BLOWER DATA
SLP98UH070V36B BLOWER PERFORMANCE (less filter)
RIGHT SIDE RETURN AIR WITH OPTIONAL RETURN AIR BASE
HEATING BLOWER PERFORMANCE
Heating Adjust CFM Selections
Heating Input Range and Blower Volume - CFM
35%
40%
50%
60%
70%
80%
90%
100%
Increase (+15%) Heat CFM
471
519
614
709
805
900
996
1091
Increase (+7.5%) Heat CFM
435
480
570
660
751
841
931
1021
Default Heat CFM
399
441
526
611
696
781
866
951
Decrease (-7.5% ) Heat CFM
369
408
486
564
643
721
799
877
Decrease (-15% ) Heat CFM
339
375
446
517
589
660
732
803
COOLING BLOWER PERFORMANCE
Cooling Adjust CFM
Selections
Blower Speed Selections
First Stage Cool Speed - cfm
Second Stage Cool Speed - cfm
Low
Medium-
Low
Medium
High
High
(Default)
Low
Medium-
Low
Medium
High
High
(Default)
Increase (+10%) Cool CFM
595
715
815
950
855
1045
1205
1350
Default Cool CFM
520
655
755
840
790
945
1090
1255
Decrease (-10%) Cool CFM
490
595
670
745
720
845
985
1130
The effect of static pressure is included in air volumes shown.
The following control configurations are available. See Installation Instructions for details and DIP switch settings.
Heat Modes Available (Heating Blower Performance Table):
Single stage thermostat:
- 35%, 70%, 100% input (three-stage) with time delays in-between
Two-stage thermostat:
- Variable Rate Capacity Mode - furnace automatically adjusts firing rate based on first- and second-stage cycle times
- W1 demand at 70% input, W2 demand at 100% input. No delay between stages
icomfort Touch™ Communicating Thermostat:
- Variable Rate Capacity Mode - furnace automatically adjusts firing rate based on first- and second-stage cycle times
- 35%, 60%, 80%, 100% (four-stage) with time delays in-between
Cool Mode Available (Cooling Blower Performance table):
First stage COOL (two-stage air conditioning units only) is approximately 70% of the same second stage COOL speed position.
Continuous Fan speeds are approximately 28%, 38%, 70% and 100% (DIP switch selectable) of the same second-stage COOL speed position
minimum 300 cfm.
Lennox Harmony III™ Zoning System Applications - Minimum blower speed is 250 cfm.
SLP98UH090V36C BLOWER PERFORMANCE (less filter)
BOTTOM RETURN AIR
HEATING BLOWER PERFORMANCE
Heating Adjust CFM Selections
Heating Input Range and Blower Volume - CFM
35%
40%
50%
60%
70%
80%
90%
100%
Increase (+15%) Heat CFM
687
734
827
921
1014
1108
1201
1295
Increase (+7.5%) Heat CFM
654
697
782
867
953
1038
1123
1209
Default Heat CFM
621
660
737
814
891
968
1045
1122
Decrease (-7.5% ) Heat CFM
581
616
687
757
828
899
970
1041
Decrease (-15% ) Heat CFM
540
572
637
701
766
830
895
959
COOLING BLOWER PERFORMANCE
Cooling Adjust CFM
Selections
Blower Speed Selections
First Stage Cool Speed - cfm
Second Stage Cool Speed - cfm
Low
Medium-
Low
Medium
High
High
(Default)
Low
Medium-
Low
Medium
High
High
(Default)
Increase (+10%) Cool CFM
625
710
830
950
875
1040
1210
1360
Default Cool CFM
565
670
760
860
800
945
1100
1240
Decrease (-10%) Cool CFM
520
610
685
785
720
840
970
1115