background image

506694-01

Issue 1720

Page 15 of 16

Electric Shock Hazard

. Can cause injury or death. Unit must be grounded in accordance with national and 

local codes.
Line voltage is present at all components when unit is not in operation on units with single-pole contactors. 

Disconnect all remote electric power supplies before opening access panel. Unit may have multiple power 

supplies.

 WARNING

Figure 11. Typical Unit Wiring Diagram

If unit is equipped with a crankcase heater, it should 

be energized 24 hours before unit start-up to prevent 

compressor damage as a result of slugging.

 IMPORTANT

Servicing Outdoor Unit Delivered Void of 

Nitrogen Charge

If the outdoor unit is void of factory nitrogen charge, clean 

the system using the procedure described below.

1.  Use nitrogen to repressurize system and check for 

leaks.

2.  Evacuate the system using evacuating procedure 

provided in this instruction.

3.  Use nitrogen to break the vacuum and install a new 

filter drier in the system.

4.  Evacuate the system again using evacuating 

procedure provided in this instruction.

5.  Monitor the system to determine the amount of 

moisture remaining in the oil. It may be necessary 

to  replace  the  filter  drier  several  times  to  achieve 

the required dryness level. If system dryness is not 

verified, the compressor will fail in the future.

Maintenance

Maintenance and service must be performed by a qualified 

installer or service agency. At the beginning of each cooling 

season, the system should be checked as follows:

Outdoor Unit

1.  Outdoor unit fan motor is pre-lubricated and sealed. 

No further lubrication is needed.

2.  Visually inspect all connecting lines, joints and coils for 

evidence of oil leaks.

3.  Check all wiring for loose connections.
4.  Check for correct voltage at unit (unit operating).
5.  Check amp draw on outdoor fan motor.

Motor Nameplate:_________ Actual:__________.

Содержание 13ACD-018-230

Страница 1: ...rged with dry nitrogen The unit is intended for installation in existing HCFC 22 systems Carefully follow all installation procedures Open both service valves to evacuate system This unit is construct...

Страница 2: ...ce included with outdoor unit or thermal expansion valve TXV See the 13ACD product specification sheet for approved fixed orifice sizes and expansion valve kit match ups Important The air conditioning...

Страница 3: ...K SEATED OPENED BALL SHOWN CLOSED SERVICE PORT CORE TO INDOOR UNIT TO OUTDOOR UNIT TO OPEN ROTATE STEM COUNTERCLOCKWISE 90 TO CLOSE ROTATE STEM CLOCKWISE 90 SERVICE PORT SERVICE PORT CAP STEM CAP VALV...

Страница 4: ...rnal pressure relief valve Compressor has internal vacuum protection that is designed to unload the scrolls compressor stops pumping when the pressure ratio meets a certain value or when the suction p...

Страница 5: ...ANEL MINIMUM CLEARANCE ABOVE UNIT NOTES Clearance to one of the other three sides must be 36 inches 914mm Clearance to one of the remaining two sides may be 12 inches 305mm and the final side may be 6...

Страница 6: ...ides information on replacement of existing line set If replacement line set is not required then proceed to Brazing Connections on Page 7 Refrigerant Line Set Field refrigerant piping consists of liq...

Страница 7: ...ay result in ignition of the refrigerant and oil mixture Check the high and low pressures before applying heat WARNING Allow braze joint to cool before removing the wet rag from the service valve Temp...

Страница 8: ...OM SERVICE VALVE Flow regulated nitrogen at 1 to 2 psig through the low side refrigeration gauge set into the liquid line service port valve and out of the suction vapor line service port valve CUT AN...

Страница 9: ...RVICE VALVE PREPARATION FOR NEXT STEP 7 WARNING 1 FIRE PERSONAL INJURY OR PROPERTY DAMAGE will result if you do not wrap a wet cloth around both liquid and suction line service valve bodies and copper...

Страница 10: ...H Use a field provided fitting to temporary reconnect the liquid line to the indoor unit s liquid line orifice housing LOW HIGH EXISTING INDOOR UNIT GAUGE MANIFOLD INVERTED CYLINDER CONTAINS CLEAN LI...

Страница 11: ...d end of the expansion valve and lightly lubricate the connector threads and expose surface of the Teflon ring with refrigerant oil C Attach the stubbed end of the expansion valve to the liquid line o...

Страница 12: ...unit A trace amountis a maximum of two ounces 57 g refrigerant or three pounds 31 kPa pressure Close the valve on the HCFC 22 cylinder and the valve on the high pressure side of the manifold gauge set...

Страница 13: ...nnect the manifold gauge to the vacuum pump turn the pump on and continue to evacuate the line set and indoor unit until the absolute pressure does not rise above 500 microns 29 9 inches of mercury wi...

Страница 14: ...HERMOSTAT 5 FEET 1 5M CHECK EXISTING ROOM THERMOSTAT Any excess high voltage field wiring should be trimmed and secured away from any low voltage field wiring To facilitate a conduit a cutout is locat...

Страница 15: ...system using evacuating procedure provided in this instruction 3 Use nitrogen to break the vacuum and install a new filter drier in the system 4 Evacuate the system again using evacuating procedure p...

Страница 16: ...per tension 5 Check all wiring for loose connections 6 Check for correct voltage at unit blower operating 7 Check amp draw on blower motor Motor Nameplate _________ Actual __________ Indoor Coil 1 Cle...

Отзывы: