User Manual Of ELP AC Servo
115
www.leadshine.com
Repower
-
When analog speed given value under speed control mode less than zero speed clamp
level setup, speed command will set to 0 strongly.
Other setup for SI/SO function
For details of SI input function, refer to Pr4.00 – Pr4.09.
For details of SO output function, refer to Pr4.10 – Pr4.15.
8.3 Torque Control
Notice :
Analog input for Torque/Velocity mode is only available for ELP-RS***Z
Pls do inspection before velocity control test run.
Table 8.6 Parameter Setup of Torque Control
No
Parameter
Name
input
Setup value
Unit
1
Pr0.01
Control mode setup
/
2
/
2
Pr3.12
Acceleration time setup
/
User-specified
ms
3
Pr3.13
Deceleration time setup
/
User-specified
ms
4
Pr3.14
Sigmoid acceleration/deceleration time setup
/
User-specified
ms
5
Pr3.15
Zero-clamp function selection
/
0
/
6
Pr3.17
Torque setup internal/external switching
/
0
/
7
Pr3.19
Torque command direction input gain
/
User-specified
0.1V/100%
8
Pr3.20
Torque setup input reversal
/
User-specified
/
9
Pr3.21
Speed limit value 1
/
User-specified
r/min
10
Pr4.00
SI1 input selection
Srv_on
hex:030000
/
11
Pr4.28
Analog input 3(AI3) offset setup
/
User-specified
0.359mv
12
Pr4.29
Analog input 3(AI3) filter
/
User-specified
0.01ms
◆
Wiring Diagram
◆
Operation Steps
1. connect terminal CN1.
2. Enter the power (DC12V to 24V) to control signal (the and SI1).
3. Enter the power to the driver.
4. Confirm the value of the parameters, and write to the EEPROM and turn off/on the power (of the driver)
5.Connect the Srv_on input to bring the driver to servo-on status and energize the motor.
6. apply DC voltage between torque command input ,AI1 and AGND, and gradually increase from 0V to
confirm the motor runs.
7.
Check the motor torque at monitor mode ("
d04tr
" ), Whether actual torque is as per the setup or not
8.
When you want to change the torque magnitude, direction and velocity limit value against the command
voltage, set up the following parameters :
Pr3.19. Pr3.20. Pr3.21
If the motor does not run correctly, refer to the Factor of No-Motor running in data monitor mode
("
d17Ch
" ).