Set up internal command speeds, 1st to 8th
8.2.3 Speed command acceleration and deceleration
On the basis of speed command input, acceleration and deceleration are added as internal speed
commands to control the speed. This function can be used when entering the ladder-like speed command and
internal speed setting. In addition, the acceleration and deceleration function can also be used when the
vibration is reduced by the change of acceleration
Pr3.12
Name
time setup acceleration
Mode
S
Range
0~10000
Unit
Ms/
(1000r/min)
Default
100
Data Type
16bit
Access R/W
Address
0319H
Repower
-
Pr3.13
Name
time setup deceleration
Mode
S
Range
0~10000
Unit
Ms/
(1000r/min)
Default
100
Data Type
16bit
Access R/W
Address
031BH
Repower
-
Set up acceleration/deceleration processing time in response to the speed command
input.
Set the time required for the speed command(stepwise input)to reach 1000r/min to
Pr3.12
Acceleration time setup. Also set the time required for the speed command to reach
from 1000r/min to 0 r/min, to Pr3.13 Deceleration time setup.
Assuming that the target value of the speed command is Vc(r/min), the time required
for acceleration/deceleration can be computed from the formula shown below.
Acceleration time (ms)=Vc/1000 *Pr3.12 *1ms
Deceleration time (ms)=Vc/1000 *Pr3.13 *1ms
Pr3.14
Name
Sigmoid acceleration
/deceleration time setup
Mode
S
Range
0~1000
Unit
ms
Default
0
Data Type
16bit
Access R/W
Address
031DH
Repower