Page 15
BLOWER DATA - DIRECT DRIVE - KGB024
BLOWER TABLE INCLUDES RESISTANCE FOR BASE UNIT ONLY WITH DRY INDOOR COIL AND AIR FILTERS IN PLACE.
FOR ALL UNITS ADD:
1 - Any factory installed options air resistance (larger gas heat section, economizer, wet coil, etc.) See page 41.
2 - Any field installed accessories air resistance (duct resistance, diffuser, etc.) See page 41.
External Static
Pressure (in. w.g.)
Air Volume (cfm) at Various Blower Speeds
208 VOLTS
230 VOLTS
High
Medium
Low
High
Medium
Low
2 Ton Standard Efficiency (Downflow)
KGB024S
0.0
1275
979
878
1453
1140
926
0.1
1262
960
834
1440
1124
912
0.2
1243
938
790
1420
1096
884
0.3
1218
909
746
1396
1065
853
0.4
1186
866
710
1352
1033
822
0.5
1137
838
657
1316
986
774
0.6
1104
795
604
1263
954
727
0.7
1055
752
534
1210
906
680
0.8
990
694
463
1158
859
632
0.9
925
637
392
1070
764
538
1.0
794
523
290
928
669
477
2 Ton Standard Efficiency (Horizontal)
KGB024S
0.0
1204
937
818
1370
1098
879
0.1
1186
913
788
1352
1066
864
0.2
1164
882
748
1327
1034
839
0.3
1137
860
710
1300
1001
809
0.4
1104
818
670
1263
968
768
0.5
1070
775
612
1227
925
728
0.6
1031
733
554
1190
881
688
0.7
991
690
500
1136
816
628
0.8
937
626
432
1081
751
557
0.9
804
566
362
1009
665
492
1.0
678
497
287
900
565
416