CLIMATIC™ 60 – AIRCOOLED CHILLERS
Page 78
MUL
41E
-0610/
06-2011
ALARM 043, 044:
PUMP CONDENSER, ELECTRICAL FAILURE
Description
The thermal magnetic circuit breaker protection of the condenser pump 1 or 2 has tripped for 5s, whereas the
pump was in demand for at least 5s.
•
Alarm 43: Thermal magnetic circuit breaker protection of the pump 1,
•
Alarm 44: Thermal magnetic circuit breaker protection of the pump 2.
Action
Case of single pump:
•
Immediate shut down of the pump and the unit.
•
The alarm is signalling.
Case of double pump:
•
Immediate shut down of the current pump and the compressor(s).
•
Time delay of 30s,
•
Start the second pump if possible (refers to the “PUMP CONDENSER MANAGMENENT“ paragraph)
•
The alarm is signalling.
Reset
These alarms are manually reset.
Possible cause(s)
•
Problem with wiring connection,
•
Circuit breaker wrong adjusted.
Remedies
•
Check the pump connections,
•
Adjust the circuit breaker.