Technical data

480VAC Models

Type

Power

[Hp/kW]

Mains

Output Current

SM2 

Watts

Loss

SM4 

Watts 

Loss

Voltage

(1)

I

in

I

n

CLim

max

(2)

400V

480V

400V

480V

400V

480V

174620-174671

0.5 / 0.37

400 V Three-phase (3/PE)

(340 … 440 V)

OR

480 V Three-phase (3/PE)

(340 … 528 V)

1.7

1.5

1.3

1.1

175

200

23

21

174621-174672

1 / 0.75

2.9

2.5

2.4

2.1

175

200

37

33

174622-174673

1.5 / 1.1

4.2

3.6

3.5

3.0

175

200

48

42

174623-174674

2 / 1.5

4.7

4.1

4.0

3.5

175

200

57

50

174624-174675

3 / 2.2

6.1

5.4

5.5

4.8

175

200

87

78

174625-174676

5 / 4.0

10.6

9.3

9.4

8.2

175

200

128

103

174626-174677

7.5 / 5.5

14.2

12.4

12.6

11.0

175

200

178

157

174627-174678

10 / 7.5

18.1

15.8

16.1

14.0

175

200

208

190

174628

15 / 11

27

24

24

21

155

180

418

174629

20 / 15

35

31

31

27

155

180

493

174630

25 / 18.5

44

38

39

34

155

180

645

174991

30 / 22

52

45

46

40

155

180

709

174992

40 / 30

68

59

60

52

155

180

1020

174710

50 / 37.5

85

74

75

65

155

180

1275

174711

60 / 45

100

87

88

77

155

180

1530

600 VAC Models

Type

Power

[Hp/kW]

Mains

Output Current

SM2 

Watts

Loss

SM4 

Watts 

Loss

Voltage

(1)

I

in

I

n

CLim

max

(2)

174631-174663

1 / 0.75

600 V Three-phase (3/PE)

(425 … 660 V)

2.0

1.7

200

37

31

174632-174664

2 / 1.5

3.2

2.7

200

51

43

174633-174665

3 / 2.2

4.4

3.9

200

68

57

174634-174666

5 / 4.0

6.8

6.1

200

101

67

174635-174667

7.5 / 5.5

10.2

9

200

148

116

174636-174668

10 / 7.5

12.4

11

200

172

152

174637

15 / 11

19.7

17

180

380

174638

20 / 15

25

22

180

463

174639

25 / 18.5

31

27

180

560

174993

30 / 22

36

32

180

640

174994

40 / 30

47

41

180

930

174712

50 / 37.5

59

52

180

1163

174713

60 / 45

71

62

180

1395

(1) Frequency Range: 48 Hz … 62 Hz

(2) Current Limit (CLim) is a percentage of the output current, I

n

.  CLim

max

 is the maximum setting for P171.  

For 480VAC models, the CLim

max

 value in the 480V column of the table is used when P107 is set to 1. 

The CLim

max

 value in the 400V column is used when P107 is set to 0.

STOP!

Drive Derating

The SM2 and SM4 Vector Series drive is designed to operate at the Nominal Output Current (I

n

)shown 

in the Ratings tables for most standard applications and industrial environments. The drive output 

current or operating temperature may need to be limited as described below:

•  For installations above 1000m a.m.s.l., derate I

n

 by 5% per 1000m, do not exceed 4000m a.m.s.l.

• Operation above 40°C, derate I

n

 by 2.5% per °C, do not exceed 55°C.

•  Carrier Frequency (P166): 

- If P166=2 (8 kHz), derate I

n

 to 92% of drive rating or do not exceed 33°C ambient 

- If P166=3 (10 kHz), derate I

n

 to 84% of drive rating or do not exceed 27°C ambient

For combinations of the above, please consult LEESON applications support for proper derating.

CALL NOW 800-985-6929

http://www.automatedpt.com

Email: [email protected]

CALL NOW 800-985-6929

http://www.automatedpt.com

Email: [email protected]

Содержание SPEEDMASTER SM2 Series

Страница 1: ...ctor SM4 Series Flux Vector Installation and Operation Manual A Regal Brand CALL NOW 800 985 6929 http www automatedpt com Email charles automatedpt com CALL NOW 800 985 6929 http www automatedpt com...

