sensors the control detects outdoor ambient coil and liquid temperature fault conditions As the detected tem perature changes the resistance across the sensor ch...

Страница 65: ...61693 26 2 204829 92 0 7007 42 3 24525 9 9 62712 27 0 210805 90 6 7225 41 7 24934 9 3 63752 27 8 217080 89 4 7444 41 1 25349 8 8 64812 28 7 223677 88 1 7666 40 5 25769 8 3 65895 29 5 230621 86 9 7890...

Страница 66: ...sensor range Outdoor unit control will not perform demand or time temperature defrost operation System will still heat or cool Check the resistance of the coil sensor and compare to temperature resis...

Страница 67: ...ert Codes and Inverter LED Flash Codes NOTE System fault and lockout codes take precedence over system status codes cooling heating operating percentages or defrost dehumidification Only the latest ac...

Страница 68: ...ated If condi tion occurs 5 times within an hour system will lock out To clear disconnect power to outdoor unit and restart E 434 53 5 flashes 3 flashes Moderate Critical Outdoor control has lost comm...

Страница 69: ...24VAC System Operation System Refrigerant IMPORTANT The system must be operating at full capacity during charging Increase heat or decrease cooling the thermostat setting by 5 F to create system dema...

Страница 70: ...4 13 12 72 20 20 19 18 17 17 16 15 15 14 13 12 11 10 70 19 19 18 18 17 17 16 15 15 14 13 12 11 10 57 58 59 60 61 62 63 64 65 66 67 68 69 70 TEMPERATURE OF AIR ENTERING INDOOR COIL F INDOOR COIL DRY BU...

Страница 71: ...RN AIR TEMPERATURE IF NECESSARY OPERATE COOLING TO REACH THAT TEMPERATURE RANGE THEN SET THERMOSTAT TO HEATING MODE SETPOINT TO 77 F 25 C WHICH SHOULD CALL FOR SECOND STAGE HIGH STAGE HEATING WHEN PRE...

Страница 72: ...72 XC25 Figure 59 XC25 Charging Sticker...

Отзывы: