C-Refrigerant Charge and Check - Fin/Tube Coil
KGA/KCA 036 to 060
WARNING-Do not exceed nameplate charge under
any condition.
This unit is factory charged and should require no further
adjustment. If the system requires charge,
reclaim the
charge,
evacuate the system and
add required
nameplate charge.
NOTE - System charging is not recommended below
60°F (15°C). In temperatures below 60°F (15°C) ,
the
charge
must
be weighed into the system.
If weighing facilities are not available, or to check the
charge, use the following procedure:
1- Attach gauge manifolds and operate unit in cooling
mode until system stabilizes (approximately five
minutes). Make sure outdoor air dampers are closed.
2- Use a thermometer to accurately measure the
outdoor ambient temperature.
3- Apply the outdoor temperature to tables 7 through 12
to determine normal operating pressures.
4- Compare the normal operating pressures to the
pressures obtained from the gauges. Minor
variations in these pressures may be expected due to
differences in installations. Significant differences
could mean that the system is not properly charged
or that a problem exists with some component in the
system.
Correct any system problems before
proceeding.
5- If discharge pressure is high, remove refrigerant from
the system. If discharge pressure is low, add
refrigerant to the system.
Add or remove charge in increments.
Allow the system to stabilize each time
refrigerant is added or removed.
6- Use the following approach method along with the
normal operating pressures to confirm readings.
TABLE 7
KGA 036S -3 & LOWER; KCA 036S -2 & LOWER
NORMAL OPERATING PRESSURES
Outdoor Coil
Entering Air Temp
Discharge
+10 psig
S 5
psig
65
5
F
269
146
75
5
F
311
148
85
5
F
357
150
95
5
F
407
152
105
5
F
466
155
115
5
F
532
157
TABLE 8
KGA 036S -4 & HIGHER; KCA 036S -3 & HIGHER
NORMAL OPERATING PRESSURES
Outdoor Coil
Entering Air Temp
Discharge
+10 psig
S 5
psig
65
°
F
275
137
75
°
F
312
139
85
°
F
353
142
95
°
F
399
146
105
°
F
450
149
115
°
F
506
150
TABLE 9
KGA 048S -3 & LOWER; KCA 048S -2 & LOWER
NORMAL OPERATING PRESSURES
Outdoor Coil
Entering Air Temp
Discharge
+10 psig
S 5
psig
65
°
F
280
142
75
°
F
321
144
85
°
F
365
147
95
°
F
414
149
105
°
F
467
151
115
°
F
526
153
TABLE 10
KGA 048 -4 & HIGHER; KCA 048S -3 & HIGHER
NORMAL OPERATING PRESSURES
Outdoor Coil
Entering Air Temp
Discharge
+10 psig
S 5
psig
65
°
F
279
132
75
°
F
319
136
85
°
F
360
140
95
°
F
404
144
105
°
F
454
147
115
°
F
506
148
TABLE 11
KGA 060S -4 & LOWER; KCA 060S -3 & LOWER
NORMAL OPERATING PRESSURES
Outdoor Coil
Entering Air Temp
Discharge
+10 psig
S 5
psig
65
°
F
265
136
75
°
F
302
137
85
°
F
344
139
95
°
F
391
142
105
°
F
442
146
115
°
F
499