29
Commissioning
Code
Possible Settings
IMPORTANT
No.
Name
Default Selection
P131
Preset Speed #1
0.0
0.0
{Hz} 500
PRESET
SPEED
13A 13B 13C 13D
1
X
--
--
--
2
--
X
--
--
3
--
--
X
--
4
X
X
--
--
4 (alternate) --
--
--
X
5
X
--
X
--
6
--
X
X
--
7
X
X
X
--
8 (alternate) --
X
--
X
8 (alternate) --
--
X
X
P132
Preset Speed #2
0.0
0.0
{Hz} 500
P133
Preset Speed #3
0.0
0.0
{Hz} 500
P134
Preset Speed #4
0.0
0.0
{Hz} 500
P135
Preset Speed #5
0.0
0.0
{Hz} 500
P136
Preset Speed #6
0.0
0.0
{Hz} 500
P137
Preset Speed #7
0.0
0.0
{Hz} 500
P138
Preset Speed #8
0.0
0.0 {Hz} 500
P140
Relay Output
TB-16, 17
0
0 None
Disables the output
1 Run
Energizes when the drive is running
2 Reverse
Energizes when reverse rotation is
active
3 Fault
De-energizes when the drive trips, or
power is removed
4 Inverse Fault
Energizes when the drive trips
5 Fault Lockout
P110 = 3...6: De-energizes if all
restart attempts fail
6 At Speed
Energizes when output frequency =
commanded frequency
7 Above Preset Speed #6
Energizes when output freq. > P136
8 Current Limit
Energizes when motor current = P171
9 Follower Loss (4-20 mA)
Energizes when 4-20 mA signal falls
below 2 mA
10 Loss of Load
Energizes when motor load drops
below P145; see also P146
• Speed setting is used by P158
• 13D available on 15HP (11kW) &
higher drives.