CLIMATIC™ 60 – AIRCOOLED CHILLERS
MUL
41E
-0610/
06-2011
Page 91
ALARM 111, 112, 211, 212:
DISCHARGE TEMPERATURE COMPRESSOR, OVERHEATING
Description
The CLIMATIC™ 60 has detected an overheating discharge temperature on the compressor.
•
Alarm 111: Overheating discharge temperature on the circuit 1 – compressor 1,
•
Alarm 112: Overheating discharge temperature on the circuit 1 – compressor 2,
•
Alarm 211: Overheating discharge temperature on the circuit 2 – compressor 1,
•
Alarm 212: Overheating discharge temperature on the circuit 2 – compressor 2.
Action
Immediate shut down of the compressor. The alarm is signalling.
Reset
Once the discharge temperature has reached a permitted operating range for 2 minutes, the alarm is automatically
deleted. Up to 6 trips can occur during a day and are saved in the alarm historic. The five first trips don’t give the
alarm alert except if a trip is still present during 1 hour, and are automatically reset every day at 6h00 am. The sixth
trip activates the fault report and must be manually reset.
Possible cause(s)
•
Problem of refrigerant capacity,
•
Compressor damage.
Remedies
•
Check the frigorific operating,
•
Replace the compressor.