64
XC25
OUTDOOR
AMBIENT
LIQUID LINE
TEMPERATURE
SENSOR HARNESS
BLACK WIRES WITH
BLACK
SLEEVE
BLACK WIRES WITH
YELL0W
SLEEVE
SENSOR
RESISTANCE VALUES
RANGE (OHMS)
TEMP RANGE ºF
(ºC)
PIN# / WIRE
SLEEVE COLOR
LIQUID LINE
OUTDOOR
AMBIENT
NONE
4 AND 3
(
BLACK
)
6 AND 5
2 AND 1
(
YELLOW
)
-40 (-40) TO
140 (60)
336,000 to 2,487 (see
table 15 on page 65 for
exact temperature to
ohm readings).
314669 and 3779
N/A
Figure 50. Temperature Sensor Specifications
CHECKOUT
Sensors connect to the outdoor control through a field‐replaceable harness assembly that plugs into the outdoor control.
Through the sensors, the control detects outdoor ambient, coil and liquid temperature fault conditions. As the detected tem
perature changes, the resistance across the sensor changes. Check sensor operation by reading ohms across pins shown
in figure 50.
NOTE - When checking the ohms across a sensor, be aware that a sensor showing a resistance value that is not within the
range shown in figure 50, may be performing as designed. However, if a shorted or open circuit is detected, then the sensor
may be faulty and the sensor harness will need to be replaced.
OUTDOOR AMBIENT
TEMPERATURE
SENSOR
LIQUID LINE SENSOR
CRANKCASE HEATER
THERMOSTAT (S40) OPENS AT
70ºF, CLOSES AT 50ºF
Figure 51. Temperature Sensor Locations
Содержание XC25-024-230-01
Страница 43: ...43 XC25 Figure 24 Typical Unit Wiring XC25 048 and 060...