80 / 137
Proline Kryomats
Weekplan
Arrange
takes you to the
window shown on the left.
Using the cursor keys
,
select the field,
which is to be filled in.
Open the input dialog of the field with
: Select a time in the time fields and an
action in the action field.
In the example on the right, the thermostat is
started on Monday at 7:30h, Program 4 is
executed at 10:00h on Tuesday and the
standby mode is switched in on Friday at
16:00h. Fields displaying ------ are passive.
Confirm each field selection with
or quit
with without making changes.
The menu
Action
is used to define what is to be
carried out:
Start
activates the thermostat from the
standby mode.
Standby
activates the standby mode
(refrigerating unit, heater and pump are
switched off).
Program X
all actions of this program defined
in the programmer are processed.
7.11
Control parameters
The control parameters are optimized ex-works for operation as a bath thermostat (with water as the bath medium)
with internal control. The parameters are also preset for the operation of external containers with external control.
Sometimes however, the operation of external containers requires adaptation. In addition, the thermal capacity and
viscosity of the heat transfer liquid sometimes require adaptation.
The intelligent menu guidance with the Master control elemant and Command remote control
detects whether you have set the device (as described in Section 7.5.4), to internal or external
control and only displays, the relevant dialog boxes in each case.
Your Proline Kryomat automatically optimizes some control parameters. This automatic
mechanism should only be deactivated and manually optimized in exceptional cases.
Pump Menu
End
T
set
T
fix
Start
Standby
Program 1
Program 2
Program 3
Program 4
Program 5
Status
Function
Action
Set time
Set date
Weekplan
Time Action Time Action
Monday
07:30 Start
17:00 -------
Tuesday
10:00 Prog.4 17:00 -------
Wednesday 08:00 -------
17:00 -------
Thursday
08:00 -------
17:00 -------
Friday
08:00 -------
16:00 Standby
Saturday
08:00 -------
17:00 -------
Sunday
08:00 -------
17:00 -------
Pump Menu
End
T
set
T
fix
Содержание RP 3090 C
Страница 130: ...130 137 Proline Kryomats 03 2022 12 Declaration of conformity and product returns declaration ...
Страница 131: ...03 2022 Proline Kryomats 131 137 ...
Страница 134: ...134 137 Proline Kryomats 03 2022 ...
Страница 135: ......