Commissioning
Code
Possible Settings
IMPORTANT
No.
Name
Default Selection
P244
Sleep Entry
Mode
0
0 Enter SLEEP if Drive Speed
<P240
For time longer than P241
1 Enter SLEEP if Feedback
>P243
For time longer than P241 or same
as Sel 0
2 Enter SLEEP if Feedback
<P243
For time longer than P241 or same
as Sel 0
P245
Sleep Entry Stop
Type
0
0 Coast to Stop
1 Ramp to Stop
2 Stop with P111 settings
P246
Feedback
Recovery
from Sleep
Threshold
0.0
P204 P205
Active only when P247 = 1 or 2
P247
Sleep Recovery
Mode
0
0 Recovery if Speed Setpoint
> P240 or if PID feedback
differs from setpoint by more
than P242
1 Recovery only if Feedback
< P246
2 Recovery only if Feedback
> P246
P250
Auto Rinse in
Sleep
Mode
0
0 Disabled
Activated in sleep mode only.
1 Enabled
Sleep Recovery cancels Auto Rinse
P251
Time Delay
between
Auto Rinses
30.0 0.0 {min} 6553.5
Time delay reset by re/entering sleep
mode
P252
Auto Rinse
Speed
0.0
-500.0 {Hz} 500.0
If P112 = 1, negative sign = reverse
direction
P253
Auto Rinse Time
0.0
0.0 {sec} 6553.5
Does not include time to decel back
to speed
Auto Pump Rinse Setup:
P250=1 (Enabled)
P251=# minutes between each
Pump Rinse
P252=Hz speed of Pump Rinse
P253=# seconds Pump Rinse
duration