background image

506694-01

Issue 1720

Page 10 of 16

Removing Existing Metering Device and Flushing Line Set and Indoor Coil

Flushing is only recommended if existing indoor coil and line set are to be used. Otherwise, proceed to Installing Indoor 

Metering Device on Page 11.

SENSING

LINE

TEFLON

®

 RING

FIXED ORIFICE

BRASS NUT

LIQUID LINE ASSEMBLY

(INCLUDES STRAINER)

LIQUID LINE ORIFICE HOUSING

DISTRIBUTOR TUBES

DISTRIBUTOR

ASSEMBLY

A

On fully cased coils, remove the coil access and plumbing panels.

B

Remove any shipping clamps holding the liquid line and distributor

assembly.

C

Using two wrenches, disconnect liquid line from liquid line orifice

housing. Take care not to twist or damage distributor tubes during

this process.

D

Remove and discard fixed orifice, valve stem assembly if present

and Teflon

®

 washer as illustrated above.

E

Use a field-provided fitting to temporarily reconnect the liquid line to

the indoor unit's liquid line orifice housing.

TYPICAL EXISTING FIXED ORIFICE

REMOVAL PROCEDURE

(UNCASED COIL SHOWN)

TYPICAL EXISTING EXPANSION VALVE

REMOVAL PROCEDURE (UNCASED COIL

SHOWN)

TWO PIECE PATCH PLATE

(UNCASED COIL ONLY)

VAPOR

LINE

DISTRIBUTOR

ASSEMBLY

DISTRIBUTOR

TUBES

LIQUID

LINE

MALE EQUALIZER

LINE FITTING

EQUALIZER

LINE

EXPANSION

VALVE

TEFLON

®

RING

STUB END

TEFLON

®

RING

SENSING BULB

LIQUID LINE

ORIFICE

HOUSING

LIQUID LINE

ASSEMBLY WITH

BRASS NUT

A

On fully cased coils, remove the coil access and plumbing panels.

B

Remove any shipping clamps holding the liquid line and distributor

assembly.

C

Disconnect the equalizer line from the expansion valve equalizer line

fitting on the vapor line.

D

Remove the vapor line sensing bulb.

E

Disconnect the liquid line from the expansion valve at the liquid line

assembly.

F

Disconnect the expansion valve from the liquid line orifice housing.

Take care not to twist or damage distributor tubes during this process.

G

Remove and discard expansion valve and the two Teflon

®

 rings.

H

Use a field-provided fitting to temporary reconnect the liquid line to the

indoor unit's liquid line orifice housing.

LOW

HIGH

EXISTING

INDOOR

UNIT

GAUGE

MANIFOLD

INVERTED CYLINDER

CONTAINS CLEAN

LIQUID HCFC-22* TO BE

USED FOR FLUSHING.

LIQUID LINE SERVICE

VALVE

INLET

DISCHARGE

TANK

RETURN

CLOSED

OPENED

RECOVERY

CYLINDER

RECOVERY MACHINE

NEW

OUTDOOR

UNIT

VAPOR LINE

SERVICE VALVE

VAPO
R

LIQUID

1

A

Inverted HCFC-22 cylinder with clean refrigerant* to the vapor service

valve.

B

HCFC-22 gauge set (low side) to the liquid line valve.

C

HCFC-22 gauge set center port to inlet on the recovery machine with an

empty recovery tank to the gauge set.

D

Connect recovery tank to recovery machine per machine instructions.

CONNECT GAUGES AND EQUIPMENT FOR

FLUSHING PROCEDURE

A

B

C

D

B

OR

FLUSHING LINE SET

A

Set  the  recovery  machine  for  liquid  recovery  and  start  the

recovery machine.  Open  the  gauge  set  valves  to  allow  the

recovery machine to pull a vacuum on the existing system line

set and indoor unit coil.

B

Invert the cylinder of clean refrigerant* and open its valve to allow

liquid refrigerant to flow into the system through the vapor line

valve. Allow the refrigerant to pass from the cylinder and through

the line set and the indoor unit coil before it enters the recovery

machine.

C

After all of the liquid refrigerant has been recovered, switch the

recovery machine to vapor recovery so that all of the HCFC-22

vapor is  recovered.  Allow  the  recovery  machine  to  pull  the

system down to zero.

