background image

16

XC25

Brazing Connections

Use the procedures outlined in figures 8 and 9 for brazing
line set connections to service valves.

WARNING

Danger of fire. Bleeding the refrigerant
charge from only the high side may result
in pressurization of the low side shell and
suction tubing. Application of a brazing
torch to a pressurized system may result
in ignition of the refrigerant and oil mixture
- Check the high and low pressures
before applying heat.

CAUTION

Brazing alloys and flux contain materials which are
hazardous to your health.

Avoid breathing vapors or fumes from brazing
operations. Perform operations only in well-ventilated
areas.

Wear gloves and protective goggles or face shield to
protect against burns.

Wash hands with soap and water after handling brazing
alloys and flux.

IMPORTANT

Allow braze joint to cool before removing the wet rag
from the service valve. Temperatures above 250ºF can
damage valve seals.

WARNING

Fire, Explosion and Personal Safety
Hazard.

Failure to follow this warning could re­
sult in damage, personal injury or death.

Never use oxygen to pressurize or
purge refrigeration lines. Oxygen, when
exposed to a spark or open flame, can
cause a fire and/or an explosion, that
could result in property damage, per­
sonal injury or death.

Содержание XC25-024-230-01

Страница 1: ...ctrical components may hold charge Do not remove this panel or service this area for 5 minutes after the power has been removed TABLE OF CONTENTS I OVERVIEW Model Number Identification 2 Typical Seria...

Страница 2: ...Number of Blades Diameter inches Maximum Minimum XC25 024 230 01 70 59 13 lbs 10 oz 5 26 Model Number Unit Outdoor Fan Sound Rating Number dB 1 Factory Refrigerant Charge2 Number of Blades Diameter in...

Страница 3: ...18 0 1 3 4100 1950 650 350 157 32 2 0 208 230V 60 Hz 1 Ph Model Number Unit Compressor Outdoor Fan RPM varies with compressor RPM Maximum Over current Protection amps 1 Minimum Circuity Ampacity2 Rate...

Страница 4: ...ges and corners while applying excessive force or rapid motion can result in personal injury Be aware of and use caution when working nearby these areas during installation or while servicing this equ...

Страница 5: ...R SPST 25FLA 35RES GROUND LUGS CONTACTOR SPST 35FLA 40RES OUTDOOR CONTROL INVERTER NOISE FILTER FOR 6KW INVERTER 208 240V 60HZ CURRENT RANGE 30A MAXIMUM INDUCTANCE 4 3MH INVERTER REACTOR 230V 6KW CONT...

Страница 6: ...18 15 PSIG CRANKCASE HEATER THERMOSTAT S40 OPENS AT 70 F CLOSES AT 50 F COMPRESSOR TOP CAP SWITCH THERMAL VARIABLE CAPACITY COMPRESSOR HFC 410A 3 PHASE Figure 2 Plumbing Component Locations and Specif...

Страница 7: ...ommended Torque Service valve cap 8 ft lb 11 NM Sheet metal screws 16 in lb 2 NM Machine screws 10 28 in lb 3 NM Compressor bolts 90 in lb 10 NM Gauge port seal cap 8 ft lb 11 NM TORQUE REQUIREMENTS W...

Страница 8: ...TURN To Access Service Port A service port cap protects the service port core from contamination and serves as the primary leak seal 1 Remove service port cap with an appropriately sized wrench 2 Conn...

Страница 9: ...THE UNIT Units are outfitted with elongated support feet as illustrated in figure 5 detail C If additional elevation is necessary raise the unit by ex tending the height of the unit support feet Use...

Страница 10: ...ail D us ing conventional practices 3 Replace the panels after installation is complete ROOF MOUNTING Locate the unit above a load bearing wall or area of the roof that can adequately support the unit...

Страница 11: ...C SLAB NO PLASTIC ANCHOR HOLE DRILL 1 8 INSTALL UNIT LEVEL OR IF ON A SLOPE MAINTAIN SLOPE TOLERANCE OF 2 DEGREES OR 2 INCHES PER 5 FEET 50 MM PER 1 5 M AWAY FROM BUILDING STRUCTURE MOUNTING SLAB BUIL...

Страница 12: ...L INSTALLATION Position the panel almost parallel with the unit as illustrated in detail D with the screw side as close to the unit as possible Then in a continuous motion 1 SLIGHTLY ROTATE AND GUIDE...

Страница 13: ...ANT If this unit is being matched with an approved line set or indoor unit coil that was previously charged with mineral oil or if it is being matched with a coil which was manufactured before January...

