7
Technical data
480VAC Models
Type
Power
[Hp/kW]
Mains
Output Current
SM2
Watts
Loss
SM4
Watts
Loss
Voltage
(1)
I
in
I
n
CLim
max
(2)
400V
480V
400V
480V
400V
480V
174620-174671
0.5 / 0.37
400 V Three-phase (3/PE)
(340 … 440 V)
OR
480 V Three-phase (3/PE)
(340 … 528 V)
1.7
1.5
1.3
1.1
175
200
23
21
174621-174672
1 / 0.75
2.9
2.5
2.4
2.1
175
200
37
33
174622-174673
1.5 / 1.1
4.2
3.6
3.5
3.0
175
200
48
42
174623-174674
2 / 1.5
4.7
4.1
4.0
3.5
175
200
57
50
174624-174675
3 / 2.2
6.1
5.4
5.5
4.8
175
200
87
78
174625-174676
5 / 4.0
10.6
9.3
9.4
8.2
175
200
128
103
174626-174677
7.5 / 5.5
14.2
12.4
12.6
11.0
175
200
178
157
174627-174678
10 / 7.5
18.1
15.8
16.1
14.0
175
200
208
190
174628
15 / 11
27
24
24
21
155
180
418
174629
20 / 15
35
31
31
27
155
180
493
174630
25 / 18.5
44
38
39
34
155
180
645
174991
30 / 22
52
45
46
40
155
180
709
174992
40 / 30
68
59
60
52
155
180
1020
174710
50 / 37.5
85
74
75
65
155
180
1275
174711
60 / 45
100
87
88
77
155
180
1530
600 VAC Models
Type
Power
[Hp/kW]
Mains
Output Current
SM2
Watts
Loss
SM4
Watts
Loss
Voltage
(1)
I
in
I
n
CLim
max
(2)
174631-174663
1 / 0.75
600 V Three-phase (3/PE)
(425 … 660 V)
2.0
1.7
200
37
31
174632-174664
2 / 1.5
3.2
2.7
200
51
43
174633-174665
3 / 2.2
4.4
3.9
200
68
57
174634-174666
5 / 4.0
6.8
6.1
200
101
67
174635-174667
7.5 / 5.5
10.2
9
200
148
116
174636-174668
10 / 7.5
12.4
11
200
172
152
174637
15 / 11
19.7
17
180
380
174638
20 / 15
25
22
180
463
174639
25 / 18.5
31
27
180
560
174993
30 / 22
36
32
180
640
174994
40 / 30
47
41
180
930
174712
50 / 37.5
59
52
180
1163
174713
60 / 45
71
62
180
1395
(1) Frequency Range: 48 Hz … 62 Hz
(2) Current Limit (CLim) is a percentage of the output current, I
n
. CLim
max
is the maximum setting for P171.
For 480VAC models, the CLim
max
value in the 480V column of the table is used when P107 is set to 1.
The CLim
max
value in the 400V column is used when P107 is set to 0.
STOP!
Drive Derating
The SM2 and SM4 Vector Series drive is designed to operate at the Nominal Output Current (I
n
)shown
in the Ratings tables for most standard applications and industrial environments. The drive output
current or operating temperature may need to be limited as described below:
• For installations above 1000m a.m.s.l., derate I
n
by 5% per 1000m, do not exceed 4000m a.m.s.l.
• Operation above 40°C, derate I
n
by 2.5% per °C, do not exceed 55°C.
• Carrier Frequency (P166):
- If P166=2 (8 kHz), derate I
n
to 92% of drive rating or do not exceed 33°C ambient
- If P166=3 (10 kHz), derate I
n
to 84% of drive rating or do not exceed 27°C ambient
For combinations of the above, please consult LEESON applications support for proper derating.