BA_084_2019-05_10.00 Temperature transmitter clamp-on
Page 5/20
3.3 Electrical Connection
Complete the mechanical installation before you connect the device electrically.
Set up all electrical connections while the voltage supply is switched off.
Output (2-wire)
4...20 mA (20...4 mA)
Permissible supply voltage
U
V
= 12…30 VDC
Permissible load
R
B
≤ (U
V
- 12 V) / 22 mA
Circular connector M12
Cable gland
Figure 4: Options for the electrical connection
Pay attention to the following points regarding electrical connections via cable gland:
The display can be dismounted as described in Chapter 3.2. Use a small screwdriv-
er to press the spring of the terminal block completely downwards before inserting
the cable. Otherwise, it is not possible to ensure a safe electrical connection.
Do not forget to tighten the cable gland after the electrical connection is finalised.
3.4 Device orientation
The case can be turned in relation to the process connection as well as the display in rela-
tion to the case.
Turning the case in relation to the process connection (±170°) allows to choose the posi-
tion of the electrical connection. Turning the display in relation to the case allows to
choose the viewing angle independently of the position of the electrical connection.
3.5 Adjustment of the Display Contrast
The display contrast can be adjusted.
Press and hold the ESC key and use the arrow keys to adapt the contrast.
The setting is saved and the contrast screen closes as soon as the ESC key is released.