I–UNIT COMPONENTS (Figure 1)

G25MV unit components are shown in figure 1. The
blower controls, gas valve and burners can be accessed
by removing the front access panel. A separate blower
access door is located behind the front access panel.
Electrical control components are mounted to the
blower access door. Units are factory equipped with
bottom return air panels

A–Blower Door Components (Figure 2)

Electrical burner control and blower control components
are located on the outside surface of the blower access
door. Jackplugs allow the blower door to be easily re-
moved for blower service.

Located on the blower door are the unit transformer
(T1), burner control (A3), VSP2 blower control board
(A24), and door interlock switch (S51).

1– Control Transformer (T1)

A transformer located on the blower door provides power
to the low voltage section of the unit. Transformers on all
models are rated 50VA with a 120V primary and a 24V
secondary. The transformer is protected by a 3.0 amp
circuit breaker.

2–Door Interlock Switch (S51)

A door interlock switch rated 16A at 125VAC is located
on the blower access door. The switch is wired in series
with line voltage. When the blower door is removed the
unit will shut down.

3– Burner Control (A3)

All G25MV units utilize a burner control manufactured
by RAM Electronics Corporation. The “RAM” board is
a printed circuit board which controls the gas valve,
combustion air blower and ignition. It also monitors
the flame, limit and gas valve operation. The board
utilizes both 120 and 24VAC. See figure 3. The board is
equipped with a diagnostic LED for use when trouble-
shooting the unit.

When the furnace is idle (blower off and no heating or
cooling demand), the diagnostic LED flashes at a
slow steady rate. On a call for heat, the diagnostic
LED begins flashing at a fast rate and the combustion
air blower is energized. The LED flashes different
codes to indicate problem conditions. The diagnostic
LED lights red (not flashing) to indicate control board fail-
ure. Table 1 shows how to interpret the other LED modes.

Pre-Purge

On a call for heat, the combustion air blower begins
operating. If the combustion air prove switch closes,
the combustion air blower continues to operate for
30 seconds (pre-purge) before allowing ignition. Pre-
purge allows the heat exchanger to be cleared of
combustion products and to introduce fresh air for
combustion. If the combustion air prove switch does
not close, the combustion air blower continues to run
indefinitely (until the prove switch closes).

Post-Purge

After a demand, the combustion air blower continues
to operate for 5 seconds (post-purge) before stopping.
Post-purge allows the heat exchanger to be cleared of
combustion products.

Ignition Control

The ignition control is a hot surface ignition control
module integral to the burner control. See table 2 and
figure 3. When there is a call for heat, the control delays
ignition until combustion air blower operation has been
proved and pre-purge period has elapsed. It then ener-
gizes a hot surface for 35 seconds. At the end of the 35
seconds the main gas valve opens on high fire. Trial for
ignition lasts for 7 seconds. At the same time, the control
begins monitoring the flame sensor. If the flame current
is too weak (less than 1 microamp) or if the burners do
not ignite (within the 7 second ignition trial), the control
will shut off the hot surface ignitor and the combustion
air blower and de-energize the gas valve. Flame current
should be between 1 and 5 microamps to keep the gas
valve open.

The control will attempt to ignite the burners up to two
more times. Each time the control restarts the ignition
sequence, it begins with a 30 second pre-purge. If flame
is not sensed after the third trial, the control locks out.
Lockout means that the control shuts off the gas valve,
spark and combustion air blower for 60 minutes. At the
end of 60 minutes the control completely resets and
will attempt ignition up to three times. The control
can be manually reset before the end of 60 minutes
by momentarily turning off power to the unit.

When flame is sensed, the indoor blower starts after a
45 second delay. Gas valve remains open and blower
continues to run until demand stops, flame sensor
senses loss of flame, a limit opens or the combustion
air prove switch opens. If any of these events occur
during a thermostat demand, the gas valve closes
and the diagnostic LED registers the error condition.

Содержание G25MV Series

Страница 1: ...equipped with an electronic vari able speed VSM fan motor The VSM motor maintains a specified air volume throughout the entire external static range Units may be installed in upflow downflow or horizo...

Страница 2: ...er is furnished with kit 2 in x 3 in 51 mm x 76 mm flue adaptor furnished with 60 input furnaces for connection to furnace induced draft blower 2 in x 4 in 51 mm x102 mm flue adaptor furnished with 75...

Страница 3: ...LIMITS FRONT LOUVERED PANEL DOOR INTERLOCK SWITCH BURNER CONTROL BOARD TRANSFORMER PRESSURE SWITCHES NOx TURBULATOR VSP2 BOARD FLUE THERMOSTAT VARIABLE SPEED BLOWER MOTOR PRIMARY LIMIT G25MV BLOWER D...

Страница 4: ...erating If the combustion air prove switch closes the combustion air blower continues to operate for 30 seconds pre purge before allowing ignition Pre purge allows the heat exchanger to be cleared of...

Страница 5: ...Switch Open Failed to Prove Combustion Blower Operation or Blocked Vent Repair or Replace as Necessary Four Flashes Open Limit Check Primary Limit Rollout Switches and Secondary Limits Find source of...

Страница 6: ...range The unit uses the VSP2 1 variable speed control board located on the blower access door which controls the blower speed and provides diagnostic LEDs The control has both a non adjustable factor...

Страница 7: ...Ref V ICM2 reference voltage PIN 11 Heat Tap Heating blower speed programming PIN 12 C 24 VAC common PIN 13 cfm Motor speed diagnostic signal Diagnostic LED Lights ON OFF DS3 indicates there is a dem...

Страница 8: ...mony II zoning applications HEATING BLOWER jumper must be in position 2 The HEAT jumper is used to set the blower speed to obtain the required CFM as outlined in HEAT SPEED section of the tables on pa...

Страница 9: ...indicate the blower is operating NOTE In Harmony II zoning ap plications HTG BLOWER jumper must be in position 2 HARMONY ZONED APPLICATIONS The blower speed is controlled by the PWM pulse width modula...

Страница 10: ...This allows for precise control of motor speed and allows the motor to compensate for varying load conditions as sensed by the controller In this case the controller monitors the static workload on th...

Страница 11: ...s down Then the motor will immediately attempt a restart The shutdown feature provides protection in case of a frozen bearing or blocked blower wheel The motor may attempt to start eight times If the...

Страница 12: ...oke Coil L13 A choke coil is used on all G25MV units The choke is located on the blower housing and is used to block radio frequency interference Precautions If the G25MV or its electronically control...

Страница 13: ...auto reset switches which actuate on a temperature rise The switches are factory set and cannot be adjusted The 1 S21 limit shown on the top opens at 140 F 5 F 60 0 C 2 8 C on a temperature rise and...

Страница 14: ...mit located on top of combustion air blower collector box see figure 15 The limit is a N C SPST auto reset limit which opens at 200 F 5 F 93 3 C 2 8 C on a temperature rise and closes at 160 F 8 F 71...

Страница 15: ...same type valve must be used 24VAC terminals and gas control knob are located on top of the valve All terminals on the gas valve are connected to wires from the electronic burner control 24V applied t...

Страница 16: ...to atmospheric pres sure If the flue becomes obstructed during operation and either switch senses a loss of negative pressure pressure becomes more equal with atmospheric pressure the switch opens th...

Страница 17: ...anual shut off valve before pressure testing to isolate furnace from gas supply FIGURE 22 MANUAL MAIN SHUT OFF VALVE GAS VALVE WILL NOT HOLD TEST PRESSURE IN EXCESS OF 0 5 PSIG 14 W C GAS VALVE CAP GA...

Страница 18: ...ered panel and disconnect the sensor wire from the flame sensor 2 Place meter in series between flame sensor and sensor wire Connect the positive lead of meter to the sensor wire and the negative lead...

Страница 19: ...the return duct as above For systems with non ducted returns leave the other end of the manometer open to the atmosphere 3 With only the blower motor running and the evaporator coil dry observe the ma...

Страница 20: ...lly clean piping thor oughly after leak detection has been completed Can cause damage to piping resulting in gas leaks fire or explosion C Supply Air Blower Check and clean blower wheel Motors are pre...

Страница 21: ...5 The combustion air blower B6 is energized by A3 If the gas valve is energized on high fire then B6 is energized on high speed if the gas valve is energized on low fire then B6 is energized on low s...

Страница 22: ...ANGED THROUGHOUT SEQUENCE THERMOSTAT CALLS FOR COOLING SYSTEM FAN SWITCHES TO HEATING SPEED AFTER SELECTED DELAY ACCA ACCH TERMINALS REMAIN ENERGIZED SYSTEM FAN SWITCHES TO CONTINUOUS SPEED AND ENERGI...

Страница 23: ...OCKOUT MAIN VALVE OFF COMBUSTION AND SYSTEM FANS ON RESET OR REPLACE ROLLOUT SWITCH BURNER CONTROL LED 4 flashes MAIN VALVE OFF COMBUSTION SYSTEM FANS ON SEQUENCE HOLDS UNTIL SWITCH CLOSES BURNER CONT...

Страница 24: ...NO NO YES YES DOES UNIT OPERATE CHECK 1 UNIT POWER 2 INTERLOCK SWITCH 3 TRANSFORMER 4 LIMIT SWITCH END OF TEST REPLACE THE VSP2 1 HEATING MODE NO YES YES YES AFTER THE SELECTED TIME DOES BLOWER TURN...