CLIMATIC™ 60 – AIRCOOLED CHILLERS
MUL
41E
-0610/
06-2011
Page 83
ALARM 071, 072:
EXPANSION BOARD LINK, FAILURE
Description
The link between the expansion board(s) 1 or 2 and the CLIMATIC™ 60 is disconnected.
•
Alarm 71: The expansion board N°1 is disconnected from the CLIMATIC™ 60,
•
Alarm 72: The expansion board N°2 is disconnected from the CLIMATIC™ 60.
Action
•
Immediate shut down of the unit.
•
The alarm is signalling.
Reset
Once the communication is re-established for 30s, the alarm is automatically deleted. Up to 6 trips can occur during
a day and are saved in the alarm historic. The five first trips don’t give the alarm alert except if a trip is still present
during 1 hour, and are automatically reset every day at 6h00 am. The sixth trip activates the fault report and must
be manually reset.
Possible cause(s)
•
Problem with wiring connection,
•
Wrong expansion board address,
•
Expansion board damaged.
Remedies
•
Check the wiring connections,
•
Check the expansion board address (refers to the “FREE INPUT / OUTPUT” paragraph),
•
Replace the expansion board.