FIGURE 22
TYPICAL EXHAUST PIPE CONNECTIONS AND CONDENSATE TRAP INSTALLATION
IN UPFLOW APPLICATIONS
TRANSITION
2”
2”
2”
3”
2”
Use only the factory− supplied
trap. Trap can be installed on
either side of cabinet within 5 ft
of the furnace
DO NOT transition
from smaller to larger
pipe size in horizontal
runs of exhaust pipe.
TRAP
FIGURE 23
2”
TRANSITION
2”
SIDE VIEW
2”
2”
2”
2”
or
TYPICAL EXHAUST PIPE CONNECTIONS AND CONDENSATE TRAP INSTALLATION
IN HORIZONTAL AIR APPLICATIONS
(RIGHT HAND DISCHARGE SHOWN)
3”
2”
45°
MAX
45°
MAX
DO NOT transition
from smaller to larger
pipe size in horizontal
runs of exhaust pipe.
Use only the factory−
supplied trap. Trap MUST
be installed on left side
for left hand discharge
within 5 ft of the furnace.
12" max.