Страница 2: ...and Modes of Operation 19 4 3 Parameter setting 20 4 4 Electronic programming module EPM 20 4 5 Parameter menu 21 4 5 1 Basic Setup Parameters 21 4 5 2 I O Setup Parameters 25 4 5 3 Advanced Setup Pa...

Страница 3: ...al SV06 Made in USA Inverter SM2 Vector V0115 2 About these instructions A Certifications C Input Ratings B Type D Output Ratings Scope of delivery Important 1 SM2 or SM4 Vector inverter with EPM inst...

Страница 4: ...information about UL Warnings Suitable for use on a circuit capable of delivering not more than 200 000 rms symmetrical amperes at the maximum voltage rating marked on the drive Use minimum 75 C copp...

Страница 5: ...ccordance with European directives reference machinery directive and electromagnetic compatibility directive It is the responsibility of the end user to ensure that the machine meets the applicable st...

Страница 6: ...ures are plenun rated in accordance with UL 508C and are suitable for installation in a compartment handling conditioned air Protection measures against short circuit earth fault phase loss over volta...

Страница 7: ...E OR 240 V Three phase 3 PE 170 264 V 5 1 2 9 2 4 200 27 30 174608 174656 1 0 75 8 8 5 0 4 2 200 41 42 174609 174657 1 5 1 1 12 0 6 9 6 0 200 64 63 174610 174658 2 1 5 13 3 8 1 7 0 200 75 73 174611 17...

Страница 8: ...5 5 10 2 9 200 148 116 174636 174668 10 7 5 12 4 11 200 172 152 174637 15 11 19 7 17 180 380 174638 20 15 25 22 180 463 174639 25 18 5 31 27 180 560 174993 30 22 36 32 180 640 174994 40 30 47 41 180...

Страница 9: ...5 45 138 0 6 15 2 0 50 2 8 1 3 CH3 174615 174625 174634 3 90 99 3 10 79 7 50 190 7 00 178 0 25 6 5 80 147 0 6 15 2 0 50 3 2 1 5 CH4 174616 174617 174626 174627 174635 174636 5 12 130 4 25 108 9 83 25...

Страница 10: ...0 6 15 2 0 50 24 0 10 9 CH7 174710 174712 8 72 221 7 50 190 17 19 436 16 30 414 0 45 11 4 10 07 256 0 6 15 2 0 50 31 14 1 CH8 174711 174713 8 72 221 7 50 190 20 09 513 19 30 490 0 45 11 4 10 07 256 0...

Страница 11: ...167 0 66 17 6 31 160 2 00 51 2 00 51 5 9 2 68 CH3 174659 7 12 181 6 74 171 8 00 203 6 56 167 0 66 17 6 77 172 2 00 51 2 00 51 7 1 3 24 CH4 174661 174662 174678 174668 8 04 204 7 56 192 10 00 254 8 04...

Страница 12: ...ply PE L1 L2 N PE L1 N 3 2 Electrical installation Installation After a Long Period of Storage STOP Severe damage to the drive can result if it is operated after a long period of storage or inactivity...

Страница 13: ...omply with local safety regulations for high leakage current equipment 174603 174604 174605 174651 174652 174653 174654 174603 174604 174605 174651 174652 174653 174654 174607 174608 174609 174610 174...

Страница 14: ...800 3 or other EMC standards motor cables line cables and control or communications cables must be shielded with each shield screen clamped to the drive chassis This clamp is typically located at the...

Страница 15: ...amic braking operation The dynamic brake resistor connections for 40 60HP 30 45kW drives are standard built in connections as illustrated in the diagram below In the 40HP 30kW model drives the dynamic...

Страница 16: ...174620 174624 174671 174675 M10 A C10 A 10 A 1 5 14 174625 174676 M16 A C16 A 20 A 2 5 14 174626 174677 M20 A C20 A 20 A 2 5 14 174627 174678 M25 A C25 A 25 A 4 0 10 174628 M40 A C40 A 40 A 4 8 174629...

Страница 17: ...ce 4 3k 2 Analog Common 5 Analog Input 0 10 VDC input resistance 50 k 6 Internal DC supply for speed pot 10 VDC max 10 mA 25 Analog Input 4 20 mA input resistance 250 4 Digital Reference Common 15 VDC...

