CLIMATIC 50 – ROOFTOP – VERSION 23
BALTIC R410A-IOM-0708-E
Page 94
WIRING CONNECTIONS
Important Warning
Any wiring modification on the CLIMATIC 50 must be done by Lennox technician or employees
having valid electrical qualification and authorisation.
For any modification of wiring on the 24V supply or on 4-20mA sensor, check the polarity prior to apply the power.
Wrong polarity may cause serious damage and destroy the Plan network. Lennox will not accept liability for damage
caused by wrong power connection or any wiring modification done by people without valid training and
qualifications.
Any external connection with the unit, using 24Vac voltage should not exceed a length of more than 30m. It concerns
external contacts connected to
Climatic™50
logical inputs or humidifier control connection to the output 0-10v.
Over 30 m, the installer must interface this information with relays or converters.
In any case, the 24Vac control voltage must not be used to drive external function with Cl
imatic™
50 logical output
WARNING: Separate as much as possible probes, displays, logical input cables from power
cables with strong inductive load, in order to avoid possible electromagnetic perturbations
Connection
Sensors and Probes
External sensors or probes connection must be carried out with the following cable:
Cable length up to 20m: AWG22 (0.34 mm ²), 1 pair crossed with screen (2 pairs for CO2 sensor).
Cable length up to 50m: LiYCY-P (0.34 mm ²), 1 pair with general shield. (2 pairs for CO2 sensor).
The cable length should not exceed 50m.
For a better electromagnetic protection, Lennox recommends the use of LiYCY-P cable
Room Temperature Probe (NTC)
The room temperature probe (- BT10) is connected to
the Climatic™ main board BM50 50
entry B7 connector J6 (refer to
the unit electrical wiring diagram).
Room Humidity Sensor (0-20mA / Option)
The room humidity sensor (- BH10) is connected to the
Climatic™
extension board BE50 entry B1 connector J9 (refer to the
unit electrical wiring diagram).
Room Air Quality Sensor CO² (4-20mA / Option)
The room air quality sensor (-BG10) is co
nnected to Climatic™
main board BM50 entry B2 connector (refer to the unit
electrical wiring diagram).
DS 50 Display
The Display DS50 can be connected
to the Climatic™ either
on one of the RJ12 connectors located on the board DT50, or
directly on the main board BM50 connector J10.
Connection is carried out by the flat 1.5m cable delivered with this DS50.
In any the case, Display DS50 cannot be remotely connected.
In case of Master/Slave installation, one, and only one, display DS50 must be connected on the pLan bus.
Содержание BAC020SNM
Страница 11: ...COMMISSIONING REPORT BALTIC R410A IOM 0708 E Page 10 ...
Страница 65: ...VENTILATION AIRFLOW BALANCING BALTIC R410A IOM 0708 E Page 64 PERFORMANCE CURVES AT12 9S ROOF TOP ...
Страница 66: ...VENTILATION AIRFLOW BALANCING BALTIC R410A IOM 0708 E Page 65 ROOF TOP AT15 11S ...
Страница 67: ...VENTILATION AIRFLOW BALANCING BALTIC R410A IOM 0708 E Page 66 ROOF TOP AT15 15S ...
Страница 68: ...VENTILATION AIRFLOW BALANCING BALTIC R410A IOM 0708 E Page 67 AT15 11G2L ROOF TOP EXHAUST ROOF CURB ...
Страница 69: ...VENTILATION AIRFLOW BALANCING BALTIC R410A IOM 0708 E Page 68 AT10 10S EXHAUST ROOF CURB ...
Страница 70: ...VENTILATION AIRFLOW BALANCING BALTIC R410A IOM 0708 E Page 69 EXHAUST ROOF CURB AT10 8G2L ...
Страница 71: ...VENTILATION AIRFLOW BALANCING BALTIC R410A IOM 0708 E Page 70 EXHAUST ROOF CURB AT10 10G2L ...
Страница 85: ...HEATING GAS BURNER BALTIC R410A IOM 0708 E Page 84 MODULE GAZ 20KW B BOX MODULE GAZ 33KW B BOX Fig 67 Fig 68 ...
Страница 86: ...HEATING GAS BURNER BALTIC R410A IOM 0708 E Page 85 MODULE GAZ 20KW C BOX MODULE GAZ 46KW C BOX Fig 69 Fig 70 ...
Страница 87: ...HEATING GAS BURNER BALTIC R410A IOM 0708 E Page 86 MODULE GAZ 33KW D BOX MODULE GAZ 60KW D BOX Fig 71 Fig 72 ...
Страница 88: ...HEATING GAS BURNER BALTIC R410A IOM 0708 E Page 87 MODULE GAZ 60KW E BOX MODULE GAZ 120KW E BOX Fig 73 Fig 74 ...
Страница 93: ...HEATING MODULATING GAS BURNER BALTIC R410A IOM 0708 E Page 92 MODULATING GAZ 120KW E BOX Fig 89 ...
Страница 116: ...PRINCIPLE SKETCHES BALTIC R410A IOM 0708 E Page 115 BAH 035 to 055 dual circuit BAC 035 to 055 dual circuit ...
Страница 126: ...CERTIFICATES BALTIC R410A IOM 0708 E Page 125 ...
Страница 127: ...CERTIFICATES BALTIC R410A IOM 0708 E Page 126 ...
Страница 128: ...CERTIFICATES BALTIC R410A IOM 0708 E Page 127 ...
Страница 129: ...CERTIFICATES BALTIC R410A IOM 0708 E Page 128 ...
Страница 130: ...CERTIFICATES G4 FILTERS BALTIC R410A IOM 0708 E Page 129 ...
Страница 131: ...CERTIFICATES F7 FILTERS BALTIC R410A IOM 0708 E Page 130 ...
Страница 132: ...CERTIFICATES CLIMAVER 202 BALTIC R410A IOM 0708 E Page 131 ...
Страница 133: ...CERTIFICATES CLIMAVER 274 BALTIC R410A IOM 0708 E Page 132 ...
Страница 134: ...CERTIFICATES BALTIC R410A IOM 0708 E Page 133 ...
Страница 135: ...CERTIFICATES BALTIC R410A IOM 0708 E Page 134 ...
Страница 136: ...CERTIFICATES BALTIC R410A IOM 0708 E Page 135 ...