BLOWER DATA - DIRECT DRIVE - KCB030
BLOWER TABLE INCLUDES RESISTANCE FOR BASE UNIT ONLY WITH DRY INDOOR COIL AND AIR FILTERS IN PLACE.
FOR ALL UNITS ADD:
1 - Any factory installed options air resistance (economizer, wet coil, etc.) See page 41.
2 - Any field installed accessories air resistance (electric heat, duct resistance, diffuser, etc.) See page 41.
External Static
Pressure (in. w.g.)
Air Volume (cfm) at Various Blower Speeds
208 VOLTS
230 VOLTS
High
Medium
Low
High
Medium
Low
2.5 Ton Standard Efficiency (Downflow)
KCB030S
0.0
1199
928
838
1379
1085
877
0.1
1229
926
813
1409
1086
872
0.2
1206
928
782
1367
1094
850
0.3
1183
881
742
1350
1047
820
0.4
1159
843
686
1321
1009
783
0.5
1136
812
643
1282
981
762
0.6
1103
766
569
1242
921
705
0.7
1046
728
496
1195
888
625
0.8
953
648
432
1134
792
583
0.9
909
584
335
1037
738
492
1.0
783
465
247
926
592
411
2.5 Ton Standard Efficiency (Horizontal)
KCB030S
0.0
1152
909
801
1325
1063
838
0.1
1152
893
770
1321
1048
826
0.2
1136
866
734
1288
1021
798
0.3
1104
826
697
1260
982
771
0.4
1072
787
643
1222
942
734
0.5
1041
747
589
1175
903
698
0.6
1009
707
534
1137
850
662
0.7
946
654
467
1081
797
588
0.8
861
588
396
1024
718
535
0.9
798
508
319
911
642
468
1.0
715
443
237
846
564
394