Страница 18: ...o the drive inputs with dry contacts or with PNP solid state switches set the switch and P120 to High If using NPN devices for inputs set both to Low Active high is the default setting HIGH 12 30 V LO...

Страница 19: ...er Menu when programming the drive and to enter a changed parameter value UP AND DOWN BUTTONS Used for programming and can also be used as a reference for speed PID setpoint or torque setpoint When th...

Страница 20: ...P100 6 the CTRL button is used to toggle start control between the terminal strip REMOTE and the keypad LOCAL REM LOC LED indicating the present start control source is ON Press CTRL the LED for othe...

Страница 21: ...when the drive is in run non programming mode If P179 0 the Units LEDs will show the unit of the diagnostic parameter that is being displayed current display value is in RPM current display value is i...

Страница 22: ...inserted into a drive without power being applied to the drive This means that the drive will be fully operational with the new settings on the next application of power Additionally when the drive s...

Страница 23: ...keypad using one of the TB 13 inputs See note below 6 CTRL Button Select Allows start control to be switched between terminal strip and local keypad using the CTRL button NOTE P100 Selection 6 is app...

Страница 24: ...ine manufacturer before operating above rated frequency Overspeeding the motor machine may cause damage to equipment and injury to personnel P104 Acceleration Time 1 20 0 0 0 s 3600 P104 time of frequ...

Страница 25: ...ailed attempts drive will Auto Restart with DC brake P110 5 Performs speed search starting at Max Frequency P103 P110 6 Performs speed search starting at the last output frequency prior to faulting or...

Страница 26: ...ay cause damage to equipment and or injury to personnel Automatic starting restarting should only be used on equipment that is inaccessible to personnel P111 Stop Method 0 0 Coast Drive s output will...

Страница 27: ...s been setup on the terminal strip then reference control is dictated by P101 2 Manual Control Only Reference is dictated by P101 regardless of any AUTO source that may be selected by the TB 13x termi...

Страница 28: ...art Forward See note for typical circuit 12 Start Reverse 13 Run Forward See note for typical circuit 14 Run Reverse 15 Jog Forward Jog Forward speed P134 16 Jog Reverse Jog Reverse speed P135 WARNING...

Страница 29: ...setting except 0 and 3 can only be used once One input is set to MOP Up and another is not set to MOP Down or vice versa One input is set to 10 and another input is set to 11 14 One input is set to 11...

Страница 30: ...2 Reverse Energizes when reverse rotation is active 3 Fault De energizes when the drive trips or power is removed 4 Inverse Fault Energizes when the drive trips 5 Fault Lockout P110 3 6 De energizes...

Страница 31: ...P215 21 Inverse PID Feedback Max Alarm De energizes when PID feedback signal P215 22 PID Feedback within Min Max Alarm range Energizes when PID feedback signal is within the Min Max Alarm range see P...

Страница 32: ...0 s 240 0 P149 Analog Offset 0 0 0 100 Scaled value Example P149 10 Scaled variable freq P150 1 P152 60Hz then TB30 0VDC below 6HZ P150 TB 30 Output 0 0 None 2 10 VDC signal can be converted to 4 20 m...

Страница 33: ...TB25 0 20mA 7 TB5 10 10 VDC TB25 0 20mA Available on special option module only P157 TB5 0 10 VDC Analog Input Monitoring Action 0 No Action Selects the reaction to a loss of the 0 10 V signal at TB5...

Страница 34: ...ion 0 0 No Action Selects the reaction to a loss of the 4 20 mA signal at TB 25 Signal is considered lost if it falls below 2 mA Digital outputs can also indicate a loss of 4 20 mA signal see P140 P14...

Страница 35: ...reases Digital outputs can also indicate when the limit is reached see P140 P142 Refer to section 2 2 for CLimmax P172 Current Limit Reduction 0 0 Current Limit Reduction Active Normal response In fie...

Страница 36: ...control mode For this parameter to be used P178 must be set to a value other than 0 IF P178 is set to 0 the Hz LED will be illuminated regardless of the value set in P177 1 RPM 2 3 UNITS 4 NONE P178 D...

