User Manual for ELD2 Servo
www.leadshine.com
81
22-23
Pr9.07
Trigger control
0x0010
24
CRC
Check code
L
25
H
62 00
first address mapped to Pr9.00
00 08
8 consecutive operating addresses from 62 00 to 62 07
,
mapped to Pr9.00~Pr9.07
10
Hexadecimal data of the number of data
,
8 register
,
each address data is divided into high and low
bits
,
8*2=16
00 01
data written down to the first addresses of 6200 mapped to Pr9.00
Motion Model
,
Absolute positioning mode
00 01 86 A0
data written down to the second and third addresses of 6201 mapped to Pr9.01
;
6202 mapped to
Pr9.02
Hexadecimal data of position=100000plus. All positions in PR mode are in units of 10000P/r
,
therefore, 00 01 86 A0 represents ten turns of motor rotation
01 F4
data written down to the fourth addresses of 6203 mapped to Pr9.03
Hexadecimal data of Speed=500r/min
00 64
data written down to the five addresses of 6204 mapped to Pr9.04
Hexadecimal data of acceleration time=100ms
00 64
data written down to the six addresses of 6205 mapped to Pr9.05
Hexadecimal data of deceleration time=100ms
00 00
data written down to the seven addresses of 6206 mapped to Pr9.06
Hexadecimal data of the delay time=0ms
00 10
data written down to the eight addresses of 6207 mapped to Pr9.07
,
to trigger the action
,
Immediately trigger method
(
1P
,
Immediately trigger path-P
,
The sample Pr9.00~9.07 is the
positioning related data of path-0
)
67 B3
the CRC verification code, do not have to directly input, click the corresponding send area
verification button automatically generated
The final analysis is as follows: speed is 500r/min, acceleration and deceleration time is 100ms, and the
position of absolute positioning is 10 rotation
11 10 62 00 00 08 10 00 01
00 00 00 00
01 F4 00 64 00 64 00 00 00 10 3B 73
The final analysis was performed at a speed of 500r/min, acceleration and deceleration time of 100ms, and the
position of absolute positioning 0 rotation was taken
Homing
:
11 06 60 02 00 21 F4 82
(
Back to origin high-speed, low-speed, and back to zero mode can be set in
the eighth set of parameters, using default values this time
)
Caution
:
In Pr mode, the origin induction switch is connected to the driver, which is different from the impulse
control. Limited by conditions, only the current position can be demonstrated to the customer
:
Write 0x021
,
The current location manually set to zero.
。
The frame format function is
:
11
slave ID 17
06
function code
,
write single data
NO
Send
Receive
1
ID
Slave ID
0x01
ID
Slave ID
0x01