38
®
6. Installation
Output connection
Before connecting the output make certain the UPS is off and there is no voltage on the output disconnector terminals.
- Connect the output line earth cable to the terminal on the base of the equipment.
- Connect the output line Neutral cable to its terminal on the output disconnector using a suitable cable terminal.
- Insert a copper plate between terminals L1out, L2out and L3out of the output disconnector.
- Connect the output line cable L1 to its terminal L1out on the output disconnector using a suitable cable terminal.
- Plug the EC15 connector into the backplane of each UPS tunnel as shown in the figure.
ATTENTION
The plate must be mounted in contact on the disconnector switch terminals with the cable terminals on top – and
not vice versa.
In the single-phase output configuration the UPS could be seriously damaged if the EC15 connector is not plugged
in to each UPS backplane.
When connecting the output line take great care not to reverse the UPS cables that are already on the terminals of
the disconnector switch.
Archimod® 20kVA-40kVA Three-phase/Single-phase UPS (without separate bypass line)
Nin
Nout
L1in
L2in
L3in
L1out
L1byp
Nin
Nout
L1in
L2in
L3in
L1out
Nbyp
brown
brown
black
grey
blue
brown
black
grey
blue
blue
blue
blue
blue
Содержание Archimod
Страница 1: ...Archimod Operating and Maintenance Manual Part LE05755AA 09 12 01 GF ...
Страница 2: ...Archimod 2 EN ENGLISH 3 ...
Страница 13: ...Archimod Operating and maintenance manual 13 3 3 Models UPS Archimod 20 18U UPS Archimod 20 UPS Archimod 40 ...
Страница 14: ...14 3 Technical description UPS Archimod 60 UPS Archimod 80 UPS Archimod 100 ...
Страница 15: ...Archimod Operating and maintenance manual 15 UPS Archimod 120 UPS Archimod Battery ...
Страница 81: ...81 Archimod ...
Страница 82: ...82 ...
Страница 83: ......