Table Table 18 continued
Alert
Codes
Inverter
Code
Inverter LED Flash
Code (number of
flashes)
Priority
Alarm Description
Possible Causes and Clearing Alarm
Red LED
Green LED
E 427
21
2 flashes
1 flash
Moderate /
Critical
The inverter has de
tected a DC peak
fault condition
.
If condition (55A or higher) is detected, outdoor unit will stop (compressor and fan).
Antishort cycle is initiated. If peak current (55A or higher) occurs 10 times within an
hour, system will lock out.
Indicates high pressure, condenser fan failure, locked compressor rotor or over
charge.
To clear, disconnect power to outdoor unit and restart.
E 428
22
2 flashes
2 flashes
Moderate /
Critical
The inverter has de
tected a high main in
put current condition
.
If condition is detected, outdoor unit will stop (compressor and fan). Antishort cycle is
initiated. If condition occurs 5 times within an hour, system will lock out.
Indicates high pressure, condenser fan failure or overcharge.
To clear, disconnect power to outdoor unit and restart.
E 429
23
2 flashes
3 flashes
Moderate /
Critical
The inverter has de
tected a DC link low
voltage condition
.
Error occurs when DC link voltage drops below 14VDC. If condition is detected, out
door unit will stop (compressor and fan). Antishort cycle is initiated. If condition occurs
10 times within an hour, system will lock out.
Indicates power interruption, brownout, poor electrical connection or loose inverter in
put wire.
To clear, disconnect power to outdoor unit and restart.
E 430
26
2 flashes
6 flashes
Moderate /
Critical
Compressor start
failure
.
If condition is detected, outdoor unit will stop (compressor and fan). Antishort cycle is
initiated. If condition occurs 10 times within an hour, system will lock out.
Indicates poor connection at compressor harness, improper winding resistance,
locked compressor rotor, or flooded compressor.
To clear, disconnect power to outdoor unit and restart.
E 431
27
2 flashes
7 flashes
Moderate /
Critical
The inverter has de
tected a PFC circuit
over-current condition
.
Error occurs when PFC detects a over-current condition of 100A peak. If condition is
detected, outdoor unit will stop (compressor and fan). Antishort cycle is initiated. If
condition occurs 10 times within an hour, system will lock out.
Indicates high pressure, condenser fan failure, locked compressor rotor or over
charge.
To clear, disconnect power to outdoor unit and restart.
E 432
28
2 flashes
8 flashes
Moderate /
Critical
The inverter has de
tected a DC link high
voltage condition.
Error occurs when the DC link capacitor voltage is greater than 480VDC. If condition is
detected, outdoor unit will stop (compressor and fan). Antishort cycle is initiated. If
condition occurs 10 times within an hour, system will lock out. System will stop. To
clear, disconnect power to outdoor unit and restart.
E 433
29
2 flashes
9 flashes
Moderate /
Critical
The inverter has de
tected a compressor
over-current condi
tion
.
Error occurs when compressor peak phase current is greater than 28A. Inverter will
issue code 14 first and slow down to try to reduce the current. If the current remains
high, outdoor unit will stop (compressor and fan). Antishort cycle is initiated. If condi
tion occurs 5 times within an hour, system will lock out. To clear disconnect power to
outdoor unit and restart.
E 434
53
5 flashes
3 flashes
Moderate /
Critical
Outdoor control has
lost communications
with the inverter for
greater than 3
minutes.
Error occurs when communication a checksum error occurs for 3 minutes. Outdoor
control stops all compressor demands. Recycle power to the inverter by deenergiz
ing the contactor for 2 minutes.
E 435
60
6 flashes
OFF
Moderate /
Critical
Inverter internal er
ror.
When this error occurs, the outdoor control will cycle power to the inverter by opening
the contactor for 2 minutes. Check that the EEPROM is properly seated. After power is
cycled to the inverter 3 times, the outdoor unit is locked out
.
E 436
62
6 flashes
2 flashes
Moderate /
Critical
Inverter heat sink
temperature ex
ceeded limit
.
Occurs when the heat sink temperature exceeds the inverter limit. Inverter issues
code 13 first, then slows down to allow the heat sink to cool. If temperature remains
high, outdoor unit stops (compressor and fan). Antishort cycle is initiated. If condition
occurs 5 times within an hour, system is locked out. To clear, disconnect power to out
door unit and restart.
E 437
65
6 flashes
5 flashes
Moderate /
Critical
Heat sink temperat
ure sensor fault has
occurred (temperat
ure less than 4 ºF or
greater than 264ºF
after 10 minutes of
operation)
.
This occurs when the temperature sensor detects a temperature less than 0.4ºF or
greater than 264ºF after 10 minutes of operation. If condition is detected, outdoor unit
will stop (compressor and fan). Antishort cycle is initiated. If condition occurs 5 times
within an hour, system will lock out. To clear disconnect power to outdoor unit and re
start. If problem persists, replace inverter.
E 438
73
7 flashes
3 flashes
Moderate /
Critical
The inverter has de
tected a PFC circuit
over-current condi
tion
.
Error occurs when PFC detects an input over-current condition of 35A peak. If condi
tion is detected, outdoor unit will stop (compressor and fan). Antishort cycle is initi
ated. If condition occurs 10 times within an hour, system will lock out.
Indicates high pressure, condenser fan failure, or locked compressor rotor.
To clear, disconnect power to outdoor unit and restart.
E 439
12
1 flash
2 flashes
Moderate
Compressor slow
down due to high in
put current.
Input current is approaching a high limit. Compressor speed will automatically slow
down. The control continues sending the inverter speed demanded by the thermostat.
The control will set indoor CFM and outdoor RPM to values according to demand per
centage rather than the actual Hz. Alarm is automatically clear.
E 440
13
1 flash
3 flashes
Moderate
Compressor slow
down due to high
heatsink temperat
ure.
Heat sink temperature is approaching limit. The compressor speed will automatically
slow down to reduce heatsink temperature. The control will set indoor CFM and out
door RPM to values according to demand percentage rather than the actual Hz. Alarm
is automatically cleared.
E 441
14
1 flash
4 flashes
Moderate
Compressor slow
down due to high
compressor current.
Compressor current is approaching high limit. The compressor speed will automatic
ally slow down. The control will set indoor CFM and outdoor RPM to values according
to demand percentage rather than the actual Hz. Alarm is automatically cleared.