Страница 14: ...ections Recommended Line Sets Model Number xx Liquid Line Suction Line L15 Line Set Model Line Set Length Catalog Number XC25 024 230 XX XC25 036 230 XX XC25 048 230 XX 3 8 10 mm 7 8 22 mm L15 65 30 3...

Страница 15: ...BE USED IF LINE SET IS TO BE INSTALLED ON EXTERIOR OF OUTSIDE WALL PVC PIPE FIBERGLASS INSULATION CAULK OUTSIDE WALL VAPOR LINE WRAPPED WITH ARMAFLEX LIQUID LINE OUTSIDE WALL LIQUID LINE VAPOR LINE WO...

Страница 16: ...lth Avoid breathing vapors or fumes from brazing operations Perform operations only in well ventilated areas Wear gloves and protective goggles or face shield to protect against burns Wash hands with...

Страница 17: ...EN HIGH LOW B A C PIPING PANEL REMOVAL AND LINE SET PREPARATION CAP AND CORE REMOVAL Remove piping panel for easier access to service valves Cut ends of the refrigerant lines square free from nicks or...

Страница 18: ...SET TO SERVICE VALVES POINT FLAME AWAY FROM SERVICE VALVE WARNING 1 FIRE PERSONAL INJURY OR PROPERTY DAMAGE will result if you do not wrap a water saturated cloth around both liquid and suction line s...

Страница 19: ...PROVIDED FITTING TO TEMPORARILY RECONNECT THE LIQUID LINE TO THE INDOOR UNIT S LIQUID LINE ORIFICE HOUSING LOW HIGH EXISTING INDOOR UNIT GAUGE MANIFOLD INVERTED HCFC 22 CYLINDER CONTAINS CLEAN HCFC 2...

Страница 20: ...PLICATION INFORMATION A REMOVE THE FIELD PROVIDED FITTING THAT TEMPORARILY RECON NECTED THE LIQUID LINE TO THE INDOOR UNIT S DISTRIBUTOR AS SEMBLY B INSTALL ONE OF THE PROVIDED TEFLON RINGS AROUND THE...

Страница 21: ...ith an approved line set or indoor unit coil which was previously charged with mineral oil or if it is being matched with a coil which was manufactured before January of 1999 the coil and line set mus...

Страница 22: ...GEN WITH A PRESSURE REGULATING VALVE TO THE CENTER PORT OF THE MANIFOLD GAUGE SET D ADJUST DRY NITROGEN PRESSURE TO 150 PSIG 1034 KPA OPEN THE VALVE ON THE HIGH SIDE OF THE MANIFOLD GAUGE SET IN ORDER...

Страница 23: ...DOES NOT RISE ABOVE 500 MICRONS 29 9 INCHES OF MERCURY WITHIN A 20 MINUTE PERIOD AFTER SHUTTING OFF THE VACUUM PUMP AND CLOSING THE MANIFOLD GAUGE VALVES F WHEN THE ABSOLUTE PRESSURE REQUIREMENT ABOVE...

Страница 24: ...2 completing the circuit between terminals R and L on the outdoor control The 24VAC input to terminal L activates the load shedding mode in the outdoor control cycling the outdoor unit OFF The 7 Segm...

Страница 25: ...the four unused wires at each end of the cable Each bundle should also include an additional wire that should be connected on each end to the C termi nal as shown in the figure below Any excess high v...

Страница 26: ...trostatic potential Neutralize electrostatic charge by touching hand and all tools on an unpainted unit surface before performing any service procedure STEP 3 ELECTRICAL Continued Outdoor Control Unit...

Страница 27: ...th the HI PS and TC N A Switched 24VAC Nominal N A Cntctr Contactor common N A 24VAC common Fan PWM PWM fan output N A 10 97 duty cycle 19 23 VDC peak N A COM PWM fan common connection N A N A Fan PWM...

Страница 28: ...ter Connects to Tx of inverter Outdoor control communication receive pin P6 Pin 4 Inv 5V Inverter 5VDC volts Inverter 5VDC volts LIQ Liquid line temperature sensor sup ply N A N A N A LIQ Liquid line...

Страница 29: ...ized 24 hours before unit start up to prevent compressor damage as a result of slugging 1 Rotate fan to check for binding 2 Inspect all factory and field installed wiring for loose connections 3 After...

Страница 30: ...cases errors are related to electrical noise Make sure high voltage power is separated from RS Bus Check for mis wired and or loose connections between the stat indoor unit and outdoor unit Check for...

Страница 31: ...r CFM may be set too low For zoning system zone CFM may be set too low E 413 N A N A N A Critical The high pressure switch has opened 5 times within one hour As a result the out door unit is locked ou...