Страница 37: ...always on with deceleration 3 Braking with bus regulator 4 Special Consult factory before using P191 Motor Brake Level 0 0 75 flux braking disabled Active when P190 0 and drive is in deceleration mode...

Страница 38: ...t to 1 or 2 Note 2 When P199 is set to 1 the drive operates from the OEM settings stored in the EPM Module and no other parameters can be changed GE will be displayed if attempted Note 3 Auto Calibrat...

Страница 39: ...t TB 13x 6 Auto Reference Keypad TB 13x closed PID mode is active TB 13x open PID mode is disabled and the drive speed will be controlled by the reference selected in P101 P201 PID Feedback Source 0 0...

Страница 40: ...P231 Preset PID Setpoint 1 0 0 P204 P205 TB 13A activated P121 3 and P200 1 or 2 P232 Preset PID Setpoint 2 0 0 P204 P205 TB 13B activated P122 3 and P200 1 or 2 P233 Preset PID Setpoint 3 0 0 P204 P2...

Страница 41: ...from setpoint by more than P242 1 Recovery only if Feedback P246 2 Recovery only if Feedback P246 P250 Auto Rinse in Sleep Mode 0 0 Disabled Activated in sleep mode only 1 Enabled Sleep Recovery cance...

Страница 42: ...ply a Start command Display will indicate CAL for about 40 seconds Once the calibration is complete the display will indicate StoP apply another Start command to actually start the motor If an attempt...

Страница 43: ...P122 3 and P300 5 P333 Preset Torque Setpoint 3 100 0 400 TB 13C activated P123 3 and P300 5 P334 2 Preset Torque Setpoint 4 100 0 400 TB 13D activated P124 3 and P300 5 P340 1 Current Loop P Gain 0 2...

Страница 44: ...ation enable operation in vector mode w o Auto Calibration 4 Standard Calibration Complete 5 Advanced Calibration Complete Note To run the Auto Calibration Set P302 P306 according to motor nameplate S...

Страница 45: ...x1200 12 0 0 P402 Module Status 0 0 Not Initialized 1 Initialization Module to EPM 2 Initialization EPM to Module 3 Online 4 Failed Initialization Error 5 Time out Error 6 Initialization Failed Module...

Страница 46: ...s Format n xxx where n 1 8 1 is the newest fault xxx fault message without the F see Section 5 3 P501 Software version Format x yz P502 Drive ID A flashing display indicates that the Drive ID stored i...

Страница 47: ...Total Run Time 0 h 9999999 Alternating display xxx yyyy when value exceeds 9999 P541 Total Power On Time 0 h 9999999 P550 Fault History 1 8 Displays the last 8 faults Format n xxx where n 1 8 1 is th...

Страница 48: ...tes the protective circuit is active LED 1 the Logic Assertion Switch is set to High input terminal is asserted LED 2 output terminal is energized LED 4 the Charge Relay is not a terminal this segment...

Страница 49: ...have access to any of the other P6xx parameters P610 Network Address 1 1 247 Modbus 1 1 99 Lecom P611 Network Baud Rate 2 0 2400 bps Modbus 1 4800 bps 2 9600 bps 3 19200 bps 0 0 9600 bps Lecom 1 4800...

Страница 50: ...22 123 25 step sequence 3 Enabled transition on timer or rising edge P701 Sequencer TB13A Trigger Segment 1 1 16 TB13A lowest priority Asserting TB13A with selection 24 Start Sequence starts the seque...

Страница 51: ...00 0 If P112 1 negative sign forces reverse direction P711 Segment 1 Accel Decel Time 20 0 0 0 sec 3600 0 P712 Segment 1 Time in current step 0 0 0 0 0 P708 6553 5 0 P708 65535 Scaling units depend on...

Страница 52: ...t 1 ON Energized The corresponding digital output relay must be set to accept value the Bit1 TB14 P724 Segment 3 TB30 Analog Output Value 0 00 0 00 VDC 10 00 TB30 configuration parameter must be set t...

Страница 53: ...sign forces reverse direction P736 Segment 6 Accel Decel Time 20 0 0 0 sec 3600 0 P737 Segment 6 Time in current step 0 0 0 0 0 P708 6553 5 0 P708 65535 Scaling units depend on P708 Skip segment if ti...

