background image

506694-01

Issue 1720

Page 6 of 16

Positioning Considerations

In order to avoid injury, take proper precaution when 

lifting heavy objects.

 CAUTION

Physical contact with metal edges and corners while 

applying excessive force or rapid motion can result in 

personal injury. Be aware of, and use caution when 

working near these areas during installation or while 

servicing this equipment.

 CAUTION

Consider the following when positioning the unit:

•  Some localities are adopting sound ordinances based 

on the unit’s sound level registered from the adjacent 

property, not from the installation property. Install the 

unit as far as possible from the property line.

•  When possible, do not install the unit directly outside 

a window. Glass has a very high level of sound 

transmission. For proper placement of unit in relation 

to a window, see the provided illustration in Figure 5.

Placing Outdoor Unit on Slab

When installing a unit at grade level, the top of the slab 

should be high enough above the grade so that water 

from higher ground would not collect around the unit as 

illustrated in Figure 5.

Slab may be level or have a slope tolerance away from the 

building of not more than two degrees, or 2 inches per 5 

feet (51 mm per 1524 mm) as illustrated in Figure 5.

Installing Outdoor Unit on Roof

Install the unit at a minimum of 4 inches (102 mm) above 

the surface of the roof. Ensure the weight of the unit is 

properly distributed over roof joists and rafters. Redwood 

or steel supports are recommended.

Replacement Line Set

This section provides information on replacement of 

existing line set. If replacement line set is not required, 

then proceed to Brazing Connections on Page 7.

Refrigerant Line Set

Field refrigerant piping consists of liquid and suction lines 

from the outdoor unit (braze connections) to the indoor unit 

coil (flare or braze connections). If replacing line set, use 

brazed,  non-flare  line  set,  or  field-fabricated  refrigerant 

lines as listed in Table 2.

Existing line set should meet size requirements listed in 

Table 2.

NOTE: 

When installing refrigerant lines longer than 50 

feet, contact technical support for assistance. To obtain 

the correct information from manufacturer, be sure to 

communicate the following points:

•  Model (13ACD) and size of unit (e.g. -060).
•  Line set diameters for the unit being installed as listed 

in Table 2 and total length of installation.

•  Number of elbows and if there is a rise or drop of the 

piping.

Model

Field Connections

Recommended Line Set

Liquid Line

Suction Line

Liquid Line

Suction Line

Line Sets

13ACD-018-230

3/8 in. (10 mm)

3/4 in. (19 mm)

3/8 in. (10 mm)

3/4 in. (19 mm)

Field-fabricated 

brazed, non flare

13ACD-024-230
13ACD-030-230
13ACD-036-230

3/8 in. (10 mm)

7/8 in. (22 mm)

3/8 in. (10 mm)

7/8 in. (22 mm)

13ACD-042-230
13ACD-048-230
13ACD-060-230

3/8 in. (10 mm)

1-1/8 in. (29 mm)

3/8 in. (10 mm)

1-1/8 in. (29 mm)

Table 2. Refrigerant Line Set - inches (mm)

Roof Damage!

This system contains both refrigerant and oil. Some 

rubber roofing material may absorb oil and cause the 

rubber to swell when it comes into contact with oil. The 

rubber will then bubble and could cause leaks. Protect 

the roof surface to avoid exposure to refrigerant and 

oil during service and installation. Failure to follow this 

notice could result in damage to roof surface.

NOTE

Содержание 13ACD-018-230

Страница 1: ...rged with dry nitrogen The unit is intended for installation in existing HCFC 22 systems Carefully follow all installation procedures Open both service valves to evacuate system This unit is construct...

Страница 2: ...ce included with outdoor unit or thermal expansion valve TXV See the 13ACD product specification sheet for approved fixed orifice sizes and expansion valve kit match ups Important The air conditioning...

Страница 3: ...K SEATED OPENED BALL SHOWN CLOSED SERVICE PORT CORE TO INDOOR UNIT TO OUTDOOR UNIT TO OPEN ROTATE STEM COUNTERCLOCKWISE 90 TO CLOSE ROTATE STEM CLOCKWISE 90 SERVICE PORT SERVICE PORT CAP STEM CAP VALV...

Страница 4: ...rnal pressure relief valve Compressor has internal vacuum protection that is designed to unload the scrolls compressor stops pumping when the pressure ratio meets a certain value or when the suction p...

Страница 5: ...ANEL MINIMUM CLEARANCE ABOVE UNIT NOTES Clearance to one of the other three sides must be 36 inches 914mm Clearance to one of the remaining two sides may be 12 inches 305mm and the final side may be 6...

Страница 6: ...ides information on replacement of existing line set If replacement line set is not required then proceed to Brazing Connections on Page 7 Refrigerant Line Set Field refrigerant piping consists of liq...

Страница 7: ...ay result in ignition of the refrigerant and oil mixture Check the high and low pressures before applying heat WARNING Allow braze joint to cool before removing the wet rag from the service valve Temp...

Страница 8: ...OM SERVICE VALVE Flow regulated nitrogen at 1 to 2 psig through the low side refrigeration gauge set into the liquid line service port valve and out of the suction vapor line service port valve CUT AN...

Страница 9: ...RVICE VALVE PREPARATION FOR NEXT STEP 7 WARNING 1 FIRE PERSONAL INJURY OR PROPERTY DAMAGE will result if you do not wrap a wet cloth around both liquid and suction line service valve bodies and copper...

Страница 10: ...H Use a field provided fitting to temporary reconnect the liquid line to the indoor unit s liquid line orifice housing LOW HIGH EXISTING INDOOR UNIT GAUGE MANIFOLD INVERTED CYLINDER CONTAINS CLEAN LI...

Страница 11: ...d end of the expansion valve and lightly lubricate the connector threads and expose surface of the Teflon ring with refrigerant oil C Attach the stubbed end of the expansion valve to the liquid line o...

Страница 12: ...unit A trace amountis a maximum of two ounces 57 g refrigerant or three pounds 31 kPa pressure Close the valve on the HCFC 22 cylinder and the valve on the high pressure side of the manifold gauge set...

Страница 13: ...nnect the manifold gauge to the vacuum pump turn the pump on and continue to evacuate the line set and indoor unit until the absolute pressure does not rise above 500 microns 29 9 inches of mercury wi...

Страница 14: ...HERMOSTAT 5 FEET 1 5M CHECK EXISTING ROOM THERMOSTAT Any excess high voltage field wiring should be trimmed and secured away from any low voltage field wiring To facilitate a conduit a cutout is locat...

Страница 15: ...system using evacuating procedure provided in this instruction 3 Use nitrogen to break the vacuum and install a new filter drier in the system 4 Evacuate the system again using evacuating procedure p...

Страница 16: ...per tension 5 Check all wiring for loose connections 6 Check for correct voltage at unit blower operating 7 Check amp draw on blower motor Motor Nameplate _________ Actual __________ Indoor Coil 1 Cle...

Отзывы: