4.2 External consuming unit
4.2.1 Hoses
CAUTION!
Risk of heat transfer liquid escaping during operation due to the
use of unsuitable hoses
Cold burns
Use hoses with a temperature resistance corresponding to
the operating temperature range of the device.
CAUTION!
Contact with cold hoses
Cold burns
Use insulated hoses for temperatures below 0 °C.
The hoses described below can be used for all heat transfer liquids
approved for the devices.
You will find further information on the pump connections of
the individual devices in
Chapter 11.4 “Hydraulic circuit”
.
Table 3: Hoses, non-insulated
Type
Hose
nozzle
Maximum permissible
pressure
Clear Ø in
mm
Outer
diameter in
mm
Tem-
perature
range in °C
Catalog
number
EPDM hose
10 mm
Devices with a maximum
pump pressure of < 1 bar
9
11
10 – 90
RKJ 111
EPDM hose
½
" (13 mm) Devices with a maximum
pump pressure of < 1 bar
12
14
10 – 90
RKJ 112
Rubber hose with fabric
reinforcement
½
" (13 mm)
up to 10 bar
13 (
½
")
19
-40 – 100
RKJ 031
Rubber hose with fabric
reinforcement
¾
" (19 mm)
up to 10 bar
19 (
¾
")
27
-40 – 100 RKJ 032
Approved hoses, adapters and hose clips
V07
Microcool
23 / 57