Archimod®
Oper
ating and main
tenanc
e manual
59
7.2.3 Power Modules
PM status
PM X Info
Mod
Model of power module X
SW Vers.
Firmware version inside the power module X
HW Vers.
Hardware version of the power module X
S/N
Serial number of the power module X
Max VA
Maximum apparent power suppliable by the power module X [VA]
Max W
Maximum active power suppliable by the power module X [W]
Max Icgh
Maximum current suppliable by the battery charger of the power module X [A]
PM
Measure-
ments
Input X
Power
Active power absorbed by the mains by the power module X [W]
Appar. Power Apparent power absorbed by the mains by the power module
X [VA]
Vrms.
Effective voltage in input to power module X [V RMS]
Bypass Vrms Effective voltage in input to the power module X
for the bypass line [V RMS]
Linked Vrms Input line voltage to the power module X [V RMS]
I rms
Effective current absorbed by the power module X by the
mains [A RMS]
Peak I Value Peak current absorbed by the power module X
by the mains [A]
Frequency
Frequency of the sinusoid voltage in input to the power
module X [Hz] for the bypass line
Crest I Factor Crest factor applied by the power module X to the mains
Power factor Power factor applied by the power module X to the mains
Output X
Power
Active power supplied by the power module X [W]
Appar. Power Apparent power supplied in output by the power module X [VA]
V rms
Effective voltage supplied in output by the power module X [V RMS]
Linked Vrms Line voltage in output by the power module X [V RMS]
I rms
Effective current supplied in output by the power module X [A RMS]
Peak I Value Peak current supplied in output by the power module X [A]
Frequency
Frequency of the sinusoid voltage in output from the power
module X [Hz]
Crest Factor Crest factor of the current in output from the power module X
Power factor Power factor in output from the power module X
Max W
Maximum active power suppliable by the power module X [W]
Power
Active power supplied by the power module X,
expressed as a percentage in relation to the maximum active
power the power module X can supply [%]
Max VA
Maximum apparent power suppliable
by the power module X [W]
App. Power
Apparent power supplied by the power module X,
expressed as a percentage in relation to the maximum
apparent power the power module X can supply [%]
(continue)
Содержание Archimod
Страница 1: ...Archimod Operating and Maintenance Manual Part LE05755AA 09 12 01 GF ...
Страница 2: ...Archimod 2 EN ENGLISH 3 ...
Страница 13: ...Archimod Operating and maintenance manual 13 3 3 Models UPS Archimod 20 18U UPS Archimod 20 UPS Archimod 40 ...
Страница 14: ...14 3 Technical description UPS Archimod 60 UPS Archimod 80 UPS Archimod 100 ...
Страница 15: ...Archimod Operating and maintenance manual 15 UPS Archimod 120 UPS Archimod Battery ...
Страница 81: ...81 Archimod ...
Страница 82: ...82 ...
Страница 83: ......