Page 31
BLOWER DATA - DIRECT DRIVE - KCA060
BLOWER TABLE INCLUDES RESISTANCE FOR BASE UNIT ONLY WITH DRY INDOOR COIL AND AIR FILTERS IN PLACE.
FOR ALL UNITS ADD:
1 - Any factory installed options air resistance (economizer, wet coil, etc.) See”BLOWER DATA” on page 41.
2 - Any field installed accessories air resistance (electric heat, duct resistance, diffuser, etc.) See”BLOWER DATA” on page 41.
External Static
Pressure (in. w.g.)
Air Volume (cfm) at Various Blower Speeds
208 VOLTS
230 VOLTS
460/575 VOLTS
High
Low
High
Low
High
Low
5 Ton Standard Efficiency (Downflow)
KCA060S
0.0
2121
1644
2324
1952
2160
1750
0.1
2162
1660
2315
1991
2128
1733
0.2
2100
1704
2285
1946
2092
1712
0.3
2078
1667
2230
1928
2054
1687
0.4
2056
1646
2185
1909
2005
1652
0.5
2014
1626
2154
1873
1972
1629
0.6
1953
1592
2049
1821
1907
1583
0.7
1913
1594
1966
1787
1858
1549
0.8
1830
1519
1936
1715
1810
1515
0.9
1774
1509
1763
1650
1744
1469
1.0
1601
1319
1649
1508
1679
1400
5 Ton Standard Efficiency (Horizontal)
KCA060S
0.0
2038
1611
2222
1875
2225
1885
0.1
2026
1601
2194
1866
2236
1895
0.2
1978
1590
2145
1833
2186
1853
0.3
1940
1563
2096
1800
2137
1818
0.4
1902
1537
2047
1766
2106
1799
0.5
1845
1497
1973
1716
2031
1763
0.6
1787
1470
1924
1666
2002
1711
0.7
1730
1431
1850
1616
1970
1677
0.8
1653
1378
1776
1549
1853
1607
0.9
1558
1312
1677
1449
1800
1586
1.0
1462
1257
1579
1377
1750
1418