Страница 32: ...s 10 times within an hour sys tem is locked out Indicates power interruption brownout poor electrical connec tion or loose inverter input wire To clear disconnect power to outdoor unit and restart E 4...

Страница 33: ...continues sending the in verter speed demanded by the thermostat The control sets indoor CFM and outdoor RPM to values according to demand percentage rather than the actual Hz Alarm is automatically c...

Страница 34: ...unit type cannot be determined three bars ap pear OR 7 SEGMENT POWER UP DISPLAY STRING EXAMPLE FIRMWARE VERSION UNIT TYPE UNIT CAPACITY UNIT CODE IDLE MODE Figure 16 Outdoor Control 7 Segment Unit St...

Страница 35: ...s repeated if cooling is active with outdoor fan speed set at 650 RPM and LIQ is 105 F pause pause pause Pump Down Mode While the unit is in pump down mode is displayed repeatedly Errors are shown if...

Страница 36: ...cond time period the control exits the test mode If this occurs test mode must be repeated Error Code Recall Mode NOTE control must be in idle mode To enter error code recall mode push and hold button...

Страница 37: ...uration and test mode Idle mode decimal flashes at 1 Hertz 0 5 second ON 0 5 second OFF Cooling operation Shows and the cooling demand percentage Example pause pause Fan RPM Shows and the current fan...

Страница 38: ...l and liquid line temperature information All temperatures are dis played in Fahrenheit Outdoor control is either in IDLE mode or heating cooling demand To enable temperature display push and hold but...

Страница 39: ...ELECTED Configuring Unit Selection Code Power up Unit selection code two digit number displayed represents unit size code outdoor unit capacity During initial power up firmware version unit type unit...

Страница 40: ...ble through the thermostat s user interface Refer to the iComfort Wi Fi Installer s System Setup Guide D Compressor anti short cycle delay timer status D Cooling rate D Compressor shift delay timer st...

Страница 41: ...r proper intervals procedures for your geographic area or service contract Indoor Unit 1 Clean or change filters 2 Lennox blower motors are pre lubricated and perman ently sealed No more lubrication i...

Страница 42: ...ction Service technician will need to visually inspect the unit being serviced to determine which wiring diagram is applicable Quick verification can usually be made by comparing the wiring diagram lo...

Страница 43: ...43 XC25 Figure 24 Typical Unit Wiring XC25 048 and 060...

Страница 44: ...44 XC25 NOTE For more information on Load Shedding see Electrical on page 24 Figure 25 Load Shedding Feature Wiring Diagram...

Страница 45: ...45 XC25 Factory Wiring Diagrams OUTDOOR CONTROL INVERTER REACTOR INVERTER Figure 26 Typical Factory Wiring XC25 024 and 036...

Страница 46: ...46 XC25 OUTDOOR CONTROL INVERTER REACTOR INVERTER INVERTER NOISE FILTER Figure 27 Typical Factory Wiring XC25 048 and 060...

Страница 47: ...of the outdoor fan motor 3 View the AIR HANDLER screen for actual CFM of the indoor blower motor From idle mode Outdoor Control 1 Sends a demand to the compressor inverter to start and run the compres...

Страница 48: ...REACHES 5 WITHIN A SINGLE Y1 DEMAND LOW PRESSURE SWITCH S87 LOCKOUT LED ALERT CODE OR CRITICAL ALERT 411 DISPLAYED SERVICE REQUIRED2 LED ALERT CODE OR MODERATE ALERT 410 DISPLAYED SERVICE REQUIRED2 NO...

Страница 49: ...MAND HIGH PRESSURE SWITCH S4 LOCKOUT LED ALERT CODE OR CRITICAL ALERT 413 CLEARED SERVICE REQUIRED2 LED ALERT CODE OR MODERATE ALERT 412 DISPLAYED NORMAL OPERATION CLOSED CLOSED OPEN OPEN OPEN CLOSED...

Страница 50: ...Operation 69 Verifying High and Low Pressure Switch Operation OPERATION The unit s pressure switches LO PS S87 and HI PS S4 are factory wired into the control on the LO PS and HI PS termin als respect...

Страница 51: ...D ALERT CODE OR CRITICAL ALERT 411 DISPLAYED SERVICE REQUIRED2 LED ALERT CODE OR MODERATE ALERT 410 DISPLAYED SERVICE REQUIRED2 NORMAL OPERATION CLOSED CLOSED OPEN OPEN 1 The thermostat will terminate...

