III. SYSTEM OPERATION AND SERVICE
7-Segment Alert and System Status Codes
Alert codes are displayed using the 7-segment display loc
ated on the outdoor control.
NOTE - System fault and lockout codes take precedence
over system status codes (cooling, heating operating per
centages or defrost/dehumidification).
The 7-segment will display an abnormal condition (error
code) when detected in the system. A list of the codes are
shown in table 6.
RESETTING ALERT CODES
Alert codes can be reset manually or automatically:
1.
Manual Reset
Manual reset can be achieved by one of the following
methods:
•
Disconnecting
R
wire from the outdoor control
R
terminal.
•
Turning the indoor unit off and back on again
After power up, all currently displayed codes are
cleared.
2.
Automatic Reset
After an alert is detected, the outdoor control continues
to monitor the unit's system and compressor opera
tions. When/if conditions return to normal, the alert
code is turned off automatically.
NOTE - Error codes can be recalled by following in
formation shown in the table on page 35.
Table 6. Outdoor Control 7-Segment Display Alert Codes and Inverter LED Flash Codes
NOTE - System fault and lockout codes take precedence over system status codes (cooling, heating operating percentages
or defrost/dehumidification). Only the latest active fault or lockout codes are displayed (if present). If no fault or lockout codes
are active, then system status codes are displayed. Alert codes are also displayed on the iComfort Wi-Fi
®
thermostat.
Alert
Codes
Inverter
Code
Inverter LED Flash
Code (number of
flashes)
Priority
Alarm Description
Possible Causes and Clearing Alarm
Red LED
Green LED
N/A
N/A
ON
OFF
N/A
XC/XP 25-024 and -036 only: Indicates inverter is operating normally.
N/A
N/A
ON
ON
N/A
XC/XP 25-048 and -060 only: Indicates inverter is operating normally.
N/A
N/A
OFF
OFF
N/A
Indicates inverter is NOT energized.
E 105
N/A
N/A
N/A
Moderate
The outdoor control
has lost communic
ation with either the
thermostat or in
door unit.
Equipment is unable to communicate. Indicates numerous
message errors. In most cases errors are related to electrical
noise. Make sure high voltage power is separated from RS
Bus. Check for miswired and/or loose connections between
the stat, indoor unit and outdoor unit. Check for a high voltage
source of noise close to the system. Fault clears after commu
nication is restored.
E 120
N/A
N/A
N/A
Moderate
There is a delay in
the outdoor unit
re
sponding to the
system.
Typically, this alarm/code does not cause any issues and
clears on its own. The alarm / code is usually caused by a
delay in the outdoor unit responding to the thermostat. Check
all wiring connections. Cleared after unresponsive device re
sponds to any inquiry.
E 124
N/A
N/A
N/A
Critical
The iComfort WiFi
®
thermostat has lost
communication with
the outdoor unit
for
more than 3
minutes.
Equipment lost communication with the thermostat. Check the
wiring connections, ohm wires and cycle power. The alarm
stops all associated HVAC operations and waits for a heartbeat
message from the unit that's not communicating. The alarm /
fault clears after communication is reestablished.
E 125
N/A
N/A
N/A
Critical
There is a hardware
problem with the
outdoor control.
There is a control hardware problem. Replace the outdoor con
trol if the problem prevents operation and is persistent. The
alarm / fault is cleared 300 seconds after the fault recovers.
E 131
N/A
N/A
N/A
Critical
The outdoor unit con
trol parameters are
corrupted.
Reconfigure the system. Replace the control if heating or cool
ing is not available.
E 132
N/A
N/A
N/A
Critical
Internal software er
ror.
Replace outdoor control.
E 180
N/A
N/A
N/A
Critical
The outdoor unit am
bient temperature
sensor has malfunc
tioned. As a result
the outdoor unit con
trol will not perform
low ambient cooling.
In normal operation, after outdoor control recognizes sensors,
the alarm is sent if valid temperature reading is lost. Compare
outdoor sensor resistance to temperature/resistance charts in
unit installation instructions. Replace sensor pack if necessary.
At the beginning of (any) configuration, furnace or airhandler
control detects the presence of the sensor(s). If detected (read
ing in range), appropriate feature is shown in the iComfort
WiFi
®
thermostat About screen. The alarm / fault clears upon
configuration, or when normal values are sensed.