background image

506694-01

Issue 1720

Page 12 of 16

Capacity

Catalog 

Number

Part 

Number

Drill Size

018

10W95

100484-07

0.055

024

98M12

100484-12

0.062

030

11W00

100484-16

0.067

036

98M78

100484-24

0.076

042

10W86

100484-28

0.080

048

98M14

100484-36

0.089

060

98M15

100484-45

0.099

Table 3. 

Indoor Fixed Orifice Kits

Leak Test Line Set and Indoor Coil

After completing the leak testing of the line set and indoor 

coil as outlined in Figure 9, proceed to Evacuating Line Set 

and Indoor Coil on Page 13.

The Environmental Protection Agency (EPA) prohibits 

the intentional venting of HCFC refrigerants during 

maintenance, service, repair and disposal of appliance. 

Approved methods of recovery, recycling or reclaiming 

must be followed.

 IMPORTANT

Refrigerant can be harmful if it is inhaled. Refrigerant 

must be used and recovered responsibly.
Failure to follow this warning may result in personal 

injury or death.

 WARNING

Leak detector must be capable of sensing HCFC-22 refrigerant.

 IMPORTANT

TO VAPOR

SERVICE VALVE

HCFC-22

MANIFOLD GAUGE SET

OUTDOOR UNIT

HIGH

LOW

NITROGEN

A

With both manifold valves closed, connect the cylinder of HCFC-22 refrigerant to the center port of the manifold gauge set. Open the

valve on the HCFC-22 cylinder (vapor only).

B

Open the high pressure side of the manifold to weigh in a trace amount of HCFC-22 into the line set and indoor unit.  A trace amount is a

maximum of two ounces (57 g) refrigerant or three pounds (31 kPa) pressure.

 

Close the valve on the HCFC-22 cylinder and the valve

on the high pressure side of the manifold gauge set. Disconnect the HCFC-22 cylinder.

C

Connect a cylinder of dry nitrogen with a pressure regulating valve to the center port of the manifold gauge set.

D

Adjust dry nitrogen pressure to 150 psig (1034 kPa). Open the valve on the high side of the manifold gauge set in order to pressurize the line

set and the indoor unit.

E

After a few minutes, open one of the service valve ports and verify that the refrigerant added to the system earlier is measurable with a

leak detector

F

After leak testing, disconnect gauges from service ports.

After the line set has been connected to the indoor and outdoor units, check the line set connections and indoor unit for leaks. Use

the following procedure to test for leaks:

A

Connect an HCFC-22 manifold gauge set high pressure hose

to the vapor valve service port.

NOTE 

— Normally, the high pressure hose is connected to

the liquid line port. However, connecting it to the vapor port

better protects the manifold gauge set from high pressure

damage.

B

With both manifold valves closed, connect the cylinder of

HCFC-22 refrigerant to the center port of the manifold gauge

set.

NOTE 

— Later in the procedure,

the HCFC-22  container  will  be

replaced  by  the  nitrogen

container.

IMPORTANT 

— 

Leak detector

must  be  capable  of sensing

HCFC-22 refrigerant.

1

CONNECT GAUGE SET

2

TEST FOR LEAKS

A

B

DIGITAL SCALE

Figure 9. Leak Test

Содержание 13ACD-018-230

Страница 1: ...rged with dry nitrogen The unit is intended for installation in existing HCFC 22 systems Carefully follow all installation procedures Open both service valves to evacuate system This unit is construct...

Страница 2: ...ce included with outdoor unit or thermal expansion valve TXV See the 13ACD product specification sheet for approved fixed orifice sizes and expansion valve kit match ups Important The air conditioning...

Страница 3: ...K SEATED OPENED BALL SHOWN CLOSED SERVICE PORT CORE TO INDOOR UNIT TO OUTDOOR UNIT TO OPEN ROTATE STEM COUNTERCLOCKWISE 90 TO CLOSE ROTATE STEM CLOCKWISE 90 SERVICE PORT SERVICE PORT CAP STEM CAP VALV...

Страница 4: ...rnal pressure relief valve Compressor has internal vacuum protection that is designed to unload the scrolls compressor stops pumping when the pressure ratio meets a certain value or when the suction p...

Страница 5: ...ANEL MINIMUM CLEARANCE ABOVE UNIT NOTES Clearance to one of the other three sides must be 36 inches 914mm Clearance to one of the remaining two sides may be 12 inches 305mm and the final side may be 6...

Страница 6: ...ides information on replacement of existing line set If replacement line set is not required then proceed to Brazing Connections on Page 7 Refrigerant Line Set Field refrigerant piping consists of liq...

Страница 7: ...ay result in ignition of the refrigerant and oil mixture Check the high and low pressures before applying heat WARNING Allow braze joint to cool before removing the wet rag from the service valve Temp...

Страница 8: ...OM SERVICE VALVE Flow regulated nitrogen at 1 to 2 psig through the low side refrigeration gauge set into the liquid line service port valve and out of the suction vapor line service port valve CUT AN...

Страница 9: ...RVICE VALVE PREPARATION FOR NEXT STEP 7 WARNING 1 FIRE PERSONAL INJURY OR PROPERTY DAMAGE will result if you do not wrap a wet cloth around both liquid and suction line service valve bodies and copper...

Страница 10: ...H Use a field provided fitting to temporary reconnect the liquid line to the indoor unit s liquid line orifice housing LOW HIGH EXISTING INDOOR UNIT GAUGE MANIFOLD INVERTED CYLINDER CONTAINS CLEAN LI...

Страница 11: ...d end of the expansion valve and lightly lubricate the connector threads and expose surface of the Teflon ring with refrigerant oil C Attach the stubbed end of the expansion valve to the liquid line o...

Страница 12: ...unit A trace amountis a maximum of two ounces 57 g refrigerant or three pounds 31 kPa pressure Close the valve on the HCFC 22 cylinder and the valve on the high pressure side of the manifold gauge set...

Страница 13: ...nnect the manifold gauge to the vacuum pump turn the pump on and continue to evacuate the line set and indoor unit until the absolute pressure does not rise above 500 microns 29 9 inches of mercury wi...

Страница 14: ...HERMOSTAT 5 FEET 1 5M CHECK EXISTING ROOM THERMOSTAT Any excess high voltage field wiring should be trimmed and secured away from any low voltage field wiring To facilitate a conduit a cutout is locat...

Страница 15: ...system using evacuating procedure provided in this instruction 3 Use nitrogen to break the vacuum and install a new filter drier in the system 4 Evacuate the system again using evacuating procedure p...

Страница 16: ...per tension 5 Check all wiring for loose connections 6 Check for correct voltage at unit blower operating 7 Check amp draw on blower motor Motor Nameplate _________ Actual __________ Indoor Coil 1 Cle...

Отзывы: