LAUDA Ultra-Thermostats
UB 20(-D), UB 25, UB 50, UB 30, UB 40
UB 20 F, UB 20 J, UB 30 J, UB 40 J, UB 65 J
UB 20 JL, UB 30 JL, UB 40 JL
YATE0013 /10.04.02
- 52 -
The current range selection is omitted if the voltage range 0...10 V has been selected in
the previous menu. The display shows the scalings available for selection
L
1
CONFIGURABLE=1
L
2
analog output_
By pressing the key
(SHIFT ON) the pre-set scalings are displayed consecutively.
The selection is made by input of the appropriate code (SHIFT OFF).
Configurable means that the temperature range required to correspond to the voltage
range 0...10 V, current range 0...20 mA or 4...20 mA can be determined by setting the
range start (T
min
) and the range end (T
max
).
The display shows
L
1
CONFIGURABLE=1
L
2
T
min
=_ . °C
Example: range 20...220°C
Input 0, 2, 0, 0, 0
. The display shows
L
2
T
max
=_ . °C
Input 2, 2, 0, 0, 0
.
The following fixed scalings are available:
-200...400°C = 0...6 V = 10 mV/K
0°C = 2 V Code 2
-100...400°C = 0...10 V or 0...20 mA or 4...20 mA Code 3
0...100°C = 0...10 V or 0...20 mA or 4...20 mA Code 4
The display then shows
L
2
T
i
T
1
T
2
T
S
0-3_
E.g. to set the bath temperature on channel 1 input 0
.
Similarly for the temperature signal of the external Pt 100 T
1
input 1
etc.
The display then returns to the standard display.