D

Close the valve on the inverted HCFC-22 drum and the gauge

set valves. Pump the remaining refrigerant out of the recovery

machine and turn the machine off.

The line set and indoor unit coil must be flushed with at least the

same amount of clean refrigerant* that previously charged the

system. Check the charge in the flushing cylinder before

proceeding.

1A

2

3

1B

*IMPORTANT - Clean refrigerant is any refrigerant in a system that has not had compressor burn out. If the system

has experienced burn out, it is recommended that the existing line set and indoor coil be replaced.

Figure 7. Removing Metering Device and Flushing

Содержание 13ACD-018-230

Страница 1: ...rged with dry nitrogen The unit is intended for installation in existing HCFC 22 systems Carefully follow all installation procedures Open both service valves to evacuate system This unit is construct...

Страница 2: ...ce included with outdoor unit or thermal expansion valve TXV See the 13ACD product specification sheet for approved fixed orifice sizes and expansion valve kit match ups Important The air conditioning...

Страница 3: ...K SEATED OPENED BALL SHOWN CLOSED SERVICE PORT CORE TO INDOOR UNIT TO OUTDOOR UNIT TO OPEN ROTATE STEM COUNTERCLOCKWISE 90 TO CLOSE ROTATE STEM CLOCKWISE 90 SERVICE PORT SERVICE PORT CAP STEM CAP VALV...

Страница 4: ...rnal pressure relief valve Compressor has internal vacuum protection that is designed to unload the scrolls compressor stops pumping when the pressure ratio meets a certain value or when the suction p...

Страница 5: ...ANEL MINIMUM CLEARANCE ABOVE UNIT NOTES Clearance to one of the other three sides must be 36 inches 914mm Clearance to one of the remaining two sides may be 12 inches 305mm and the final side may be 6...

Страница 6: ...ides information on replacement of existing line set If replacement line set is not required then proceed to Brazing Connections on Page 7 Refrigerant Line Set Field refrigerant piping consists of liq...

Страница 7: ...ay result in ignition of the refrigerant and oil mixture Check the high and low pressures before applying heat WARNING Allow braze joint to cool before removing the wet rag from the service valve Temp...

Страница 8: ...OM SERVICE VALVE Flow regulated nitrogen at 1 to 2 psig through the low side refrigeration gauge set into the liquid line service port valve and out of the suction vapor line service port valve CUT AN...

Страница 9: ...RVICE VALVE PREPARATION FOR NEXT STEP 7 WARNING 1 FIRE PERSONAL INJURY OR PROPERTY DAMAGE will result if you do not wrap a wet cloth around both liquid and suction line service valve bodies and copper...

Страница 10: ...H Use a field provided fitting to temporary reconnect the liquid line to the indoor unit s liquid line orifice housing LOW HIGH EXISTING INDOOR UNIT GAUGE MANIFOLD INVERTED CYLINDER CONTAINS CLEAN LI...

Страница 11: ...d end of the expansion valve and lightly lubricate the connector threads and expose surface of the Teflon ring with refrigerant oil C Attach the stubbed end of the expansion valve to the liquid line o...

Страница 12: ...unit A trace amountis a maximum of two ounces 57 g refrigerant or three pounds 31 kPa pressure Close the valve on the HCFC 22 cylinder and the valve on the high pressure side of the manifold gauge set...

Страница 13: ...nnect the manifold gauge to the vacuum pump turn the pump on and continue to evacuate the line set and indoor unit until the absolute pressure does not rise above 500 microns 29 9 inches of mercury wi...

Страница 14: ...HERMOSTAT 5 FEET 1 5M CHECK EXISTING ROOM THERMOSTAT Any excess high voltage field wiring should be trimmed and secured away from any low voltage field wiring To facilitate a conduit a cutout is locat...

Страница 15: ...system using evacuating procedure provided in this instruction 3 Use nitrogen to break the vacuum and install a new filter drier in the system 4 Evacuate the system again using evacuating procedure p...

Страница 16: ...per tension 5 Check all wiring for loose connections 6 Check for correct voltage at unit blower operating 7 Check amp draw on blower motor Motor Nameplate _________ Actual __________ Indoor Coil 1 Cle...

Отзывы: