WARNING
The instructions in this chapter are not addressed to a normal operator but to a specialized technician, authorised
to work only if he uses the Individual Protective Gear mentioned in Chapter 4.
6.1
Safety rules and regulations
Before starting installation please read and apply the following:
1. Attention: equipment with a high sneak current, it is indispensable to earth it before connecting the power supply. It
is necessary to ensure that the distribution panel, to which the UPS is to be connected, has a secure connection to the
earth circuit and adequate protection as required by law.
2. Only the fixed type of the UPS Archimod® units must be installed with a thermal circuit breaker upstream. Connection
of the unit to the mains using a traditional plug is not allowed.
3. The mains supply panel or disconnecting device, must be installed near the equipment and easy to access.
4. A warning label must be affixed on all mains supply isolating switches installed far away from the UPS area to
remind assistance personnel that the circuit is connected to a UPS. The label must give the following message (or the
equivalent):
ISOLATE THE UPS UNIT BEFORE WORKING ON THIS CIRCUIT!
6.2
Electrical connections
The electrical connection of the UPS to the switchboard is part of the installation and usually is not done by the UPS
manufacturer; therefore the following indications are purely an example and the actual electrical connections must be
done in accordance with local standards.
Once the UPS has been removed from the packaging and positioned in its final place of installation, the authorised
technician can start its installation.
ATTENTION
The type and cross section of the connecting cables must be chosen according to their operating current and laying
must be as established by existing laws; this is the responsibility of the installer. The UPS input current and output
power are given in paragraph 3.4 and the battery current in Table 7.
INDICATION
In the TABLES chapter, tables 1 to 6 give indications about sizing of cables, fuses, circuit breakers and RCDs as well as an example
of cable sizing if unipolar cables are used without a sheath, in PVC and laid in a pipe above ground.
6.2.1 Safety recommendations
WARNING
Before starting please read and apply the following with attention. It is strictly forbidden to proceed with installation
if one or more of the following conditions have not been checked.
• Do not proceed with installation if there is water or moisture.
• Remember that opening or removing the panels from the UPS you risk exposure to high and dangerous voltages.
• Check there is no mains voltage on the equipment.
• Check that the loads are off and disconnected from the UPS;
• Check that the UPS is off and not live.
• Check that the battery disconnector switches on the UPS and on all the external Archimod® BATTERY cabinets are open
and remove at least 1 battery box from each battery shelf in the UPS.
• Each slot not used by power modules must be covered with a plastic mask (supplied) and secured only and exclusively
with two M4x20mm Allen screws with a 4 mm diameter Grower washer in between, without tightening too much.
• Electrical connection has to be carried out by means of the terminals of the front disconnectors and of the battery
disconnector fuse holder/bars of the UPS.
6. Installation
Содержание Archimod
Страница 1: ...Archimod Operating and Maintenance Manual Part LE05755AA 09 12 01 GF ...
Страница 2: ...Archimod 2 EN ENGLISH 3 ...
Страница 13: ...Archimod Operating and maintenance manual 13 3 3 Models UPS Archimod 20 18U UPS Archimod 20 UPS Archimod 40 ...
Страница 14: ...14 3 Technical description UPS Archimod 60 UPS Archimod 80 UPS Archimod 100 ...
Страница 15: ...Archimod Operating and maintenance manual 15 UPS Archimod 120 UPS Archimod Battery ...
Страница 81: ...81 Archimod ...
Страница 82: ...82 ...
Страница 83: ......