Страница 52: ...HIGH PRESSURE SWITCH S4 LOCKOUT LED ALERT CODE OR CRITICAL ALERT 413 CLEARED SERVICE REQUIRED2 LED ALERT CODE OR MODERATE ALERT 412 DISPLAYED NORMAL OPERATION CLOSED CLOSED OPEN OPEN OPEN CLOSED CLOSE...

Страница 53: ...limit System is shut down The high pressure switch opens at 590PSIG and closes at 418PSIG Confirm that the system is prop erly charged with refrigerant Check for clogged TXV blockage to indoor unit bl...

Страница 54: ...ected outdoor unit compressor and fan stop Anti short cycle is initiated If condition occurs 10 times within an hour system is locked out Indicates poor connection at compressor harness improper windi...

Страница 55: ...utility company to limit the maximum power level usage of the outdoor unit The feature is activated by applying 24 volts AC power to the L and C terminals on the outdoor control Crankcase Heater Chec...

Страница 56: ...detected the sensor is faulty the sensor needs to be replaced Figure 38 Checking Crankcase Heater Thermostat STATUS CODE None ERROR CODES None Compressor Sound Cover All units come with a soft sided...

Страница 57: ...off compressor operation The auto reset switch closes when the compressor casing temperature falls to 151 187 F and the compressor is re energized This single pole single throw SPST bi metallic switch...

Страница 58: ...E 442 Critical The top cap switch has opened 5 times within one hour As a result the outdoor unit is locked out When compressor thermal protection sensor opens 5 times within 1 hour outdoor stops wor...

Страница 59: ...ts have an external device see illustration below NOTE A line filter is an electronic filter which is placed between electronic equipment and an external power source in order to attenuate conducted r...

Страница 60: ...ostat CHECKOUT VAC Voltage Check Check for 208 240 VAC power at inverter contactor red wires see figure 46 With unit operating check for main VAC to motor and outdoor control VDC output to motor 1 No...

Страница 61: ...e outdoor control therefore no status or error codes are displayed on either the outdoor control or iComfort Wi Fi room thermostat NOTE If the outdoor fan does not operate at the correct RPM or does n...

Страница 62: ...s NOTE System fault and lockout codes take precedence over system status codes cooling heating operating percentages or defrost dehumidification Only the latest active fault or lockout codes are displ...

Страница 63: ...on is re established E 125 Critical There is a hardware problem with the outdoor control There is a control hardware problem Replace the outdoor control if the problem pre vents operation and is persi...

Страница 64: ...s into the outdoor control Through the sensors the control detects outdoor ambient coil and liquid temperature fault conditions As the detected tem perature changes the resistance across the sensor ch...

Страница 65: ...61693 26 2 204829 92 0 7007 42 3 24525 9 9 62712 27 0 210805 90 6 7225 41 7 24934 9 3 63752 27 8 217080 89 4 7444 41 1 25349 8 8 64812 28 7 223677 88 1 7666 40 5 25769 8 3 65895 29 5 230621 86 9 7890...

Страница 66: ...sensor range Outdoor unit control will not perform demand or time temperature defrost operation System will still heat or cool Check the resistance of the coil sensor and compare to temperature resis...

Страница 67: ...ert Codes and Inverter LED Flash Codes NOTE System fault and lockout codes take precedence over system status codes cooling heating operating percentages or defrost dehumidification Only the latest ac...

Страница 68: ...ated If condi tion occurs 5 times within an hour system will lock out To clear disconnect power to outdoor unit and restart E 434 53 5 flashes 3 flashes Moderate Critical Outdoor control has lost comm...

Страница 69: ...24VAC System Operation System Refrigerant IMPORTANT The system must be operating at full capacity during charging Increase heat or decrease cooling the thermostat setting by 5 F to create system dema...

Страница 70: ...4 13 12 72 20 20 19 18 17 17 16 15 15 14 13 12 11 10 70 19 19 18 18 17 17 16 15 15 14 13 12 11 10 57 58 59 60 61 62 63 64 65 66 67 68 69 70 TEMPERATURE OF AIR ENTERING INDOOR COIL F INDOOR COIL DRY BU...

Страница 71: ...RN AIR TEMPERATURE IF NECESSARY OPERATE COOLING TO REACH THAT TEMPERATURE RANGE THEN SET THERMOSTAT TO HEATING MODE SETPOINT TO 77 F 25 C WHICH SHOULD CALL FOR SECOND STAGE HIGH STAGE HEATING WHEN PRE...

Страница 72: ...72 XC25 Figure 59 XC25 Charging Sticker...

Отзывы: