52
Commissioning
Code
Possible Settings
IMPORTANT
No.
Name
Default Selection
Segment #5
P730
Segment #5
Frequency
Setpoint
0.0
-500.0
{Hz}
500.0
If P112 = 1, negative sign forces
reverse direction
P731
Segment #5
Accel/Decel Time
20.0
0.0
{sec} 3600.0
P732
Segment #5
Time in current
step
0.0
0
0.0
{P708}
6553.5
0
{P708}
65535
Scaling/units depend on P708
Skip segment if time = 0
P733
Segment #5
Digital Output
State
0
Bit0 Relay
bit = 0: OFF (De-energized)
bit = 1: ON (Energized)
The corresponding digital output/
relay must be set to accept value the
from the sequencer: P140, P142=27
Bit1 TB14
P734
Segment #5
TB30
Analog Output
Value
0.00
0.00
{VDC} 10.00
TB30 configuration parameter must
be set to accept this value: P150
= 10
Segment #6
P735
Segment #6
Frequency
Setpoint
0.0
-500.0
{Hz}
500.0
If P112 = 1, negative sign forces
reverse direction
P736
Segment #6
Accel/Decel Time
20.0
0.0
{sec} 3600.0
P737
Segment #6
Time in current
step
0.0
0
0.0
{P708}
6553.5
0
{P708}
65535
Scaling/units depend on P708
Skip segment if time = 0
P738
Segment #6
Digital Output
State
0
Bit0 Relay
bit = 0: OFF (De-energized)
bit = 1: ON (Energized)
The corresponding digital output/
relay must be set to accept value the
from the sequencer: P140, P142=27
Bit1 TB14
P739
Segment #6
TB30
Analog Output
Value
0.00
0.00
{VDC} 10.00
TB30 configuration parameter must
be set to accept this value: P150
= 10
Segment #7
P740
Segment #7
Frequency
Setpoint
0.0
-500.0
{Hz}
500.0
If P112 = 1, negative sign forces
reverse direction
P741
Segment #7
Accel/Decel Time
20.0
0.0
{sec} 3600.0
P742
Segment #7
Time in current
step
0.0
0
0.0
{P708}
6553.5
0
{P708}
65535
Scaling/units depend on P708
Skip segment if time = 0