13 • OPERATING AT THE RATED HEAT OUTPUT
CHECKING NOMINAL HEAT CAPACITY
N
AGB.... - NAGV.... - ARGN....
N
AGB....R - NAGV....R - ARGN....R
Check the depth of the screw
“A”
in
accordance with
table 5
of the
“Tecnical gas
data”
booklet, using a gauge.
Access the settings page for the burner to be
checked:
Check that the burner fan speed, corresponds
to the data given in table 5 of the “Technical
gas data” booklet.
Set 180°C convection cooking, operating with
“MIN” and “MAX” speeds and with the doors
open.
Check the combustion,
CO (ppm)
and
CO2
(%)
values, with an appropriate instrument.
Start the oven working, with the door open,
and wait for approximately 5 minutes.
Position the flue gas collection probe in the
flue gas outlet pipe (chamber and boiler).
The
CO
2
must be for:
Natural gas between 9% and 10.5%
L.P.G.
between 9% and 13%
The
CO
must be no greater than
300 ppm
(measured).
If these readings are outside the ranges,
proceed as stated in the technical manual.
For the conversion from natural gas to LPG,
or vice versa, proceed as described in the
technical manual.
- Boiler Burner
Repeat these operations, setting 130°C steam
cooking (also with door closed).
Conversion: As mentioned above, every appliance is factory set to burn the type of gas
specified, it may become necessary nonetheless to convert the appliance from one type of gas
to another. Therefore, only personnel authorized by the company and belonging to the technical
service who have the corresponding technical handbook can do this work.