Page 32
BLOWER DATA - DIRECT DRIVE - KCB060
BLOWER TABLE INCLUDES RESISTANCE FOR BASE UNIT ONLY WITH DRY INDOOR COIL AND AIR FILTERS IN PLACE.
FOR ALL UNITS ADD:
1 - Any factory installed options air resistance (economizer, wet coil, etc.) See page 41.
2 - Any field installed accessories air resistance (electric heat, duct resistance, diffuser, etc.) See page 41.
External Static
Pressure (in. w.g.)
Air Volume (cfm) at Various Blower Speeds
208 VOLTS
230 VOLTS
460/575 VOLTS
High
Low
High
Low
High
Low
5 Ton Standard Efficiency (Downflow)
KCB060S
0.0
1883
1570
2074
1785
2074
1785
0.1
1871
1550
2050
1760
2050
1760
0.2
1855
1538
2018
1735
2018
1735
0.3
1828
1523
1986
1704
1986
1704
0.4
1786
1499
1937
1679
1937
1679
0.5
1759
1476
1905
1642
1905
1642
0.6
1718
1452
1856
1605
1856
1605
0.7
1676
1421
1791
1567
1791
1567
0.8
1622
1358
1726
1505
1726
1505
0.9
1539
1277
1628
1406
1628
1406
1.0
1399
- - -
1502
1300
1502
1300
5 Ton Standard Efficiency (Horizontal)
KCB060S
0.0
1852
1534
2046
1713
2046
1713
0.1
1844
1532
2024
1711
2024
1711
0.2
1831
1526
1998
1706
1998
1706
0.3
1800
1504
1954
1681
1954
1681
0.4
1769
1477
1918
1654
1918
1654
0.5
1722
1450
1865
1612
1865
1612
0.6
1674
1423
1812
1570
1812
1570
0.7
1627
1369
1742
1515
1742
1515
0.8
1565
1315
1672
1459
1672
1459
0.9
1470
1241
1530
1376
1530
1376
1.0
1323
- - -
1426
1242
1426
1242