18/29
Technical data sheet: S000074637EN-5
Updated: 12/03/2015
Created: 15/04/2014
Technical data sheet
Catalogue number(s): 0 484 22
KNX multiapplication controller 16 outputs
KNX multiapp
8. COmmUNiCa
8. COmmUNiCaTiON OBJECTS (CONTiNUED)
Parameters
Setting
Xn - Short push reaction
No reaction
Up + stop
Down + stop
Stop
Open slats
Close slats
Here an adjustment is made to define which movement command is
written into the storage cell of the communication object and sent
after short pressing of the push button attached to the input.
“No reaction”: action does not change the object value and also does
not send a telegram.
Up + stop: each short push transfers the following sequence command
values into the communication object: Up, Stop, Up, Stop, etc.
Down + stop: each short push transfers the following sequence com-
mand values into the communication object: Down, Stop, Down, Stop,
etc.
Stop: a short push transfers into the communication object the stop
command value (“1” or “0”).
Open slats: a short push transfers into the communication object the
stop (open slats) command value (“0”).
Close slats: a short push transfers into the communication object the
stop (close slats) command value (“1”).
Xn - Long push reaction
No reaction
Up
Down
Stop
Open slats
Close slats
Here an adjustment is made to define which movement command is
written into the storage cell of the communication object and sent
after long pressing of the push button attached to the input.
“No reaction”: action does not change the object value and also does
not send a telegram.
Up: a long push action transfers into the communication object the Up
command (value “0”)
Down: a long push action send the Down command (value “1”)
Stop: a long push action sends the stop command (value “1” or “0”)
Open slats: a long push action transfers into the communication object
the stop (open slats) command (value “0”)
Close slats: a long push action transfers into the communication object
the stop (close slats) command (value “1”)
Xn - Long push release
No reaction
Stop
Here an adjustment is made to define which value is written into the
storage cell of the communication object and sent when releasing the
push button after a long press.
“No reaction”: action does not change the object value and also does
not send a telegram.
Stop: the stop command (value “1” or “0”) is transferred into the com-
munication object and sent.
Xn - Long push action min.
0.5 second
1 second
2 seconds
3 seconds
4 seconds
5 seconds
10 seconds
This parameter determines the minimum period for detecting a long
push.
Parameters
Setting
Xn+1 - Short push reaction
No reaction
Up + stop
Down + stop
Stop
Open slats
Close slats
Here an adjustment is made to define which movement command is
written into the storage cell of the communication object and sent
after short pressing of the push button attached to the input.
“No reaction”: action does not change the object value and also does
not send a telegram.
Up + stop: each short push transfers the following sequence command
values into the communication object: Up, Stop, Up, Stop, etc.
Down + stop: each short push transfers the following sequence com-
mand values into the communication object.
Stop: a short push transfers into the communication object the stop
command value (“1” or “0”).
Open slats: a short push transfers into the communication object the
stop (open slats) command value (“0”).
Close slats: a short push transfers into the communication object the
stop (close slats) command value (“1”).
Xn+1 - Long push reaction
No reaction
Up
Down
Stop
Open slats
Close slats
Here an adjustment is made to define which movement command is
written into the storage cell of the communication object and sent
after long pressing of the push button attached to the input.
“No reaction”: action does not change the object value and also does
not send a telegram.
Up: a long push action transfers into the communication object the Up
command (value “0”)
Down: a long push action sends the Down command (value “1”)
Stop: a long push action sends the stop command (value “1” or “0”)
Open slats: a long push action transfers into the communication object
the stop (open slats) command (value “0”)
Close slats: a long push action transfers into the communication object
the stop (close slats) command (value “1”)
Xn+1 - Long push release
No reaction / Stop
Here an adjustment is made to define which value is written into the
storage cell of the communication object and sent when releasing the
push button after a long press.
“No reaction”: action does not change the object value and also does
not send a telegram.
Stop: the stop command (value “1” or “0”) is transferred into the com-
munication object and sent.
Parameters
Xn+1 - Long push ac
This parameter deter
push.
Contact type
The contact type of
“Normally open con
closed, inactive whe
“Normally closed con
opened, inactive wh
add enable object
The parameter deter
Enable object or not
changes at this input
8.2 Outputs
8.2.1 relays
function On/Off
No.
Object n
114
(118, 122,
126, 130,
134, 138,
142, 146,
150, 154,
158, 162,
166, 170,
174)
Output Xn
This object is used t
red to the relay channel
Switching telegrams
object.
115
(119, 123,
127, 131,
135, 139,
143, 147,
151, 155,
159,163,
167, 171,
175)
Output Xn,
The current switchin
is automatically sent
116
(120, 124,
128, 132,
136, 140,
144, 148,
152, 156,
160, 164,
168, 172,
176)
Output Xn
Enable telegrams are
object. They are used
ding input.
S000074637EN-5.indd 18
20/05/15 10:16