Technical data sheet: S000074637EN-5
Updated: 12/03/2015
Created: 15/04/2014
mber(s): 0 484 22
Catalogue number(s): 0 484 22
KNX multiapplication controller 16 outputs
8. COmmUNiCaTiON OBJECTS (CONTiNUED)
tion
p
stop
ts
ts
ment command is
object and sent
the input.
alue and also does
sequence command
, Stop, etc.
wing sequence com-
n object the stop
ommunication object the
cation object the
tion
ts
ts
ment command is
object and sent
he input.
alue and also does
ommunication object the Up
ommand (value “1”)
(value “1” or “0”)
ommunication object
ommunication object
ion / Stop
s written into the
when releasing the
alue and also does
red into the com-
Parameters
Setting
Xn+1 - Long push action min.
0.5 second
1 second
2 seconds
3 seconds
4 seconds
5 seconds
10 seconds
This parameter determines the minimum period for detecting a long
push.
Contact type
Normally open contact
Normally closed contact
The contact type of the input attached to the channel is adjusted here.
“Normally open contact”: the contact of the input is active when
closed, inactive when opened.
“Normally closed contact”: the contact of the input is active when
opened, inactive when closed.
add enable object
Yes /
No
The parameter determines if the input can be blocked via an additional
Enable object or not. If an input is blocked (Enable value = 0) the status
changes at this input are not transmitted.
8.2 Outputs
8.2.1 relays
function On/Off
No.
Object name
function
Size
flags
114
(118, 122,
126, 130,
134, 138,
142, 146,
150, 154,
158, 162,
166, 170,
174)
Output Xn
Switching
1.001 DPT_
Switch
CW
This object is used to receive the swithing telegrams that are transfer-
red to the relay channel.
Switching telegrams are sent via the group address linked with this
object.
115
(119, 123,
127, 131,
135, 139,
143, 147,
151, 155,
159,163,
167, 171,
175)
Output Xn,
Switching
Status
1.001 DPT_
Switch
CRT
The current switching state of the channel is saved in the status object. It
is automatically sent each time the object value changes.
116
(120, 124,
128, 132,
136, 140,
144, 148,
152, 156,
160, 164,
168, 172,
176)
Output Xn
Enable
1.003 DPT_
Enable
CW
Enable telegrams are received via the group address linked with this
object. They are used to lock (disable) or unlock (enable) the correspon-
ding input.
No.
Object name
function
Size
flags
117
(121, 125,
129, 133,
137, 141,
145, 149,
153, 157,
161, 165,
169, 173,
177)
Output Xn
2bits Over
-
ride
2.001
DPT_Switch_
Control
CW
Override telegrams are received via the group address linked with this
object.
Output Xn can be forcibly operated (e.g. by a higher-level control). The
value of the communication object directly defines the forced position
of the contact:
0 or 1 = The output is not forcibly operated (0 switched off, 1 switched
on).
2 = The output is forcibly switched off.
3 = The output is forcibly switched on.
Parameters
Setting
Active Xn
Yes /
No
Xn : Delay before Off
immediate
, 500 ms,
1 second, 2 seconds,
5 seconds, 10 seconds,
30 seconds, 1 minute, 90 s,
2 min., 10 min., 15 min.,
30 min., 45 min., 1 h, 90 min.
This parameter sets the wanted OFF delay time. A set OFF delay acts
only on the object “Output Xn, Switch”
Xn : Delay before On
immediate
, 500 ms,
1 second, 2 seconds,
5 seconds,10 seconds,
30 seconds, 1 minute, 90 s,
2 min., 10 min., 15 min.,
30 min., 45 min., 1 h, 90 min.
This parameter sets the wanted ON delay time. A set ON delay acts only
on the object “Output Xn, Switch”.
Xn : Active auto. off
Yes /
No
This parameter defines if the ouput is to be permanently switched on
using the manual command and has to be switch off again using the
manual command (No), or if it is switched on manually for a limited
period and then automatically switched off (Yes).
Xn : auto. off delay
immediate
, 500 ms,
1 second, 2 seconds,
5 seconds,10 seconds,
30 seconds, 1 minute, 90 s,
2 min., 10 min., 15 min.,
30 min., 45 min., 1 h, 90 min.
This parameter determines the delay before automatic switch-off.
Xn : Invert relay polarity
Yes /
No
The polarity type of the output attached to the channel is adjusted
here.
“No”: the contact of the output is close when active, open when
inactive
“Yes”: the contact of the output is open when active, closed when
inactive
S000074637EN-5.indd 19