34
Audible Alarm
Monitored Welding
If the Audible Alarm is switched on, an acoustic alarm
sounds when the limit value is exceeded.
To activate the Audible alarm, select the
Audible Alarm
menu item in the menu by pressing the
Minus (32)
button and then press the
Confirm (33) button.
If Stop Device on Alert is not enabled, you can set the
alarm limit deviations individually.
If Monitored Welding is switched on, limit values of the
recorded welding parameters are logged.
Select the Monitored Welding menu item in the menu
by pressing the
Minus (32)
button.
Then press the
Confirm (33)
button.
Stop Device on Alert
Individually set limit deviation setting for Speed, Heat, and Air when Stop Device on Alert is disabled.
Select the limit value to be set by pressing the
Minus (32)
button and then press the
Confirm (33)
button. Use the
Minus/Plus (32)
button to set the limit value.
If Stop Device on Alert is switched on, the heating and drive are switched off if the limit value is exceeded. The
limit values are specified.
The maximum permissible temperature deviation of the hot-air blower is 10°C; the permissible deviation of the
drive speed is 4% and the fan speed is 4%.
If the limit value is exceeded, the machine stops automatically after 30 seconds. The Stop Device on Alert symbol
is displayed in the status display (40).
Содержание UNIROOF 300
Страница 28: ...28 Switching off Target and Actual Value Display see 10 4 Switching on ECO Mode see 10 5...
Страница 29: ...29 Switching off Data Recording see 10 6 Switching on Advanced Mode see 10 7...
Страница 37: ...37 10 7 Advanced mode settings Example Activate WLAN Press 4 times...
Страница 38: ...38 Switch on Info Mode Example Setting the time...
Страница 39: ...39 General information Reset distance counter...