BLOWER DATA - DIRECT DRIVE - KCB024
BLOWER TABLE INCLUDES RESISTANCE FOR BASE UNIT ONLY WITH DRY INDOOR COIL AND AIR FILTERS IN PLACE.
FOR ALL UNITS ADD:
1 - Any factory installed options air resistance (economizer, wet coil, etc.) See page 41 .
2 - Any field installed accessories air resistance (electric heat, duct resistance, diffuser, etc.) See page 41.
External Static
Pressure (in. w.g.)
Air Volume (cfm) at Various Blower Speeds
208 VOLTS
230 VOLTS
High
Medium
Low
High
Medium
Low
2 Ton Standard Efficiency (Downflow)
KCB024S
0.0
1244
956
859
1414
1098
876
0.1
1226
934
820
1401
1092
870
0.2
1201
906
782
1379
1070
848
0.3
1180
877
727
1348
1039
819
0.4
1152
841
690
1318
1008
775
0.5
1118
812
634
1288
968
746
0.6
1090
768
579
1243
937
702
0.7
1048
725
505
1197
890
659
0.8
1006
667
431
1152
827
600
0.9
950
609
357
1076
749
528
1.0
839
493
248
986
623
468
2 Ton Standard Efficiency (Horizontal)
KCB024S
0.0
1166
910
801
1376
1071
842
0.1
1156
893
770
1342
1054
826
0.2
1136
866
734
1307
1021
808
0.3
1115
826
697
1269
982
771
0.4
1083
800
643
1232
956
734
0.5
1051
747
589
1194
903
698
0.6
1009
707
534
1137
850
662
0.7
946
668
467
1100
797
588
0.8
861
588
396
1024
744
534
0.9
736
508
319
948
652
466
1.0
560
385
237
845
549
392