6.4.3.1 

Upper and lower adjustment 

The  lower  adjustment  results  in  an  offset  of  the  characteristic  curve.  It  thus  affects  the 
measuring range. 

The upper adjustment changes the slope of the characteristic curve by correcting the span 
of the measuring range. 

Execute the lower adjustment prior to the upper adjustment for a correct full adjustment.  

  

 

Figure 11: Effect of the upper and lower adjustment on the characteristic curve 

  

You can perform the upper and lower adjustment at any reference temperature level. For 
instance, you can perform the lower adjustment of a -

40…150 °C device at 0 °C. The ref-

erence temperature level for the upper offset can also be freely chosen. To ensure that the 
adjustment is as precise as possible, the upper and lower adjustment should be performed 
as close as possible to the lower range value and upper range value of the measurement 
ranges. 

  

6.4.3.2 

Current adjustment 

You  can  use  the  current  adjustment,  if  the  reading  at  the end  of  the measurement  chain 
(re-converted  current  value)  does  not  correspond  to  the  measured  pressure.  With  this 
function  you  can  compensate  deviations  in  the  output  stage  as  well  as  the  downstream 
measurement chain. 

Proceed as follows (example for 4 mA): 

  

  Select function "Current adjust." 

–> "Adjust. 4 mA" 

  Use "OK" to activate constant current mode (4 mA). CAUTION! The output current 

value now no longer corresponds with the measured value! This is indicated by the 
icon "Function check" (see 6.2.3). 

  Read the displayed current value at the end of the measurement chain. 

  Enter this current value (e.g. 3.996) at the device. The device now corrects the cur-

rent output so that 4 mA are shown at the end of the measurement chain. 

  

When  leaving  the  function,  the  constant  current  mode  is  disabled  and  the  current  value 
corresponds again to the measured value. 

  

Содержание GV4610 Series

Страница 1: ...eneral Safety Notes 2 1 2 Intended Use 2 1 3 Conformity with EU Regulations 2 2 Transportation and Storage 2 3 Installation and Commissioning 2 3 1 Mechanical Installation 2 3 2 Mount Dismount Display...

Страница 2: ...ice certifies its compliance with the applicable EU Directives for placing products on the market within the European Union You find the complete EU Declaration of Conformity document no KE_052 at www...

Страница 3: ...right Mount the clamping block with the included screws at the intended position on the pipe Do not exceed the allowed tightening torque of 2 Nm for pipe diameters up to 17 2 mm and 4 Nm for bigger p...

Страница 4: ...this step Never try to turn the housing if you have a device with field housing or integrated transmitter You might destroy the device by this Do not turn or move the clamping element with a mounted...

Страница 5: ...al block completely downwards before inserting the cable Otherwise it is not possible to ensure a safe electrical connection Do not forget to tighten the cable gland after the electrical connection is...

Страница 6: ...nsert and pipe For further details please consult the separate calibration guideline for the Clamp on family TA_008 4 2 Maintenance Service When properly installed in accordance with applicable specif...

Страница 7: ...on of the device The gen eral functionality of the buttons is identical in all operating modes Figure 5 Control elements If you press and hold the up or down button it will automatically be triggered...

Страница 8: ...value is larger than the displayable number due to setting a fixed decimal point or an inappropriate unit the largest displayable number is shown flashing In this case please select a different settin...

Страница 9: ...ext Write protection in combination with the lock icon Use the same key combination to unlock the menue again 6 2 3 Icons indicating device status In the top right corner of the display depending on t...

Страница 10: ...ain value is shown at the maxi mum size best readability from a dis tance One additional value can also be shown Table 4 Display layouts You can define what information shall be shown in the layout s...

Страница 11: ...by pressing and holding the ESC button for at least one second Figure 7 Navigating the operating menue In long menues and selection lists a scroll bar on the left side shows the position of the curren...

Страница 12: ...ou cancel the entry and go back to view mode The se lected value is not saved With the OK button the selected value is saved Saving the value is confirmed with an in formation window and the new value...

Страница 13: ...it is reached The value is then set to the parameter limit You can set negative numbers by decreasing the value below zero When you press the ESC button you can cancel the entry at any time and return...

Страница 14: ...Quick Setup basic configuration options are combined to make it possible to quickly configure key functions All functions of the quick setup can also be found at another posi tion in the menue tree T...

Страница 15: ...ld be performed as close as possible to the lower range value and upper range value of the measurement ranges 6 4 3 2 Current adjustment You can use the current adjustment if the reading at the end of...

Страница 16: ...are only meant for your orientation The device uses conversion values with ten decimal places Temperature unit The unit in which the temperature is to be shown can be selected from the following list...

Страница 17: ...inverse 6 4 5 2 Setting the measurement range You can freely set the lower and upper range value within the nominal range of the device Please note that when the turndown is increased the measurement...

Страница 18: ...sponds with the short address which is used for the HART Communication It can be set within a range of 0 to 63 Please note that setting the short address between 1 and 63 will not automatically activa...

Страница 19: ...es capital letters and special characters For the selection the characters are arranged in the order shown below From the end of the list special character you are automatically guided back to the sta...

Страница 20: ...BA_084_2019 05_10 00 Temperature transmitter clamp on Page 20 20 6 4 10 Overview with menue tree and device functions...

Отзывы: