CLIMATIC™ 60 – AIRCOOLED CHILLERS
Page 94
MUL
41E
-0610/
06-2011
ALARM 116, 216:
REVERSING VALVE, BLOCKED
Description
The CLIMATIC™ 60 hasn’t measure a difference of pressure of 2 bars for 5s, while a compressor was running for
30s.
•
Alarm 116: Reversing valve blocked on the circuit 1,
•
Alarm 216: Reversing valve blocked on the circuit 2.
Action
Immediate shut down of the complete circuit. The alarm is signalling.
Reset
Once the circuit has been stopped for 2 minutes, the alarm is automatically deleted. Up to 3 trips can occur during
a day and are saved in the alarm historic. The two first trips don’t give the alarm alert except if a trip is still present
during 1 hour, and are automatically reset every day at 6h00 am. The third trip activates the fault report and must
be manually reset.
Possible cause(s)
•
Problem with wiring connection,
•
Problem of reversing valve.
Remedies
•
Check the wiring connection,
•
Replace the reversing valve.