Страница 54: ...The corresponding digital output relay must be set to accept value the Bit1 TB14 P749 Segment 8 TB30 Analog Output Value 0 00 0 00 VDC 10 00 TB30 configuration parameter must be set to accept this va...

Страница 55: ...sign forces reverse direction P761 Segment 11 Accel Decel Time 20 0 0 0 sec 3600 0 P762 Segment 11 Time in current step 0 0 0 0 0 P708 6553 5 0 P708 65535 Scaling units depend on P708 Skip segment if...

Страница 56: ...ng digital output relay must be set to accept value the from the sequencer P140 P142 27 Bit1 TB14 P774 Segment 13 TB30 Analog Output Value 0 00 0 00 VDC 10 00 TB30 configuration parameter must be set...

Страница 57: ...tive sign forces reverse direction P786 Segment 16 Accel Decel Time 20 0 0 0 sec 3600 0 P787 Segment 16 Time in current step 0 0 0 0 0 P708 6553 5 0 P708 65535 Scaling units depend on P708 Skip segmen...

Страница 58: ...ent Stop or end segment DC Brake 1 Stop based on P111 2 Coast to Stop 3 Quick Stop 4 Coast with DC Brake 5 Ramp with DC Brake WARNING If P795 0 then toggling the start sequence input will also restart...

Страница 59: ...Terminal Strip 0 1 2 2 P100 Start from Remote Keypad 3 1 Start from Network SMV communications module Notes 1 Refer to relevant communications module user guide for starting from a communications netw...

Страница 60: ...will continue to complete the time remaining in the segment Notes 4 The end segment is entered once the highest number segment with a non zero value in the time in current segment P712 P711 etc parame...

Страница 61: ...tive Segment 11 active Segment 10 active Segment 9 active Segment 8 active Segment 7 active Segment 6 active Segment 5 active Segment 4 active Segment 3 active Segment 2 active End Segment active Outp...

Страница 62: ...per size for application dEC Decel Override The drive has stopped decelerating to avoid tripping into HF fault due to excessive motor regen 2 sec max If drive trips into HF fault Increase P105 P126 In...

Страница 63: ...e has tripped into a fault and will automatically restart P110 3 6 To disable Auto Restart set P110 0 2 spd PID Mode disabled Drive has been taken out of PID Mode See P200 stoP Output frequency 0 Hz o...

Страница 64: ...G Jog nt Network OP MOP P1 P7 Preset 1 7 01 16 Sequencer Segment Example L S CP Local Keypad Start control Speed mode Keypad speed reference t p EU Terminal Strip Start control PID mode 0 10 VDC setpo...

Страница 65: ...raking fault Dynamic braking resistors are overheating Increase active decel time P105 P126 P127 Check mains voltage and P107 f EF External fault P121 P123 21 and that digital input has been opened P1...

Страница 66: ...ad connections f LF Low DC Bus Voltage fault Mains voltage too low Check mains voltage f n1d No Motor ID fault An attempt was made to start the drive in Vector or Enhanced V Hz mode prior to performin...

Страница 67: ...g Restart fault Controller was unable to synchronize with the motor during restart attempt P110 5 or 6 Check motor load f SF Single Phase fault A mains phase has been lost Check mains voltage f UF Sta...

Страница 68: ...phase 2 PE ESV251GG2SFG 38 12 35 10 33 5 30 N A ESV371GG2SFG 38 12 35 10 33 5 30 N A ESV751GG2SFG 38 12 35 10 33 5 30 N A ESV112GG2SFG 38 12 35 10 33 5 30 N A ESV152GG2SFG 38 12 35 10 33 5 30 N A ESV...

Страница 69: ...cidental or other damages Even if the repair or replacement remedy shall be deemed to have failed of its essential purpose under Section 2 719 of the Uniform Commercial Code the manufacturer shall hav...

Страница 70: ...PH 262 377 8810 FAX 262 377 9025 www leeson com REGAL BELOIT CANADA Mississauga Toronto Ontario Canada L5T 2N7 PH 905 670 4770 FAX 905 670 4378 Service Dept FAX 262 377 0090 www lesson ca CALL NOW 800...

Отзывы: