CLIMATIC 50 – ROOFTOP – VERSION 23
BALTIC R410A-IOM-0708-E
Page 103
Sdc.4
Screen Sdc.4 is used to change the override values
The present time period is shown on the 2nd line. This period will remain fixed
for 3 hours.
Press
to position the cursor over the ‘
Room SP
’ line
With button
or
set the desired temperature and confirm with the ‘Enter’ button.
The cursor is positioned over the ‘Min
F
A’ line
With button
or
set the desired air change rate and confirm
with button
The DC50 returns to the main display.
If the unit is not fitted with the economiser option, only the temperature line is
displayed.
A single press on the ‘Esc’ button cancels the changes and returns to the main
screen.
It will revert back to the main screen after 15 seconds without any activity.
Clock Menu
These screens are used to display and change the time and date on the BM50.
Sdc.5
From the main screen, press the ‘clock’ button
The Sdc.5 screen displays the time and date.
To change the time or date:
Press
to position the cursor over the time.
With button
or
set the time and confirm with button
Position the cursor over ‘minutes’.
With button
or
set the minutes and confirm with button
Position the cursor over ‘month’.
With button
or
set the
month and confirm with button
Position the cursor over ‘year’.
With button
or
set the year and confirm with button
Position the cursor over ‘hours’.
…
Pressing the ‘Esc’ returns to the main screen
It will revert back to the main screen after 15 seconds without any activity.
“Programming” Menu
These screens are used to display and change the set points of the BM50 for each time period.
Sdc.6
From the main screen, press the "Prg" button,
Screen Sdc.6 displays the temperature set point and the minimum airflow rate.
If the unit is not fitted with the economiser option, only the temperature line is
displayed.
With button
or
set the desired temperature and confirm with button
.
The cursor is positioned over the ‘Min.
F
A.’ line
With button
or
set the desired air change rate and confirm with button
.
Position the cursor over the ‘
Room SP
’ line
Pressing the ‘Esc’ r
eturns to the main screen.
The time period can be selected by repeatedly pressing the ‘Clock’ button,
Содержание BAC020SNM
Страница 11: ...COMMISSIONING REPORT BALTIC R410A IOM 0708 E Page 10 ...
Страница 65: ...VENTILATION AIRFLOW BALANCING BALTIC R410A IOM 0708 E Page 64 PERFORMANCE CURVES AT12 9S ROOF TOP ...
Страница 66: ...VENTILATION AIRFLOW BALANCING BALTIC R410A IOM 0708 E Page 65 ROOF TOP AT15 11S ...
Страница 67: ...VENTILATION AIRFLOW BALANCING BALTIC R410A IOM 0708 E Page 66 ROOF TOP AT15 15S ...
Страница 68: ...VENTILATION AIRFLOW BALANCING BALTIC R410A IOM 0708 E Page 67 AT15 11G2L ROOF TOP EXHAUST ROOF CURB ...
Страница 69: ...VENTILATION AIRFLOW BALANCING BALTIC R410A IOM 0708 E Page 68 AT10 10S EXHAUST ROOF CURB ...
Страница 70: ...VENTILATION AIRFLOW BALANCING BALTIC R410A IOM 0708 E Page 69 EXHAUST ROOF CURB AT10 8G2L ...
Страница 71: ...VENTILATION AIRFLOW BALANCING BALTIC R410A IOM 0708 E Page 70 EXHAUST ROOF CURB AT10 10G2L ...
Страница 85: ...HEATING GAS BURNER BALTIC R410A IOM 0708 E Page 84 MODULE GAZ 20KW B BOX MODULE GAZ 33KW B BOX Fig 67 Fig 68 ...
Страница 86: ...HEATING GAS BURNER BALTIC R410A IOM 0708 E Page 85 MODULE GAZ 20KW C BOX MODULE GAZ 46KW C BOX Fig 69 Fig 70 ...
Страница 87: ...HEATING GAS BURNER BALTIC R410A IOM 0708 E Page 86 MODULE GAZ 33KW D BOX MODULE GAZ 60KW D BOX Fig 71 Fig 72 ...
Страница 88: ...HEATING GAS BURNER BALTIC R410A IOM 0708 E Page 87 MODULE GAZ 60KW E BOX MODULE GAZ 120KW E BOX Fig 73 Fig 74 ...
Страница 93: ...HEATING MODULATING GAS BURNER BALTIC R410A IOM 0708 E Page 92 MODULATING GAZ 120KW E BOX Fig 89 ...
Страница 116: ...PRINCIPLE SKETCHES BALTIC R410A IOM 0708 E Page 115 BAH 035 to 055 dual circuit BAC 035 to 055 dual circuit ...
Страница 126: ...CERTIFICATES BALTIC R410A IOM 0708 E Page 125 ...
Страница 127: ...CERTIFICATES BALTIC R410A IOM 0708 E Page 126 ...
Страница 128: ...CERTIFICATES BALTIC R410A IOM 0708 E Page 127 ...
Страница 129: ...CERTIFICATES BALTIC R410A IOM 0708 E Page 128 ...
Страница 130: ...CERTIFICATES G4 FILTERS BALTIC R410A IOM 0708 E Page 129 ...
Страница 131: ...CERTIFICATES F7 FILTERS BALTIC R410A IOM 0708 E Page 130 ...
Страница 132: ...CERTIFICATES CLIMAVER 202 BALTIC R410A IOM 0708 E Page 131 ...
Страница 133: ...CERTIFICATES CLIMAVER 274 BALTIC R410A IOM 0708 E Page 132 ...
Страница 134: ...CERTIFICATES BALTIC R410A IOM 0708 E Page 133 ...
Страница 135: ...CERTIFICATES BALTIC R410A IOM 0708 E Page 134 ...
Страница 136: ...CERTIFICATES BALTIC R410A IOM 0708 E Page 135 ...