XC25
High and Low Pressure Switch Errors
Table 10. Outdoor Control 7-Segment Display Alert Codes - High and Low Pressure Switches
System fault and lockout codes take precedence over system status codes (cooling, heating operating percentages or de
frost/dehumidification). Only the latest active fault or lockout codes are displayed (if present). If no fault or lockout codes are
active, then system status codes are displayed. Alert codes are also displayed on the iComfort Wi-Fi
®
thermostat.
Alert
Codes
Priority
Alarm Description
Possible Causes and Clearing Alarm
E 410
Moderate
The outdoor unit low pressure
switch has closed.
Unit pressure is below the lower limit. The system is shutdown. The low pressure
switch opens at 25PSIG and closes at 40PSIG. Confirm that the system is properly
charged with refrigerant. Check TXV, indoor unit blower motor, dirty filters or clogged
refrigerant filter. Confirm that the evaporator coil is clean. The alarm clears after the
pressure switch opens or after a power reset.
E 411
Critical
The low pressure switch has
opened 5 times within one hour. As
a result, the outdoor unit is locked
out
.
Low pressure switch error count reached 5 strikes. The low pressure switch for
HFC410A opens at 40PSIG and resets at 90PSIG. Confirm that the system is prop
erly charged with refrigerant. Check for clogged TXV, blockage to indoor unit blower
motor, dirty filters or clogged refrigerant filter. Confirm that the evaporator coil is
clean. The alarm clears after a power reset.
E 412
Moderate
The outdoor unit high pressure
switch has opened.
Unit pressure is above the upper limit. System is shut down. The high pressure
switch opens at 590PSIG and closes at 418PSIG. Confirm that the system is prop
erly charged with refrigerant. Check for clogged TXV, blockage to indoor unit blower
motor, clogged refrigerant filter. Confirm that the outdoor unit is clean. The alarm
clears after the pressure switch closes or a power reset.
For heating, indoor CFM may be set too low. For zoning system, zone CFM may be
set too low.
E 413
Critical
The high pressure switch has
opened 5 times within one hour. As
a result, the outdoor unit is locked
out
.
NOTE - Unused on XC25. Used for
heat pump applications only.
Open high pressure switch error count reached 5 strikes. System is shut down. The
high pressure switch for HFC410A will open at 590PSIG and close at 418PSIG.
Confirm that the system is properly charged with refrigerant. Check condenser fan
motor, clogged TXV, blockage to indoor unit blower motor, stuck reversing valve or
clogged refrigerant filter. Confirm that the outdoor unit is clean. The alarm clears
after a power reset.
For heating, indoor CFM may be set too low. For zoning system, zone CFM may be
set too low.
Compressor Operation, Checkout and Status / Error Codes
OPERATION:
The compressor is a 380VAC three-phase variable-capacity scroll compressor that is approved for use with HFC410A refri
gerant. The compressor, when connected to an inverter, is capable of operating in a running frequency range from 22 hertz
up to a maximum of 70 Hertz (maximum hertz is dependent on compressor size). The compressor speed is determined by
demand from the room thermostat.
CHECKOUT:
Figure 34. Compressor Operation, Checkout and Status/Error Codes
IMPORTANT
: If compressor replacement is required, remove the compressor through the top of the unit. Removal through
the access panel is not possible.