MAINTENANCE PLAN
BALTIC R410A-IOM-0708-E
Page 123
Task
Operating mode
Mo
n
th
ly
Qu
a
rt
e
rly
6
m
o
n
th
ly
Ye
a
rl
y
B
4
w
in
te
r
Es
ti
m
a
te
d
T
im
e
(m
in
)
Check outdoor fans and fan guards
Check the fan blades conditions and all fan
guards and protections
o
5
Check position of all sensors
Check the good positioning and operation of all
sensors of all sensors. Check the values given in
the control system. Replace sensor if necessary
o
5
Check and clean if necessary all
fresh air grilles
Check the fresh air grilles (if fitted). If dirty or
damaged, remove them from unit and clean with
high pressure water cleaner. Refit on unit once
clean and dry.
o
5
Clean condensate drain, indoor and
outdoor coils (following local
regulations)
Visually check the coils for dirt. If not too dirty,
cleaning with a light brush may be enough
(WARNING: Fins and copper tubes are very
fragile! Any damage WILL reduce the
performances of the unit). If very dirty, deep
industrial cleaning is required using de-greasing
agents.(External contractors must be called).
o /
[]
1h if
clea
ning
Check electric heater element for
excessive corrosion
Isolate the unit; Pull the electric heater out of the
heater module box and check the resistances of
traces of corrosion; Replace resistance as
required;
o
1h if
repl
ace
men
t
Check anti-vibration mountings, for
wear and tear.
Visually check anti-vibration mountings on
compressors and centrifugal fan. Replace if
damaged.
o
1h if
repl
ace
men
t
Check refrigeration circuit for traces
of acid in the oil
Take a sample of oil from the refrigeration
circuit.
[]
Check Glycol concentration in the
HWC circuit
Check the glycol concentration in the
pressurised water circuit. ( a concentration of
30% gives a protection down to aprox. -15°C)
check the circuit pressure
[]
30
Check defrost cycle with 4-way valve
inversion.
Switch the unit to heat pump mode. Change the
set point to obtain the standard defrost mode
and reduce the cycle time to the min value.
Check the operation of the defrost cycle.
[]
30
Gas burner module check for
corrosion
Pull out the burner to access the tubes (refer to
Gas burner section in the IOM)
[]
30
Sweeping and cleaning the gas
burner
Clean the in-shot burners and the blower wheel
lightly with a brush. Sweep the flue and flue box.
Wipe-off the dust from the housing of the motor.
Clean combustion air inlet louvers Pull-out
baffles from the tubes, sweep the tubes
CHECK FLUE BOX GASKET
[]
30
Gas supply pressures / connections
checks
refer to Gas burner section in the IOM for details
[]
15
Gas regulation valve settings
refer to Gas burner section in the IOM for details
[]
30
Check gas burner safety switches
refer to Gas burner section in the IOM for details
[]
30
Содержание BAC020SNM
Страница 11: ...COMMISSIONING REPORT BALTIC R410A IOM 0708 E Page 10 ...
Страница 65: ...VENTILATION AIRFLOW BALANCING BALTIC R410A IOM 0708 E Page 64 PERFORMANCE CURVES AT12 9S ROOF TOP ...
Страница 66: ...VENTILATION AIRFLOW BALANCING BALTIC R410A IOM 0708 E Page 65 ROOF TOP AT15 11S ...
Страница 67: ...VENTILATION AIRFLOW BALANCING BALTIC R410A IOM 0708 E Page 66 ROOF TOP AT15 15S ...
Страница 68: ...VENTILATION AIRFLOW BALANCING BALTIC R410A IOM 0708 E Page 67 AT15 11G2L ROOF TOP EXHAUST ROOF CURB ...
Страница 69: ...VENTILATION AIRFLOW BALANCING BALTIC R410A IOM 0708 E Page 68 AT10 10S EXHAUST ROOF CURB ...
Страница 70: ...VENTILATION AIRFLOW BALANCING BALTIC R410A IOM 0708 E Page 69 EXHAUST ROOF CURB AT10 8G2L ...
Страница 71: ...VENTILATION AIRFLOW BALANCING BALTIC R410A IOM 0708 E Page 70 EXHAUST ROOF CURB AT10 10G2L ...
Страница 85: ...HEATING GAS BURNER BALTIC R410A IOM 0708 E Page 84 MODULE GAZ 20KW B BOX MODULE GAZ 33KW B BOX Fig 67 Fig 68 ...
Страница 86: ...HEATING GAS BURNER BALTIC R410A IOM 0708 E Page 85 MODULE GAZ 20KW C BOX MODULE GAZ 46KW C BOX Fig 69 Fig 70 ...
Страница 87: ...HEATING GAS BURNER BALTIC R410A IOM 0708 E Page 86 MODULE GAZ 33KW D BOX MODULE GAZ 60KW D BOX Fig 71 Fig 72 ...
Страница 88: ...HEATING GAS BURNER BALTIC R410A IOM 0708 E Page 87 MODULE GAZ 60KW E BOX MODULE GAZ 120KW E BOX Fig 73 Fig 74 ...
Страница 93: ...HEATING MODULATING GAS BURNER BALTIC R410A IOM 0708 E Page 92 MODULATING GAZ 120KW E BOX Fig 89 ...
Страница 116: ...PRINCIPLE SKETCHES BALTIC R410A IOM 0708 E Page 115 BAH 035 to 055 dual circuit BAC 035 to 055 dual circuit ...
Страница 126: ...CERTIFICATES BALTIC R410A IOM 0708 E Page 125 ...
Страница 127: ...CERTIFICATES BALTIC R410A IOM 0708 E Page 126 ...
Страница 128: ...CERTIFICATES BALTIC R410A IOM 0708 E Page 127 ...
Страница 129: ...CERTIFICATES BALTIC R410A IOM 0708 E Page 128 ...
Страница 130: ...CERTIFICATES G4 FILTERS BALTIC R410A IOM 0708 E Page 129 ...
Страница 131: ...CERTIFICATES F7 FILTERS BALTIC R410A IOM 0708 E Page 130 ...
Страница 132: ...CERTIFICATES CLIMAVER 202 BALTIC R410A IOM 0708 E Page 131 ...
Страница 133: ...CERTIFICATES CLIMAVER 274 BALTIC R410A IOM 0708 E Page 132 ...
Страница 134: ...CERTIFICATES BALTIC R410A IOM 0708 E Page 133 ...
Страница 135: ...CERTIFICATES BALTIC R410A IOM 0708 E Page 134 ...
Страница 136: ...CERTIFICATES BALTIC R410A IOM 0708 E Page 135 ...