Figure 45 Choosing the Coolant
Customer Configurable Alarms
Figure 46 Setpoint Alarms
Alarms such as Coolant Supply Pressure, Low Temperature
Δ
and High Temperature
Δ
can be set in
the Setting Menu Each Alarm can be turned ON or OFF as required and the value can be changed by
clicking on the number.
Coolant supply pressure
This secondary coolant supply pressure alarm is disabled by default. If the customer doesn’t enable
this alarm, then the unit would shut off according to the primary high coolant supply pressure value
specified in
. If this alarm is enabled, the default value is 5 bar for this.
Figure 47 Coolant Supply Pressure
Low temp delta
This alarm is to alert the customer if the coolant supply temperature doesn’t come within this specified
deltaT from below the set point in a set amount of time. This alarm is disabled by default. If the
customer enables this alarm, then the default value of delta T is 1 and default time is 30 minutes.
Содержание Nextreme NRC1200 Series
Страница 1: ...Nextreme Recirculating Chiller Specification and User Manual Part Number 387004848 ...
Страница 17: ...17 Component Locations Figure 2 Isometric Views of Unit Figure 3 Top View ...
Страница 18: ...18 Figure 4 Front View Figure 5 Rear View Figure 6 Side View ...
Страница 37: ...37 Figure 21 Refrigerant Circuit and Coolant Circuit Figure 22 Coolant Circuit and Control Panel ...
Страница 39: ...39 Figure 25 Sensor Wiring Low Voltage ...
Страница 40: ...40 Plumbing Refrigeration Diagram Figure 26 Plumbing and Refrigeration Diagram ...
Страница 43: ...43 Figure 31 Pump Performance of NRC5000 with Cooling Fluids Water and 40 EG W ...
Страница 60: ...60 PCFLT Returns FLT fault or NO FAULTS FOUND PCFLT C Clears Fault Returns FLT Faults Cleared ...
Страница 69: ...69 Declaration of Conformity ...